Broan PCMMP3 Zoning System Installation guide

Type
Installation guide
Model PCMMP3
PCMMP3 ZONING SYSTEM
3 Zones For Plug-In Damper Motors
1
PCMMP3
ZONING SYSTEM - 3 Zones
Features
Table of Contents
Installation ……………………………………….….…2-3
Operation …………………………………………..…….3
HVAC Equipment Set-Up…………..…………..……….3
Checkout..………………………………………...………3
Wiring ………………………………………………..…3-4
Troubleshooting ………………………………….……4-5
INSTALLATION
The PCMMP3 Plug-In Damper Zoning System-3, Model MMP3, is a
two (2) and three (3) zone control panel for single stage heating
only, cooling only or heating and cooling. The PCMMP3 can control
any single stage gas-oil-electric furnace, hydro-air heating and air
conditioning. The PCMMP3 panel is the central control panel where
all zone dampers, zone thermostats, HVAC Equipment and power
transformer are wired.
When installing the PCMMP3 panel it is important to pick a central
location where it is most convenient to bring all the wires. Most often
this is near the furnace or air handler and closest to power, the
HVAC unit controls and the zone dampers when typically located at
or near the plenum.
The PCMMP3 case and cover are made of sturdy ABS plastic and
can be mounted to any flat surface. It is recommended that the
panel be mounted to a wall or return plenum and NOT on the
furnace or plenum where it will be in contact with the high heating
temperatures. The panel can be located in an attic space or in an
enclosed cabinet of a rooftop unit, provided the panel enclosed and
not in direct exposure to the elements.
2
The cover easily removes from the case by pulling firmly and
separating the cover from the case exposing the circuit board.
There are 4 key-hole mounting points in each corner of the case.
The case has openings in the rear of the case as well as the side for
all wiring. Wiring can come from the back as well as the side in order
to make a neat installation.
OPERATION
The PCMMP3 controls single stage heating and cooling HVAC
Equipment. The PCMMP3 is compatible with any standard single
stage thermostat and setback thermostats as well. The PCMMP3
has various features that make installation and checkout very simple
for all of the board’s functionality.
The PCMMP3’s basic function is zone control. On a call for heating
or cooling, the panel will accept the first call from any zone. Upon
accepting this call the PCMMP3 will keep open the damper(s) to the
zone calling, close the damper(s) to those zones not calling, activate
the needed HVAC controls for heating or cooling, whichever is being
called and not accept any calls for the opposite mode.
Any calls for the opposite mode will be locked out until the initial
mode is either satisfied or a period of time has elapsed that is
sufficient for the first mode to satisfy, a maximum of 20 minutes. A
Patent Pending sequence determines the time the unit has been
running or needs to continue to run in order to adequately provide
conditioning for each mode. If a particular mode has already been
calling for 20 minutes or longer and an opposite call comes in the
PCMMP3 will immediately drop the mode, enter the purge mode in
order to dissipate the conditioned air into the zones calling before
switching over to provide the new conditioning call to its zones.
PURGE TIME
Once a call is satisfied the PCMMP3 drops the call for the heating or
cooling unit controls, whichever was calling and hold the damper(s)
to the zone(s) that were last calling during the Purge Mode. The
Purge mode is nominally 2 minutes and allows the excess
conditioned air in the plenum to be distributed only to the zone(s)
that were last calling. This eliminates the problem of overshooting
the temperature in the satisfied zones.
During the Purge mode the panel can be set to keep the Fan
running during Purge or to let the fan control in the HVAC unit to
control the fan. By using the FIPG (Fan On-In Purge) jumper, on the
top right corner of the control panel, this keeps the fan running until
the Purge mode is over. This mode avoids the fan shutting off during
the Purge mode and coming back on when another zone may be on
constant fan after the Purge Mode is over. This may be more often
used in commercial applications for continuous air circulation (CAC).
In residential applications the fan remaining on, especially in
heating, may be drafty and objectionable.
Once all zone thermostats are satisfied for heating and cooling, the
PCMMP3 can now accept Fan calls allowing Continuous Air
Circulation(CAC) in those zones where the thermostat’s Fan Switch
is set to ON. These zone dampers will be OPEN while the dampers
to the zones where the Fan Switch is set to AUTO will be CLOSED.
When all zone thermostats are satisfied for both Heating and
Cooling, and all Fan switches are set to AUTO position, the HVAC
unit will be off and all zone dampers will return to a normally open
position. Once a zone calls for heating, cooling or fan, the dampers
to the calling zones remain open and the dampers to the zones not
calling will close.
HVAC Equipment Set-Up
The PCMMP3 is factory set for conventional fossil fuel (oil or gas)
single stage heating and cooling. The panel only needs to be
configured when using with a conventional electric furnace or hydro-
air system in order to bring the fan on with a call for heat.
By using the FIH (Fan On-In Heat) jumper, located on the upper
right corner of the board, this allows the Fan to be activated with a
call for heat. Once the heat call is satisfied the fan will shut off as
well, as long as the FIPG jumper is off as well.
Other jumpers on the panel are for NO SENSOR and LOW LIMIT.
The NO SENSOR jumper must be on to jumper the pins when no
sensor is used. The LOW LIMIT jumper is OFF for a Heating limit of
170°F and ON for a higher heating limit temperature 180°F.
CHANGEOVER TIMER
Whenever a call is made for either heating or cooling, the
changeover timer is activated in order to track the amount of time
heating or cooling is on. When an opposite call is made after a first
call is existing the changeover timer calculates the amount of time
the unit has already been supplying the first mode in order to
determine how long it will hold off the opposite call. If an opposite
call is made shortly after the first call, the opposite call may be held
off for as much as 20 minutes. If the first call or subsequent calls for
the first call mode has had that mode operating for up to 20 minutes
already and an opposite call comes in after 20 minutes, the
changeover timer will immediately recognize the opposite call,
shutting off the current mode, enter the purge mode and
automatically switch to the opposite mode.
The longer a call has been running up to 20 minutes, the shorter the
wait time will be for an opposite call. If a call is over 20 minutes and
an opposite call is made the changeover will be immediate following
the purge time. This intelligent changeover timing makes the
PCMMP3 unique to any other zoning system.
CHECKOUT
The PCMMP3 has unique features that simplify the checkout of the
system and has LED readouts that constantly indicate the system
operation. Once 24 Volt Power is applied to the panel the Green
Power LED will illuminate. This will stay illuminated constantly when
power is applied.
The System LED will provide several different indications based
upon color and if it is flashing.
Heat ON – RED
Heat Over limit – RED Flashing
Cool ON GREEN
Cool Over limit – Green Flashing
FAN ON – AMBER
PURGE
– AMBER Flashing
Each zone has its own small Green indicator LED next to each zone
relay. This light is lit whenever the zone damper is to be open, either
on a call or when all zones are satisfied.
WIRING
The PCMMP3 is very simple to wire and requires only a minimum
number of connections. The PCMMP3 terminal blocks are screw-
less and all wires can easily be pushed into their respective terminal
by de-pressing the button for each point and releasing once the wire
is seated. To remove the wire, just press its button again and
remove the wire.
Zone Dampers – The PCMMP3 powers only the 12VDC plug-in
dampers. Each damper comes with a modular cord and plugs
(RJ11) already installed to allow each zone damper to just plug into
the PCMMP3 panel. Additional dampers can be slaved to one
another by using the splitter included with each damper. Additional
dampers are connected via each splitter to “daisy chain’ from one
damper to the next. A maximum of 10 dampers per zone is
recommended.
Upon installation it is recommended that as each motor is connected
that each motor is cycled, before connecting the next motor, to
insure proper operation of that motor and to minimize
troubleshooting looking for a possible bad motor or wire connection.
3
Zone Thermostats – The thermostats wiring will for single stage
can be four or five wire. The fifth wire being the C-Common terminal
for 24 Volt powered thermostats. There are 5 terminals on the
PCMMP3 for each thermostat, marked Y-G-R-W-C. This wiring is
shown on Wiring Diagram 1 for single stage thermostats.
HVAC Equipment – The HVAC equipment will follow Wiring
Diagram 2 for Single Stage Systems. The PCMMP3 can also control
Heating Only and Cooling Only as well as both Heating and Cooling.
Transformer – A separate 24 Volt AC, 40VA Transformer is
recommended to power the control panel and dampers. Often the
transformer on the HVAC unit only has enough power for its own
controls. Therefore it is recommended a separate transformer be
used to power this panel and the dampers wired to it.
Transformer Wiring
24V TRANS
C
R
C
R
T24 -24V 40VA
TRANSFORMER
Zone Thermostat Wiring
G
Y
R
W
C
ZONE THERMOSTAT
G
Y
R
W
C
70°
ZONE THERMOSTAT
Plug-In Damper Wiring
To Additional Dampers
Up to 10 Per Zone, if used.
Zone Damper
Connector on
Zone Panel
NOTE: It does NOT matter which jack on damper
goes to the panel or additional dampers.
PLUG-IN ZONE DAMPER
25 Foot Modular Cord
(Provided with each damper)
HVAC Equipment Wiring
Y COMPRESSOR RELAY
G FAN RELAY
W HEAT RELAY
R 24V. TRANSFORMER C
FURNACE CONTROLS
OUTDOOR CONDENSING UNIT
Y
G
W
R
EQUIPMENT
Zone Plenum Sensor
The Zone Mix-Air Sensor, Model PCZPS, is a remote sensor that is
located in the supply air duct to sense the leaving air temperature of
the HVAC Unit. The PCZPS is a high limit protection for the heating
and a low limit protection for the cooling. When zoning, the airflow
through the HVAC Unit is critical. The LAS protects the equipment in
low air flow situations as well as when by-pass air is being directed
back into the return air duct.
The heating limit is fixed at 180nF. The cooling limit is fixed at 40nF.
When the PCZPS senses heating above its set point, or cooling
below its set point, the PCMMP3 will drop both stages of heating or
cooling. The PCZPS must sense a 10nF fall for heating or rise for
cooling before re-activating the first stages of heating or cooling. If
two stage heating or cooling is being used the second stage timer
will start again once the first stage is re-activated.
The PCZPS requires 2 wires from the sensor to the LAT terminals
on the PCMMP3 panel. The PCZPS probe can also be adjusted for
length by loosening the end nut and sliding the probe thru the
mounting plate in order for the probe to pass through any duct
insulation.
Leaving Air Sensor
(Mounted in Supply Air before Zone Dampers)
Model ZPS
LAS Terminals
On Zone Panel
NOTE: If the PCZPS is not used, the NO SENSOR jumper
located just above the LAT terminals must be on the pins.
After installing the PCZPS, use the chart supplied with the PCZPS to
check the Ohm reading for the appropriate duct temperature.
TROUBLESHOOTING
The PCMMP3 is a very simple control to troubleshoot, especially
with the LED indicators. The only other device needed is a simple
Volt/Ohm meter.
Almost all problems can be traced to an external component or
wiring to the PCMMP3. While the PCMMP3 has been designed to
operate under extreme voltage conditions and is fuse protected, like
any computer the micro-processor can hang up and not operate
properly. For these instances a BOOT button has been installed that
re-boots the micro-processor just like your computer. Pressing this
button for a few seconds and then release it will allow the micro-
processor to re-boot and in most all cases eliminate the problem. If
not the following procedure can help isolate the problem.
If the BOOT Button does not resolve the problem, turn off the power
to the panel for several seconds until the LEDs got out and then turn
the power back on to see if the panel resets. In many instances this
resolves the problem.
The first check is for 24VAC Power to the panel. When there is
power the Green Power LED will be lit. If not check the transformer
and the power supply to it.
BOOT
4
Zone(s) Not Calling
Each zone has a Green LED next to the zone relay when it is
calling. The LED being lit shows that the call is being recognized by
the PCMMP3. If a zone is supposed to be calling and the Zone LED
is not on, check for 24VAC across the thermostat terminal C and the
Y, if a Cool call, W if a Heat Call, or G if a Fan call. If there is no
voltage here at the panel the panel is not getting the signal from the
thermostat. The problem is mis-wiring, a broken wire or a problem in
the thermostat. To check the zone on the panel, place jumper from
R to Y to simulate a Cool call, R to W to simulate a Heat call, or R to
G to simulate a Fan call. By jumpering these terminals the zone call
LED will activate.
Zone(s) Will Not Shut Off
If a zone will not stop calling, the Zone LED should still be on.
Depending on the call disconnect the Y, W or G wire from the zone
terminal strip on the panel. The call from that zone will drop out
when the thermostat wire is removed. Check the thermostat wiring
for a mis-wiring or short that keeps the zone calling.
If the thermostat wire is disconnected from the proper terminal on
the zone and the zone LED remains lit, re-boot the panel to see if
the call drops. If the call still stays on, turn power off to the panel for
10 seconds and then turn back on. Once powered is restored and
the thermostat is disconnected the call should drop from the zone. If
not replace panel.
Damper Motor Checkout Procedure
In order to determine the operation of the damper motors, the panel
motor plug can be checked to determine if power is being supplied
from the panel. If there is power at the motor plug, the problem may
be a broken wire or poor connection in the cord or the motor itself.
To check the power to the motor from the damper plug on the panel,
switch your meter to DC Volts. Note the wires on the plug and check
across either Positive and Negative wires. Note that each plug has
two positive leads and two negative leads. Both positive and both
negative leads are wired together. The meter will read either Plus (+)
or Minus (-) 12VDC depending if the damper is to be Open or
Closed respectively.
DAMPER CLOSED
-12VDC
NOT USED
NOT USED
POSITIVE (+)
POSITIVE (+)
NEGATIVE (-)
MOTOR PLUG
VDC
-12VDC
NOT USED
NOT USED
POSITIVE (+)
POSITIVE (+)
NEGATIVE (-)
MOTOR PLUG
-12VDC-12VDC
NOT USED
NOT USED
POSITIVE (+)
POSITIVE (+)
NEGATIVE (-)
MOTOR PLUG
VDC
When using multiple dampers on a single zone, please note to have
no more than 6 dampers on a single zone. Adding dampers beyond
the recommended number may cause all dampers to be slow to
operate and may not fully cycle between open and closed.
DAMPER OPEN
+12VDC
NOT USED
NOT USED
POSITIVE (+)
POSITIVE (+)
NEGATIVE (-)
MOTOR PLUG
VDC
+12VDC
NOT USED
NOT USED
POSITIVE (+)
POSITIVE (+)
NEGATIVE (-)
MOTOR PLUG
+12VDC+12VDC
NOT USED
NOT USED
POSITIVE (+)
POSITIVE (+)
NEGATIVE (-)
MOTOR PLUG
VDC
5
PCMMP3 Wi
ring Diagram
693D-0311
Specifications and illustrations subject to change without
notice and without incurring obligations.
Printed in U.S.A. (03/11)
24V TRANS
C
R
C
R
T24 -24V 40VA
TRANSFORMER
Y COMPRESSOR RELAY
G FAN RELAY
W HEAT RELAY
R 24V. TRANSFORMER C
FURNACE CONTROLS
OUTDOOR CONDENSING UNIT
Y
G
W
R
EQUIPMENT
G
Y
R
W
C
ZONE THERMOSTAT
G
Y
R
W
C
70°
ZONE THERMOSTAT
G
Y
R
W
C
ZONE THERMOSTAT
G
Y
R
W
C
70°
ZONE THERMOSTAT
G
Y
R
W
C
ZONE THERMOSTAT
G
Y
R
W
C
70°
ZONE THERMOSTAT
Leaving Air Sensor
(Mounted in Supply Air before Zone Dampers)
Model ZPS
LAS Terminals
On Zone Panel
JUMPERS
FIPG – Fan On In Purge – Placing this jumper ON
keeps the Fan running during the two minute
Purge Mode. The jumper Off allows the furnace
controls to cycle the fan.
FIH – This jumper ON brings the Fan On with a
call for heat. When off the fan is brought on by the
furnace controls.
TEST – Used ONLY to test the panel as this
accelerates all of the timings.
LOW LIMIT – Sets Heating Limit at 170°F with
jumper ON and 180°F with jumper OFF.
BOOT Button– Resets the microprocessor.
NO SENSOR – Must be ON when not using
Leaving Air Sensor and OFF when sensor is
wired.
FIPG
FIH
TEST
BOOT
ON LOW LIMIT
24V TRANS
C
R
C
R
T24 -24V 40VA
TRANSFORMER
Y COMPRESSOR RELAY
G FAN RELAY
W HEAT RELAY
R 24V. TRANSFORMER C
FURNACE CONTROLS
OUTDOOR CONDENSING UNIT
Y
G
W
R
EQUIPMENT
G
Y
R
W
C
ZONE THERMOSTAT
G
Y
R
W
C
70°
ZONE THERMOSTAT
G
Y
R
W
C
ZONE THERMOSTAT
G
Y
R
W
C
70°
ZONE THERMOSTAT
G
Y
R
W
C
ZONE THERMOSTAT
G
Y
R
W
C
70°
ZONE THERMOSTAT
Leaving Air Sensor
(Mounted in Supply Air before Zone Dampers)
Model ZPS
LAS Terminals
On Zone Panel
JUMPERS
FIPG – Fan On In Purge – Placing this jumper ON
keeps the Fan running during the two minute
Purge Mode. The jumper Off allows the furnace
controls to cycle the fan.
FIH – This jumper ON brings the Fan On with a
call for heat. When off the fan is brought on by the
furnace controls.
TEST – Used ONLY to test the panel as this
accelerates all of the timings.
LOW LIMIT – Sets Heating Limit at 170°F with
jumper ON and 180°F with jumper OFF.
BOOT Button– Resets the microprocessor.
NO SENSOR – Must be ON when not using
Leaving Air Sensor and OFF when sensor is
wired.
FIPG
FIH
TEST
BOOT
ON LOW LIMIT
© Nortek Global HVAC, LLC 2015. All Rights Reserved.