This quick guide includes the essential steps for easy
installation and setup of your Vacon 20 frequency converter.
Before commissioning your drive, download and read the complete
Vacon 20 User Manual available at:
http://drives.danfoss.com/knowledge-center/technical-documentation/
1. SAFETY
ONLY A COMPETENT ELECTRICIAN IS ALLOWED TO
CARRY OUT THE ELECTRICAL INSTALLATION!
This quick guide contains clearly marked warnings which are intended for your per-
sonal safety and to avoid any unintentional damage to the product or connected ap-
pliances.
Please read these warnings carefully:
The components of the power unit of the frequency converter
are live when Vacon 20 is connected to mains. Coming into
contact with this voltage is extremely dangerous and may
cause death or severe injury.
The motor terminals U, V, W (T1, T2, T3) and the possible brake
resistor terminals - / + are live when Vacon 20 is connected to
mains, even if the motor is not running.
The control I / O-terminals are isolated from the mains poten-
tial. However, the relay output terminals may have a danger-
ous control voltage present even when Vacon 20 is
disconnected from mains.
The earth leakage current of Vacon 20 frequency converters
exceeds 3.5 mA AC. According to standard EN61800-5-1, a
reinforced protective ground connection must be ensured.
See Chapter 7!
If the frequency converter is used as a part of a machine, the
machine manufacturer is responsible for providing the
machine with a main switch (EN 60204-1).
If Vacon 20 is disconnected from mains while running the
motor, it remains live if the motor is energized by the process.
In this case the motor functions as a generator feeding energy
to the frequency converter.
After disconnecting the frequency converter from the mains,
wait until the fan stops and the display segments or status
leds on the front panel go out. Wait 5 more minutes before
doing any work on Vacon 20 connections.
The motor can start automatically after a fault situation, if the
autoreset function has been activated.
!
Doc: DPD00511H1 Release: July, 2016
Sw Package: FW0107V012.vcx
2 vacon safety
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
1
NOTE! You can download the English and French product manuals with applica-
ble safety, warning and caution information from http://drives.danfoss.com/
knowledge-center/technical-documentation/.
REMARQUE Vous pouvez télécharger les versions anglaise et française des ma-
nuels produit contenant l’ensemble des informations de sécurité, avertisse-
ments et mises en garde applicables sur le site http://drives.danfoss.com/
knowledge-center/technical-documentation/.
installation vacon 3
24-hour support +358 (0)201 212 575 • Email: [email protected]
2
2. INSTALLATION
2.1 Mechanical installation
There are two possible ways to mount Vacon 20 in the wall. For MI1 - MI3, either
screw or DIN-rail mounting; For MI4 - MI5, screw or flange mounting.
Figure 1: Screw mounting, MI1 - MI3
Figure 2: Screw mounting, MI4 - MI5
M5
MI3
MI1
=M4
MI2
=M5
LOC
REM
BACK
RESET
OK
LOC
REM
BACK
RESET
OK
LOC
REM
BACK
RESET
OK
MI4
=M 6
=M 6
MI5
LOC
REM
BACK
RESET
OK
LOC
REM
BACK
RESET
OK
4 vacon installation
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
2
Figure 3: DIN-rail mounting, MI1 - MI3
Note! See the mounting dimensions on the back of the drive.
Leave free space for cooling above (100 mm), below (50 mm), and on the sides
(20 mm) of Vacon 20! (For MI1 - MI3, side-to-side installation allowed only if the am-
bient temperature is below 40 °C; For MI4 - MI5, side-to-side installation is not al-
lowed.
Figure 4: flange mounting, MI4 – MI5
LOC
REM
BACK
RESET
OK
Drive outline
Opening outline
installation vacon 5
24-hour support +358 (0)201 212 575 • Email: [email protected]
2
Figure 5: Flange mounting cutout dimensions for MI4 (Unit: mm)
Figure 6: Flange mounting cutout dimensions for MI5 (Unit: mm)
Drive outline
Opening outline
6 vacon installation
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
2
Figure 7: Flange mounting depth dimensions for MI4 and MI5 (Unit: mm)
M15
M14
installation vacon 7
24-hour support +358 (0)201 212 575 • Email: [email protected]
2
.
Figure 8: Attaching the PE-plate and API cable support, MI1 - MI3
Figure 9: Attaching the PE-plate and API cable support, MI4 - MI5
Attach this plate
BEFORE installing
the p ower ca bl es
Attach the support
AF TER instal lin g
the power cables
Attach the support
AF TER i nstal lin g
Attach th is plate
BEFORE installing
the pow er ca bles
8 vacon installation
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
2
2.2 Cabling and connections
2.2.1 Power cabling
Note! Tightening torque for power cables is 0.5 - 0.6 Nm (4-5 in.lbs).
Figure 10: Vacon 20 power connections, MI1
Figure 11: Vacon 20 power connections, MI2 - MI3
1~ (230V)
3~ (230V, 400V)
Motor out
MAINS
MOTOR
Strip the
plastic cable
coating for
360° earthing
L1 L2/ N L3 U/ T1 V/ T2 W /T3R+ R-
1~ (230V)
3~(230V, 400V, 600V)
1~ (115V)
MAINS
MOTOR
BRAKE
RESISTOR
External brake resistor
Motor out
Strip the
plastic
cable
coating
for 360°
earthing
3~(230V, 400V,600V)
installation vacon 9
24-hour support +358 (0)201 212 575 • Email: [email protected]
2
Figure 12: Vacon 20 power connections, MI4
Figure 13: Vacon 20 power connections, MI5
MAINS
MOTOR
Motor out
Brake
RESISTOR
3~ (380, 480V)
MAINS
MOTOR
Motor out
Brake
RESISTOR
3~ (380, 480V)
10 vacon installation
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
2
2.2.2 Control cabling
Figure 14: Open the lid MI1 - MI3
Figure 15: Open the lid MI4 - MI5
installation vacon 11
24-hour support +358 (0)201 212 575 • Email: [email protected]
2
Figure 16: Install the control cables, MI1 - MI3
Figure 17: Install the control cables, MI4 - MI5
Strip the plastic
cable coating for
360°earthing
Control cable
tightening
torque: 0.4 Nm
12 vacon installation
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
2
2.2.3 Allowed option boards in Vacon20
See below for the allowed option boards in the slot:
Note! When OPT-B1 / OPT-B4 used in Vacon20, +24VDC (±10%, min.300mA) power
should be supplied to Terminal 6 (+24_out) and Terminal 3 (GND) in control board.
Option board assembly structure:
Option boards (all boards are varnished)
OPT-EC-V EtherCat
OPT-E3-V Profibus DPV1 (Screw connector)
OPT-E5-V Profibus DPV1 (D9 connector)
OPT-E6-V CANopen
OPT-E7-V DeviceNet
OPT-E9-V Modbus TCP, Profinet & Ethernet IP
OPT-B1-V 6 x DI/DO, each I/O can be individually
OPT-B2-V 2 x Relay output + Thermistor
OPT-B4-V 1 x AI, 2 x AO (isolated)
OPT-B5-V 3 x Relay output
OPT-B9-V 1 x RO, 5 x DI (42-240 VAC)
OPT-BH-V
3 x Temperature measurement (support for PT100, PT1000,
NI1000, KTY84-130, KTY84-150, KTY84-131 sensors)
OPT-BF-V 1 x AO, 1 x DO, 1 x RO
SLOT
E5
E6
B1
B2
B9
BH
E3EC E7 E9 B4 B5 BF
1
installation vacon 13
24-hour support +358 (0)201 212 575 • Email: [email protected]
2
2
3
4
14 vacon installation
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
2
5
6
vacon 20 api vacon 15
24-hour support +358 (0)201 212 575 • Email: [email protected]
3
3. CONTROL I / O AND TERMINALS
Terminal Signal Factory preset Description
1 +10 Vref Ref voltage out
Maximum load 10 mA
2 AI1 Analogue signal in 1
Freq reference
P)
0 - 10 V, Ri = 250 k
3 GND I / O signal ground
6 24 Vout 24 V output for DI's
±20%, max load 50 mA
7DI_C
Digital Input Com-
mon
Digital Input for DI1- DI6, refer
to Table 2 for DI sink type
8 DI1 Digital input 1
Start forward
P)
Positive,
Logic1: 18…30V,
Logic0: 0…5V;
Negative,
Logic1: 0…10V, Logic0: 18…30V;
Ri = 10K (floating)
9 DI2 Digital input 2
Start reverse
P)
10 DI3 Digital input 3
Fault reset
P)
A A RS485 signal A FB Communication
Negative
B B RS485 signal B FB Communication
Positive
4AI2
Analogue signal in
2
PID actual value and
Freq reference
P)
Default:
0(4) - 20 mA, Ri 250
Other:
0 - 10 V, Ri = 250 k
Selectable through microswitch
5 GND I / O signal ground
13 DO-
Digital Output
Common
Digital Output Common
14 DI4 Digital input 4
Preset speed B0
P)
AS DI1
15 DI5 Digital input 5
Preset speed B1
P)
As DI1,
Other: Encoder Input A (fre-
quency up to 10 kHz)
Selectable through microswitch
16 DI6 Digital input 6
External Fault
P)
As DI1,
Other: Encoder Input B (fre-
quency up to 10 kHz), Pulse
Train Input (frequency up to 5
kHz)
18 AO Analogue Output
Output frequency
P)
0 - 10 V, RL 1 K
0(4) - 20 mA, RL 500
Selectable through microswitch
20 DO Digital signal out
Active = READY
P)
Open collector, max load 35 V /
50 mA
Table 1: Vacon 20 General purpose application default I / O configuration and
connections for control board
P) = Programmable function, See User Manual: parameter lists and
descriptions for detail
mA
Vacon 20
1-10 k
16 vacon vacon 20 api
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
3
Figure 18: Microswitchs
Vacon 20 I / O terminals:
22 RO1 NO Relay out 1
Active = RUN
P)
Switching load:
250 Vac / 3 A, 24V DC 3A
23 RO1 CM
24 RO2 NC
Relay out 2
Active = FAULT
P)
Switching load:
250 Vac / 3 A, 24V DC 3A
25 RO2 CM
26 RO2 NO
Terminal Signal Factory preset Description
3 GND I / O signal ground
6 24 Vout 24 V output for DI's
%, max load 50 mA
7DI_C
Digital Input Com-
mon
Digital Input Common
for DI1-DI6
8 DI1 Digital input 1
Start forward
P)
Positive, Logic1:18…30V,
Logic0: 0…5V;
Negative, Logic1: 0…10V,
Logic0: 18…30V;
Ri = 10K (floating)
9 DI2 Digital input 2
Start reverse
P)
10 DI3 Digital input 3
Fault reset
P)
14 DI4 Digital input 4
Preset speed B0
P)
Positive, Logic1:18…30V,
Logic0: 0…5V;
Negative, Logic1: 0…10V,
Logic0: 18…30V;
Ri = 10K (floating)
15 DI5 Digital input 5
Preset speed B1
P)
Only for DI.
16 DI6 Digital input 6
External Fault
P)
Only for DI.
Table 2: DI Sink Type, remove jumper J500 and connect the wire using table 2
Terminal Signal Factory preset Description
Table 1: Vacon 20 General purpose application default I / O configuration and
connections for control board
P) = Programmable function, See User Manual: parameter lists and
descriptions for detail
20
DI
Enco Nor
AO
VmA
AI2
VmA
RS485
-term
ON
S1S2S3S4
J500
OFF
4 5 13 14 15 16 2018
123678910
22 23 26
2425
AI2 GND DO- DI4 DI5 DI6 AO DO+ R13 R14 * R24
+10VAI1 GND 24V DI-C DI1 DI2 DI3 A B R21 R22
navigation & startup vacon 17
24-hour support +358 (0)201 212 575 • Email: [email protected]
4
4. NAVIGATION AND STARTUP
4. 1 The main menus of Vacon 20
Figure 19: The main menu of Vacon 20
FWD R EV I/O KEYPAD BUS
REF
MON
PA R
SYS SYS
SYS SYS
SYS SYS
SYS SYS
FAULTALARMSTOPREADY RUN
FWD REV I/O KEYPAD BUS
REF
PA R
FAULTALARMSTOPREADY RUN
MON
FW D REV I/O KEY PA D BUS
REF
PAR
FAU LTALARMSTO PREADY RUN
MON
FWD REV I/O KEYPAD BUS
REF
PAR
FAULTALARMSTOPREADY RUN
MON
FWD REV I/O KEYPAD BUS
REF
PAR
FAULTALARMSTOPREADY RUN
MON
FWD REV I/O KEYPAD BUS
REF
PAR
FAULTALARMSTOPREADY RUN
MON
FWD REV I/O KEYPAD BUS
REF
PAR
FAU LTALARMSTO PREAD Y RUN
MON
PRESS
PRESS
PRESS
PRESS
PRESS
FWD REV I/O KEYPAD BUS
REF
MON
PA R
FAU LTALARMSTOPREADY RUN
PRESS
PRESS
OK
OK
OK
OK
OK
In this menu
you can
browse the
monitoring
values.
In this menu
you can
browse and
edit the
parameters.
Dispalys the
keypad reference
value
regardless of
the selected
contron place.
Here you will be
able to browse
system parameter
and fault
submenu.
MONITORING
MENU
REFERENCE
MENU
PARAMETER
MENU
SYSTEM
MENU
Hz
Hz
18 vacon navigation & startup
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
4
4.2 Commissioning and startup wizard
4.2.1 Commissioning steps:
4.2.2 Startup wizard
Vacon 20 runs the startup wizard in first power-up. The wizard can be run by setting
SYS Par.4.2 =1. The following figures show the procedure.
NOTE! Running the startup wizard will always return all parameter
settings to their factory defaults!
NOTE! StartUp-Wizard can be skipped after pressing STOP button
continuously for 30 seconds
1. Read safety instructions on page 1
7. Perform test run without motor, see the
User Manual at http://drives.danfoss.com/
knowledge-center/technical-documentation/
2. Secure the grounding and check that cables
comply with requirements
8. Run no-load tests without motor being con-
nected to the process
3. Check quality and quantity of cooling air 9. Perform an identification run (Par. ID631)
4. Check that all start / stop switches are in
STOP position
10. Connect the motor to the process and per-
form test run once again
5. Connect the drive to mains 11. Vacon 20 is now ready for use
6. Run the Startup wizard and set all necessary
parameters
Table 3: Commissioning steps
navigation & startup vacon 19
24-hour support +358 (0)201 212 575 • Email: [email protected]
4
Figure 20: Vacon 20 startup wizard (standard application)
FAU LTALARMSTOPREADY
RUN
REF
MON
PAR
SYS
FAU LTALARMSTOPREADY RUN
REF
MON
PAR
SYS
FAU LTALARMSTOPREADY RUN
REF
MON
PAR
SYS
FWD REV I/O KEY PAD BUS
FWD REV I/O KEY PAD BUS
FWD REV I/O KEY PAD BUS
FWD REV I/O KEY PAD BUS
2
1
4
3
Change
P1.3
value
with Up/Down button
and press OK to
comfirm
Perform the same
procedure for P1.4,
motor nominal current
Press OK enter
edit mode
Enter Par. menu, select
P1.3 motor nominal speed
FAU LTALARMSTOPREADY RUN
REF
MON
PAR
SYS
OK
OK
rpm
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62

Danfoss 20 User guide

Type
User guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI