ENGINEERING MANUAL
INVERTER-DRIVEN MULTI-SPLIT SYSTEM
HEAT PUMP AIR CONDITIONERS
Engineering Manual
TC-16005
Technical Catalog for Outdoor Unit
< Indoor Units >
●DOAS (Dedicated Outdoor Air System) Type
(H,Y)DOA096B21S
TC-16005-rev.2
i
IMPORTANT NOTICE AND SAFETY SUMMARY
1. Introduction
2. Important Safety Instructions
This manual should be considered as a permanent part of the air conditioning equipment and should
remain with the air conditioning equipment.
(Transportation/Installation Work) > (Refrigerant Piping Work) > (Electrical Wiring Work) > (Ref. Charge Work) > (Test
Run) > (User)
This Engineering Manual concentrates on heat pump air conditioning units. Read this manual carefully
before performing installations or operations.
Signal Words
Indicates a hazardous situation that, if not avoided, could result in death or
serious injury.
Indicates a hazardous situation that, if not avoided, could result in minor or
moderate injury.
Indicates information considered important, but not hazard-related
(for example, messages relating to property damage).
General Precautions
To reduce the risk of serious injury or death, read these instructions
thoroughly and follow all warnings or cautions included in all manuals that
accompanied the product and are attached to the unit. Refer back to these
instructions as needed.
This system should be installed by personnel certied by Johnson Controls, Inc. Personnel must be
qualied according to local, state and national building and safety codes and regulations. Incorrect
installation could cause leaks, electric shock, re or explosion. In areas where Seismic ‘’Performance
requirements are specied, the appropriate measures should be taken during installation to guard
against possible damage or injury that might occur in an earthquake if the unit is not installed
correctly, injuries may occur due to a falling unit.
Use appropriate Personal Protective Equipment (PPE), such as gloves and protective goggles and,
where appropriate, have a gas mask nearby. Also use electrical protection equipment and tools suited
for electrical operation purposes. Keep a wet cloth and a re extinguisher nearby during brazing. Use
care in handling, rigging, and setting of bulky equipment.
When transporting, be careful when picking up, moving and mounting these units. Although the
unit may be packed using plastic straps, do not use them for transporting the unit from one location
to another. Do not stand on or put any material on the unit. Get a partner to help, and bend with
your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum ns on the air
conditioner can cut ngers, so wear protective gloves.
Do not touch or adjust any safety devices inside the indoor or outdoor units. All safety features,
disengagement, and interlocks must be in place and functioning correctly before the equipment is
put into operation. If these devices are improperly adjusted or tampered with in any way, a serious
accident can occur. Never bypass or jump-out any safety device or switch.
Johnson Controls will not assume any liability for injuries or damage caused by not following steps
outlined or described in this manual. Unauthorized modications to Johnson Controls products are
prohibited as they…
May create hazards which could result in death, serious injury or equipment damage.
Will void product warranties.
May invalidate product regulatory certications.
May violate OSHA standards.
ii
TC-16005-rev.2
Take the following precautions to reduce the risk of property damage.
Be careful that moisture, dust, or variant refrigerant compounds not enter the refrigerant cycle during
installation work. Foreign matter could damage internal components or cause blockages.
If air lters are required on this unit, do not operate the unit without the air lter set in place. If the air
lter is not installed, dust may accumulate and breakdown may result.
Do not install this unit in any place where silicon gases can coalesce. If the silicon gas molecules
attach themselves to the surface of the heat exchanger, the nned surfaces will repel water. As a
result, any amount of drainage moisture condensate can overow from the condensate pan and could
run inside of the electrical box, possibly causing electrical failures.
When installing the unit in a hospital or other facility where electromagnetic waves are generated
from nearby medical and/or electronic devices, be prepared for noise and electronic interference
Electromagnetic Interference (EMI). Do not install where the waves can directly radiate into the
electrical box, controller cable, or controller. Inverters, appliances, high-frequency medical equipment,
and radio communications equipment may cause the unit to malfunction. The operation of the unit
may also adversely affect these same devices. Install the unit at least 10 ft. (approximately 3m) away
from such devices.
When a wireless controller is used, locate at a distance of at least 3.3 ft. (approximately 1m) between
the indoor unit and electric lighting. If not, the receiver part of the unit may have difculty receiving
operation commands.
Do not install the unit in any location where animals and plants can come into direct contact with the
outlet air stream. Exposure could adversely affect the animals and plants.
Do not install the unit with any downward slope to the side of the condensate pipe. If you do, you may
have drain water owing back which may cause leaks.
Be sure the condensate hose discharges water properly. If connected incorrectly, it may cause leaks.
Do not install the unit in any place where oil can seep onto the units, such as table or seating areas in
restaurants, and so forth. For these locations or social venues, use specialized units with oil-resistant
features built into them. In addition, use a specialized ceiling fan designed for restaurant use. These
specialized oil-resistant units can be ordered for such applications. However, in places where large
quantities of oil can splash onto the unit, such as a factory, even the specialized units cannot be used.
These products should not be installed in such locations.
If the wired controller is installed in a location where electromagnetic radiation is generated, make
sure that the wired controller is shielded and cables are sleeved inside conduit tubing.
If there is a source of electrical interference near the power source, install noise suppression
equipment (lter).
During the test run, check the unit’s operation temperature. If the unit is used in an environment
where the temperature exceeds the operation boundary, it may cause severe damage. Check the
operational temperature boundary in the manual. If there is no specied temperature, use the unit
within the operational temperature boundary of 32 to 104°F (0 to 40°C).
Read installation and appropriate user manuals for connection with PC or peripheral devices. If a
warning window appears on the PC, the product stops, does not work properly or works intermittently,
immediately stop using the equipment.
TC-16005-rev.2
iii
Installation Precautions
To reduce the risk of serious injury or death, the following installation
precautions must be followed.
When installing the unit into…
A wall: Make sure the wall is strong enough to hold the unit’s weight. It may be necessary to
construct a strong wood or metal frame to provide added support.
A room: Properly insulate any refrigerant tubing run inside a room to prevent “sweating” that can
cause dripping and water damage to wall and oors.
Damp or uneven areas: Use a raised concrete pad or concrete blocks to provide a solid, level
foundation for the unit to prevent water damage and abnormal vibration.
An area with high winds: Securely anchor the outdoor unit down with bolts and a metal frame.
Provide a suitable wind bafe.
A snowy area: Install the outdoor unit on a raised platform that is higher than drifting snow.
Provide snow protection hood.
If the remote sensors are not used with this controller, then do not install this controller…
in a room where there is no thermostat.
where the unit is exposed to direct sunshine or direct light.
where the unit will be in close proximity to a heat source.
where hot/cold air from the outdoors, or a draft from elsewhere (such as air vents, diffusers or
grilles) can affect air circulation.
in areas with poor air circulation and ventilation.
Do not install the unit in the following places. Doing so can result in an explosion, re, deformation,
corrosion, or product failure.
Explosive or ammable atmosphere.
Where re, oil, steam, or powder can directly enter the unit, such as in close proximity or directly
above a kitchen stove.
Where oil (including machinery oil) may be present.
Where corrosive gases such as chlorine, bromine, or sulde can accumulate, such as near a hot
tub or hot spring.
Where dense, salt-laden airow is heavy, such as in coastal regions.
Where the air quality is of high acidity.
Where harmful gases can be generated from decomposition.
Do not position the condensate pipe for the indoor unit near any sanitary sewers where corrosive
gases may be present. If you do, toxic gases can seep into breathable air spaces and can cause
respiratory injuries. If the condensate pipe is installed incorrectly, water leakage and damage to the
ceiling, oor, furniture, or other possessions may result. If condensate piping becomes clogged,
moisture can back up and can drip from the indoor unit. Do not install the indoor unit where such
dripping can cause moisture damage or uneven locations: Use a raised concrete pad or concrete
blocks to provide a solid, level foundation for the unit to prevent water damage and abnormal
vibration.
Before performing any brazing work, be sure that there are no ammable materials or open ames
nearby.
Perform a test run to ensure normal operation. Safety guards, shields, barriers, covers, and protective
devices must be in place while the compressor/unit is operating. During the test run, keep ngers and
clothing away from any moving parts.
Clean up the site when nished, remembering to check that no metal scraps or bits of wiring have
been left inside the unit being installed.
During transportation, do not allow the backrest of the forklift make contact with the unit, otherwise,
it may cause damage to the heat exchanger and also may cause injury when stopped or started
suddenly.
Remove gas inside the closing pipe when the brazing work is performed. If the brazing ller metal is
melted with remaining gas inside, the pipes will be blown off and it may cause injury.
Be sure to use nitrogen gas for an airtight test. If other gases such as oxygen gas, acetylene gas or
uorocarbon gas are accidentally used, it may cause explosion or gas intoxication.
After installation work for the system has been completed, explain the “Safety Precautions,” the proper use
and maintenance of the unit to the customer according to the information in all manuals that came with the
system. All manuals and warranty information must be given to the user or left near the Indoor Unit.
iv
TC-16005-rev.2
Refrigerant Precautions
To reduce the risk of serious injury or death, the following refrigerant
precautions must be followed.
As originally manufactured, this unit contains refrigerant installed by Johnson Controls. Johnson
Controls uses only refrigerants that have been approved for use in the unit’s intended home country
or market. Johnson Controls distributors similarly are only authorized to provide refrigerants that
have been approved for use in the countries or markets they serve. The refrigerant used in this unit
is identied on the unit’s faceplate and/or in the associated manuals. Any additions of refrigerant into
this unit must comply with the country’s requirements with regard to refrigerant use and should be
obtained from Johnson Controls distributors. Use of any non-approved refrigerant substitutes will void
the warranty and will increase the potential risk of injury or death.
If installed in a small room, take measures to prevent the refrigerant from exceeding the maximum
allowable concentration in the event that refrigerant gases should escape. The installation should
meet the requirements in ASHRAE Standards 15 and 34. If refrigerant gas has leaked during the
installation work, ventilate the room immediately.
Check the design pressure for this product is 601 psi (4.15MPa). The pressure of the refrigerant
R410A is 1.4 times higher than that of the refrigerant R22. Therefore, the refrigerant piping for
R410A shall be thicker than that for R22. Make sure to use the specied refrigerant piping. If not, the
refrigerant piping may rapture due to an excessive refrigerant pressure. Besides, pay attention to
the piping thickness when using copper refrigerant piping. The thickness of copper refrigerant piping
differs depending on its material.
The refrigerant R410A is adopted. The refrigerant oil tends to be affected by foreign matters such
as moisture, oxide lm, (or fat). Perform the installation work with care to prevent moisture, dust, or
different refrigerant from entering the refrigerant cycle. Foreign matter can be introduced into the cycle
from such parts as expansion valve and the operation may be unavailable.
To avoid the possibility of different refrigerant or refrigerant oil being introduced into the cycle, the
sizes of the charging connections have been changed from R407C type and R22 type. It is necessary
to prepare the appropriate tools before performing installation work.
Use refrigerant pipes and joints which are approved for use with R410A.
A compressor/unit comprises a pressurized system. Never loosen threaded joints while the system is
under pressure and never open pressurized system parts.
Before installation is complete, make sure that the refrigerant leak test has been performed. If
refrigerant gases escape into the air, turn OFF the main switch, extinguish any open ames and
contact your service contractor. Refrigerant (Fluorocarbon) for this unit is odorless. If the refrigerant
should leak and come into contact with open ames, toxic gas could be generated. Also, because the
uorocarbons are heavier than air, they settle to the oor, which could cause asphyxiation.
When installing the unit, and connecting refrigerant piping, keep all piping runs as short as
possible, and make sure to securely connect the refrigerant piping before the compressor starts
operating. If the refrigerant piping is not connected and the compressor activates with the stop
valve opened, the refrigerant cycle will become subjected to extremely high pressure, which can
cause an explosion or re.
Tighten the are nut with a torque wrench in the specied manner. Do not apply excessive force to the
are nut when tightening. If you do, the are nut can crack and refrigerant leakage may occur.
When maintaining, relocating, and disposing of the unit, dismantle the refrigerant piping after the
compressor stops.
When pipes are removed out from under the piping cover, after the insulation work is completed,
cover the gap between the piping cover and pipes by a packing (eld-supplied). If the gap is not
covered, the unit may be damaged if snow, rain water or small animals enter the unit.
Do not apply an excessive force to the spindle valve at the end of opening. Otherwise, the spindle
valve ies out due to refrigerant pressure. At the test run, fully open the gas and liquid valves,
otherwise, these devices will be damaged. (It is closed before shipment.)
If the arrangement for outdoor units is incorrect, it may cause owback of the refrigerant and result in
failure of the outdoor unit.
The refrigerant system may be damaged if the slope of the piping connection kit exceeds +15
o
.
TC-16005-rev.2
v
Electrical Precautions
Take the following precautions to reduce the risk of electric shock, re or
explosion resulting in serious injury or death.
Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram
and these instructions when wiring. Improper connections and inadequate grounding can cause
serious injury or death.
Perform all electrical work in strict accordance with this installation and maintenance manual and all
the relevant regulatory standards.
Before servicing, open and tag all disconnect switches. Never assume electrical power is
disconnected. Check with meter and equipment.
Only use electrical protection equipment and tools suited for this installation.
Insulate a wired controller against moisture and temperature extremes.
Use specied cables between units.
The new air conditioner may not function normally in the following instances:
If electrical power for the new air conditioner is supplied from the same transformer as the
external equipment* referred to below.
If the power source cables for this external equipment* and the new air conditioner unit are
located in close proximity to each other.
external equipment*: (Example): A lift, container crane, rectier for electric railway, inverter
power device, arc furnace, electric furnace, large-sized induction motor and large-sized
switch.
Regarding the cases mentioned above, surge voltage may be inducted into the power supply
cables for the packaged air conditioner due to a rapid change in power consumption of the device
and an activation of a switch.
Check eld regulations and standards before performing electrical work in order to protect the
power supply for the new air conditioner unit.
Communication cabling shall be a minimum of AWG18 (0.82mm
2
), 2-Conductor, Stranded Copper.
Shielded cable must be considered for applications and routing in areas of high EMI and other
sources of potentially excessive electrical noise to reduce the potential for communication errors.
When shielded cabling is applied, proper bonding and termination of the cable shield is required
as per Johnson Controls guidelines. Plenum and riser ratings for communication cables must be
considered per application and local code requirements.
The polarity of the input terminals is important, so be sure to match the polarity when using contacts
that have polarity.
Use an exclusive power supply for the air conditioner at the unit’s rated voltage.
Highly dangerous electrical voltages may be used in this system. Carefully refer to the wiring diagram
and these instructions when wiring. Improper connections and inadequate grounding can cause
serious injury or death.
Before installing the controller or remote devices, ensure that the indoor and outdoor unit operation
has been stopped. Further, be sure to wait at least ve minutes before turning off the main power
switch to the indoor or outdoor units. Otherwise, water leakage or electrical breakdown may result.
Do not open the service cover or access panel to the indoor or outdoor units without turning OFF the
main power supply. Before connecting or servicing the controller or cables to indoor or outdoor units,
open and tag all disconnect switches. Never assume electrical power is disconnected. Check with a
meter and equipment.
This equipment can be installed with a Ground Fault Circuit Breaker (GFCI), which is a recognized
measure for added protection to a properly grounded unit. Install appropriate sized breakers / fuses
/ overcurrent protection switches, and wiring in accordance with local, state and NEC codes and
requirements. The equipment installer is responsible for understanding and abiding by applicable
codes and requirements.
vi
TC-16005-rev.2
- CONTENTS -
1. General Information (Features) .................................................................................................................. 1-1
2. DOAS (Dedicated Outdoor Air System) Type ............................................................................................ 2-1
2.1 Unit Nomenclature ............................................................................................................................. 2-1
2.2 Line-up .............................................................................................................................................. 2-1
2.3 General Data ..................................................................................................................................... 2-2
2.4 Dimensional Data .............................................................................................................................. 2-3
2.5 Structure ............................................................................................................................................ 2-5
2.6 Component Data ............................................................................................................................... 2-6
2.7 Operation Space ............................................................................................................................... 2-7
2.8 Fan Performance ............................................................................................................................... 2-8
2.9 Electrical Data ................................................................................................................................... 2-9
2.10 Sound Data ....................................................................................................................................... 2-10
2.11 Control System .................................................................................................................................. 2-11
2.11.1 Refrigerant System .................................................................................................................. 2-11
2.11.2 Operating Temperature Range ................................................................................................ 2-12
2.11.3 Control Temperature ................................................................................................................ 2-13
2.11.4 Standard Operation Sequence ................................................................................................ 2-14
2.11.5 Safety and Control Device Setting ........................................................................................... 2-16
2.11.6 Wiring Diagram ........................................................................................................................ 2-17
3. Optional Parts ............................................................................................................................................ 3-1
3.1 Line Up .............................................................................................................................................. 3-1
3.2 Seismic Suspension Bracket: SSB-IDH-01 ....................................................................................... 3-2
3.2.1 Applicable Unit ......................................................................................................................... 3-2
3.2.2 Installation Work ...................................................................................................................... 3-2
3.2.3 Seismic Suspension Bracket Installation Procedures.............................................................. 3-2
3.3 Infrared (IR) Receiver Kit: CWDIRK01 .............................................................................................. 3-3
3.3.1 Specications ........................................................................................................................... 3-3
3.3.2 Dimensions .............................................................................................................................. 3-3
3.3.3 Applicable Models .................................................................................................................... 3-3
3.3.4 Accessories / Options .............................................................................................................. 3-4
3.3.5 Installation ................................................................................................................................ 3-4
3.3.6 Electrical Wiring ....................................................................................................................... 3-7
3.3.7 Setting DIP Switches on Indoor Unit Side ............................................................................... 3-7
3.3.8 Setting DIP Switch on IR Receiver Kit Side ............................................................................. 3-8
3.3.9 Identifying Indoor Units Installed in a Side-by-Side Operation ................................................ 3-9
3.3.10 Simultaneous Operation .......................................................................................................... 3-10
3.3.11 Test Run by Wireless Controller (CIR01) ................................................................................. 3-12
3.3.12 Alarm Indication ....................................................................................................................... 3-12
3.4 3P Connector Cable: PCC-1A ........................................................................................................... 3-13
3.5 Remote Sensor: THM-R2A ................................................................................................................ 3-13
3.6 Relay and 3 Pin Connector Kit: PSC-5RA ......................................................................................... 3-14
4. Selection Data ............................................................................................................................................ 4-1
4.1 Selection Guide ................................................................................................................................. 4-1
4.2 Capacity Table ................................................................................................................................... 4-3
4.2.1 Cooling Capacity ...................................................................................................................... 4-3
4.2.2 Heating Capacity ..................................................................................................................... 4-3
IMPORTANT NOTICE AND SAFETY SUMMARY ......................................................................................... i
1. Introduction ................................................................................................................................................ i
2. Important Safety Instructions ..................................................................................................................... i
FEATURES
TC-16005-rev.2
1-1
1. General Information (Features)
VRF Air Conditioners
Johnson Controls proudly introduces new Variable Refrigerant Flow (VRF) air conditioners, a highly-efcient
and reliable air-conditioning system. Recently, increased numbers of buildings are requiring "Intelligent"
facilities that include communication networks, ofce automation, and a comfortable environment. In
particular, a comfortable environment is becoming more of a year-around requirement in ofce buildings.
The VRF multi-split system air conditioner meets these requirements. The proven combination of the scroll
compressor and inverter provides the best air conditioning for small and medium ofce buildings.
VRF System
Johnson Controls has developed the VRF system with its customers in mind.
This system, which is unique in the world, allows the interconnection of indoor units for all our VRF air
conditioners.
This system provides the consumer with greater exibility for installation, which means that the air-
conditioning systems will integrate better within complex facility structures.
Two Control Mode
Depend on the installation environment and the purpose of use, the DOAS control system can be chosen
from two options.
< Indoor Temperature Control >
In this mode, the control system bring the room atmosphere temperature closer to the set point
temperature of the wired controller, using a temperature sensor (remote sensor or thermistor in the
wired controller) mounted in the room.
[Advantage]
When using an indoor temperature sensor, the system will be able to control the temperature in
collaboration with other indoor units.
Temperature Set Point Range of Wired Controller: Cooling . 66
o
F (19
o
C) ~ 86
o
F (30
o
C)
Heating . 62
o
F (17
o
C) ~ 86
o
F (30
o
C)
Outlet
OutletOutlet
Remote Sensor
(Accessory)
Wired
Controller
(Optional Part)
Intake
(Outdoor
Air)
Indoor Unit
Intake
Exhaust
Outdoor Unit
DOAS
Comfortable Air Conditioning Environment
Fresh air intake is realized while suppressing the air conditioning load by cooling or heating outdoor air.
FEATURES
1-2
TC-16005-rev.2
High External Static Pressure
Flexible duct installation due to the high external static pressure capability.
Constant Air Volume Mode
Constant air volume mode is available for the unit in order to keep the air velocity constant during defrosting
or hot start operation.
Even when combined with a ventilation fan, air supply and exhaust are balanced by this constant air volume
mode. (Settings are available using the optional function setting in the wired controller.)
NOTE:
During the defrosting operation and start of the heating operation, airow temperature will be decreased.
Carefully consider the installation location and direction of the air outlet.
Note that, when the air outlet temperature is 19.4
o
F (-7
o
C) or less, heating operation is stopped.
Flexible Layout when Using a Drain Pump
DOAS Unit
Max. Drain-Up Length
23-5/8 inches (600mm)
Unit Undersurface
Outlet
OutletOutlet
Outdoor Unit
for DOAS Unit
Outlet Air
Thermistor
Wired
Controller
(Optional Part)
Intake
(Outdoor
Air)
Indoor Unit
Intake
Exhaust
Outdoor Unit
DOAS
< Outlet Air Temperature Control >
In this mode, the control system bring the outlet temperature closer to the setting temperature of the
wired controller, using an outlet air thermistor in the unit.
[Advantage]
When it is set introduce outdoor air, the system enable intake of fresh air without impacting the room
temperature.
Temperature Set Point Range of Wired Controller: Cooling . 56
o
F (13
o
C) ~ 77
o
F (25
o
C)
Heating . 66
o
F (19
o
C) ~ 86
o
F (30
o
C)
FEATURES
TC-16005-rev.2
1-3
Operation Range
NOTES:
1. The above gure shows the sensed temperature of inlet air thermistor for the DOAS unit.
2. When the outdoor air intake temperature is 32
o
F DB (0
o
C DB) or less, the heating operation is started for
freeze protection of the heat exchanger.
However, when the condition is such that the heating operation is not available, the operation is stopped.
3. When the outdoor air intake temperature is 19.4
o
F DB (-7
o
C DB) or less, the heating operation is stopped for
protection of the heat exchanger from freezing and/or a cold draft.
In addition, even when it is within the operation range, the operation might be stopped for unit protection.
4. During the heating operation, when the outdoor air intake temperature is 59
o
F DB (15
o
C DB) or more, the
operation is changed to fan operation.
5. When starting the heating operation or defrosting operation, the fan function is stopped by setting the optional
function setting in the wired controller. Constant air volume mode is available in order to keep the air speed
constant. (If it is in abnormal condition, the fan function will stop.) Refer to the Service Manual for details.
6. During cooling operation, when the outdoor air intake temperature is 68
o
F DB (20
o
C DB) or less, the operation
is changed to fan operation.
When the outdoor air intake temperature is 109.4
o
F DB (43
o
C DB) or more, the fan operation can continue,
though the alarm might be stopped by increasing pressure due to being out of operation range.
In addition, when the outdoor air intake temperature is high (approx. 104
o
F DB (40
o
C DB) or more) or low
(approx. 73.4
o
F DB (23
o
C DB) or less) the cooling operation and the fan operation might be alternated for unit
protection.
Heating Operation
Available Range
Outdoor Air Intake Temperature [
o
F DB (
o
C DB)]
19.4
(-7)
23
(-5)
32
(0)
41
(5)
50
(10)
59
(15)
68
(20)
86
(30)
95
(35)
104
(40)
109.4
(43)
77
(25)
Fan
Operation
Cooling Operation
Available Range
DOAS
TC-16005-rev.2
2-1
2. DOAS (Dedicated Outdoor Air System) Type
2.1 Unit Nomenclature
Model Descriptions
Example
H DOA 096 B 2 1 S
Nomenclature Description
H = Hitachi Brand
Y = York Brand
H
DOA = Dedicated Outdoor Air System DOA
Capacity (MBH) 096
Refrigerant Type
B = R410A
B
Voltage
2 = 208/230Volts - 1Phase - 60Hz
2
1 = 1st Generation 1
S = Standard Type S
2.2 Line-up
Type
Capacity
Model
RT MBH
Indoor Unit DOAS 8.0 96 (H,Y)DOA096B21S
DOAS
2-2
TC-16005-rev.2
2.3 General Data
NOTES:
*1. Outlet Air Temperature Control
A control system to bring the outlet temperature closer to the set point temperature of the wired controller, using an outlet
air thermistor of the unit.
Nominal capacity (outlet air temperature control) is based on combination with VRF system and following conditions:
Cooling Operation Conditions Heating Operation Conditions
Outdoor Temperature: 91°F DB (33.0°C DB) Outdoor Temperature: 32°F DB (0°C DB)
82°F WB (28.0°C WB) 27°F WB (-2.9°C WB)
Discharge Set Temperature: 61°F DB (16.0°C DB) Discharge Set Temperature: 72°F DB (22.0°C DB)
Piping Length: 24.6 ft. (7.5m) Piping Lift: 0 ft. (0m)
*2. Indoor Temperature Control
A control system to bring the room atmosphere temperature closer to the set point temperature of the wired controller,
using a temperature sensor (remote sensor or thermistor in wired controller) mounted to any place in the room.
Nominal capacity (indoor temperature control) is based on combination with VRF system and following conditions:
Cooling Operation Conditions Heating Operation Conditions
Outdoor Temperature: 91°F DB (33.0°C DB) Outdoor Temperature: 32°F DB (0°C DB)
82°F WB (28.0°C WB) 27°F WB (-2.9°C WB)
Indoor Temperature: 81°F DB (27.0°C DB) Indoor Temperature: 68°F DB (20.0°C DB)
Piping Length: 24.6 ft. (7.5m) Piping Lift: 0 ft. (0m)
*3. The sound pressure level is based on the following conditions.
4.9 ft. (1.5m) beneath the units.
The above data is measured in an anechoic chamber so that reected sound should be taken into consideration in the
eld.
Indoor Unit Type
Model (H,Y)DOA096B21S
Indoor Unit Power Supply
Outlet Air Temperature Control *1
Nominal Cooling Capacity Btu/h
(kW)
Nominal Heating Capacity Btu/h
(kW)
Indoor Temperature Control *2
Nominal Cooling Capacity Btu/h
(kW)
Nominal Heating Capacity Btu/h
(kW)
dB
Outer Dimensions
Height in. (mm) 19-1/8 (486)
Width in. (mm) 50 (1270)
Depth in. (mm) 44-1/8 (1120)
Net Weight lbs (kg) 247 (112)
Refrigerant
Indoor Fan
Airflow Rate cfm
(
m
3
/min
)
External Pressure (208/230V)
High Pressure in.W.G (Pa) 1.06/1.24 (265/310)
Standard in.W.G (Pa)
Motor Nominal Output W 402 (201 x 2 pcs)
Min Circuit Amps A 4.3
Maximum Fuse Amps A 15
Connections
Refrigerant Piping
Liquid Line in. (mm) 3/8 (9.52)
Gas Line in. (mm) 7/8 (22.20)
Condensate Drain VP25
OD in. (mm) 1-1/4 (32)
ID in. (mm) 1 (25)
(17.6)
DOAS
AC 1Phase, 208/230V, 60Hz
96,000
(28.2)
60,000
96,000
(28.2)
83,600
(24.5)
Sound Pressure Level *3
(Overall A Scale) (208/230V)
50/51
R410A
1236
(35.0)
-
Brazed
DOAS
TC-16005-rev.2
2-3
2.4 Dimensional Data
Unit: inch (mm)
Model: (H,Y)DOA096B21S (Produced in 2017 or earlier)
DOAS
2-4
TC-16005-rev.2
Unit: inch (mm)
Model: (H,Y)DOA096B21S (Produced in 2018 or later)
DOAS
TC-16005-rev.2
2-5
2.5 Structure
Unit: inch (mm)
Model: (H,Y)DOA096B21S
19-1/8 (486)
44-1/8 (1120)
7/8 (23)
1-1/8 (28)
1412
4
3
2
1
8
11
16
17
7
6
15
20
19
18
13
9
5
10
50 (1270)
DOAS
2-6
TC-16005-rev.2
2.6 Component Data
Indoor Heat Exchanger and Fan
Tube Material
Outer Diameter
in. (mm)
1/4 (7.0)
Rows
Number of Tube/Coil
Fin Material
Pitch in. (mm) 1/16 (1.6)
psi (MPa) 601 (4.15)
ft
2
(
m
2
)
Number/Unit
Outer Diameter
in.
(mm)
Nominal Airflow cfm
(Hi)
m
3
/min.
)
Starting Method
Nominal Output W
Quantity
Insulation Class (*)
Copper Tube
4
108
Model (H,Y)DOA096B21S
Heat Exchanger Type Multi-Pass Cross Finned Tube
(0.61)
Number of Coil/Unit 1
Aluminum
Maximum Operating Pressure
Total Face Area 6.48
1236
(35.0)
(227)
Indoor Fan Multi-Blade Centrifugal Fan
2
8-15/16
2
F
Indoor Fan Motor Drip-Proof Type Enclosure
PSC (Permanent Split Capacitor)
201
NOTE:
(*) The insulation class means the heat resistant grade of the insulation material based on the IEC standard.
Refer to the IEC 60085 for more information.
DOAS
TC-16005-rev.2
2-7
2.7 Operation Space
Model: (H,Y)DOA096B21S
Unit: inch [mm]
Min. 31-1/2
[800]
5-7/8 to 7-7/8
[150 to 200]
Electrical Control Box
Min. 39-3/
8
[1000]
Min. 39-3/8
[1000]
Min. 23-5/8
[600]
Service Access Door
(Min. 23-5/8 [600]
If the ceiling board can not be detected
for servicing, prepare a service access door below
the indoor unit for removing the indoor unit.
DOAS
2-8
TC-16005-rev.2
2.8 Fan Performance
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

Johnson Controls YDOA096B21S User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI