andrews Fan Flued Range Anode User guide

Type
User guide
Technical Data Sheet Part number B196
Fitting instructions
RFF190, RFF280, RSC150 & RSC190
Water Heaters
B196 CORREX POWERED ANODE KIT
THE INTRODUCTION OF THIS KIT HAS THREE MAIN ADVANTAGES TO BE CONSIDERED:
Low Maintenance Costs (Correx is non-sacricial, therefore no anode maintenance is needed)
Low Running Costs (Less than 35kWH per year)
Increased protection (particularly in areas of low electrical conductivity).
Mains electrical supply wiring to the water heater must be installed in accordance with the current Building Regula-
tions in force and BS7671 - Requirements for Electrical Installations.
is kit is designed to use a 220/240V 1ph 50Hz permanent supply. e fuse rating is 3 Amp.
e method of connection to the mains electrical supply should facilitate complete electrical isolation of the Correx
kit and the appliance. e point of connection to the mains should be readily accessible and adjacent to the appli-
ance.
Step 1 To install the Correx kit (refer to Fig1 & 2 diagrams)
1. Drain down the water heater.
2. Remove the existing hot outlet nipple / anode.
3. Use the ¾” Nipple and Tee provided to t the correx anode into the hot outlet connection.
4. Fix the potentiostat to the heater casing using the retaining bracket provided.
5. Connect the potentiostat output lead onto the anode connection. Achieve this by cutting the lead to the de-
sired length and using the crimp type female connector provided.
6. Remove one heater top cover retaining screw and connect the earth return at this point by cutting the lead to
the desired length and using the crimp type spade connector provided.
7. Connect the potentiostat mains cable to a permanent 220/240V 1ph 50Hz electrical supply via an unswitched
spur outlet (fuse rating 3A).
Step 2 Test the installation
1. Rell the water heater and check for leaks.
2. Switch on the electrical supply to the potentiostat.
3. e green lamp on the potentiostat indicates that the installation is functioning correctly.
4. e red lamp on the potentiostat indicates a fault. Switch off the electrical supply before any work is carried
out.
e installation is now complete.
Please read and understand these instructions before commencing installation and leave this manual with the customer for future reference
Model Qty & Size of Correx Anodes
RFF 190 1 x 800mm
RFF 280 1 x 800mm
RSC 150 1 x 800mm
RSC 190 1 x 800mm
B196 – Anode Fitting Pack Contents
Qty Part
1 E048 – Correx Powered Anodes
1 C995 – Potentiostat
1 C883 – ¾” BSP Equal Tee
1 C247 – ¾” BSP x NPT NIpple
1 E049 – Earth Strap
1 Pack of accessories
RSC150 & RSC190 RFF190 & RFF280
FIG 2
FIG 1
Tel 0345 070 1055 Web andrewswaterheaters.co.uk
MAXXo Condensing Water Heater
PRODUCT SPECIFICATION
Technical Specication
Andrews. Built to perform.
MAXXo Condensing Water Heater | PRODUCT SPECIFICATION
e MAXXo is a range of fully condensing, fully
modulating stainless steel water heaters. Its unique
design offers up to four fully modulating burners.
is offers built-in redundancy for outputs of 60kW
and above, to ensure an uninterrupted, virtually instant
supply of up to 1920 litres per hour of hot water.
It’s available in outputs of 30kW, 60kW, 90kW and 120kW,
and multiple heaters can be installed where even greater
volumes of hot water are required. Each output is available
with tank capacities of 200 or 300 litres.
Features Benets
Up to four modulating burners
Recovery rates of up to 1920 litres of hot water per hour
98% gross efciency
Fully automatic electronic control with Building Management
System (BMS) interface as standard
Built-in high temperature anti-legionella program
WRAS approved and Energy Technology Listed
e optimum amount of gas is used to maximise energy efciency,
cost savings and built-in redundancy for outputs of 60kW and above
Ensures continuous supply of hot water and can satisfy the
most demanding hot water applications
Energy efcient, cost effective operation
Easy integration into the Building Management System
Safety and protection against legionella
Complies with the Water Supply (Water Fittings) Regulations and
Scottish Byelaws and qualies for the Government Enhanced Capital
Allowance scheme
OUTPUT RECOVERY RATE NOx EMISSIONS [0%O
2
]GROSS EFFICIENCY
31-124kW 98%
Up to
1920 l\hr
at
50°C rise
44mg/kWh
All the technical information you need is easy to nd
on our website, using your smart phone, tablet or PC:
-BIM les
-CAD les
-Brochures
-Technical specication sheets
-Case studies
-Installation manuals
-User guides
-Size-It Tool
Registered ofce address: Baxi Heating UK, Coventry Road, Warwick CV34 4LL
Andrews. Built to perform.
Sales
0345 070 1055
Technical
0345 070 1057
Website
andrewswaterheaters.co.uk
Twitter
@AndrewsWH
ICOM
Energy Association
RS 33961
50040 3
November 2016
Customer support
Monday - Friday
8am - 5pm
  • Page 1 1
  • Page 2 2

andrews Fan Flued Range Anode User guide

Type
User guide

Ask a question and I''ll find the answer in the document