Vemer Energy-3x130 PWRi User manual

Type
User manual

Vemer Energy-3x130 PWRi is a three-phase energy meter designed to operate in environments with measurement category III and pollution level 2. It is used to read active energy in three-phase systems. Below you will find brief product information.

The device has a power supply of 3x130 V AC phase-neutral (230VAC phase-phase) (-15% ÷ +10%) and a frequency of 50/60 Hz. It has a rated current of 5 A, a maximum current of 6 A, and a minimum start-up current of 15 mA. The maximum power consumption is less than 2.5 VA for both voltage and current circuits.

The meter constant is 1 imp = ¼ kWh. The voltage inputs have an input impedance of 2 MΩ, while the current inputs use coils with galvanic insulation between primary and secondary.

Vemer Energy-3x130 PWRi is a three-phase energy meter designed to operate in environments with measurement category III and pollution level 2. It is used to read active energy in three-phase systems. Below you will find brief product information.

The device has a power supply of 3x130 V AC phase-neutral (230VAC phase-phase) (-15% ÷ +10%) and a frequency of 50/60 Hz. It has a rated current of 5 A, a maximum current of 6 A, and a minimum start-up current of 15 mA. The maximum power consumption is less than 2.5 VA for both voltage and current circuits.

The meter constant is 1 imp = ¼ kWh. The voltage inputs have an input impedance of 2 MΩ, while the current inputs use coils with galvanic insulation between primary and secondary.

User Manual
ACTIVE ENERGY METER
Read all the instructions carefully
TheENERGY-400 and ENERGY-3x130 are electronic static devices to read active energy in
three-phasesystemsdesignedtooperateinenvironmentswithmeasurementcategoryIIIand
pollution level 2 according to EN 61010-1 standard.
SAFETY WARNINGS
To guarantee correct installation, proceed as follows:
1) The appliance should be installed by a qualified operator
2) The appliance should be installed in a panel in such a way as to guarantee that the
terminals are inaccessible after fitting
3) A protection device against over-currents should be installed in the electrical system,
upstream of the energy meter
4) Connect the instrument as shown in the alongside diagrams
5) Before touching the connector terminals make sure that the wires to be connected or
already connected to the instrument are not live
6) Touch the dip-switches only when the instrument is not powered
7) Do not power or connect the instrument if any part of it is damaged
8) The instrument must be installed and activated in compliance with current electric
system standards.
Code Model Description
VN964300 ENERGY-400PWR Three-phaseenergymeter400VAC
VN966800 ENERGY-3x130PWR Three-phaseenergymeter3x130VAC
VN967600 ENERGY-3x130PWRi Three-phaseenergymeter3x130VAC
TECHNICAL SPECIFICATIONS
• Powersupply:
- 3x230 V AC phase-neutral (400VAC phase-phase) (-15% ÷ +10%)
for Energy-400 model
- 3x130 V AC phase-neutral (230VAC phase-phase) (-15% ÷ +10%)
for Energy-3x130 models
• Frequency:50/60Hz
• Ratedcurrent:5A
• Maximumcurrent:6A
• Minimumstart-upcurrent:15mA
• Maximumpowerconsumption:
- voltage circuits < 2,5 VA
- current circuits < 2,5 VA
• Meterconstant:1imp=¼kWh
• Voltageinputs:inputimpedance=2MΩ
• Currentinputs:
 -shuntof0.022Ω(+/-10%)forPWR models
 -coilswithgalvanicinsulationbetweenprimaryandsecondaryforEnergy-3x130PWRi
model
• Twoopticinsulatedimpulseoutput:
- impulse duration < 100 ms
- voltage 9÷24 V DC
- current < 20 mA
• Insulation:
 -reinforcedbetweenimpulseoutputandotherterminals
- reinforced between terminals and parts accessible after installation
• CTavailable:5-10-25-50-75-100-125-150-200-250-300-400-500-600-8001000/5A
• Operatingtemperature:-10°C÷+45°C
• Storagetemperature:-25°C÷+70°C
• Relativehumidity:10÷90%noncondensing
• Classindex:classA(EN50470)
• Container:4moduleDIN
• Protectionlevel:IP20/IP40onthefront
INSTRUMENT DESCRIPTION
 Dip-switchforCTsetting
Green warning light:lightsuptoindicatepoweron
Red warning light:flashestoindicatethattheinstrumentismeteringenergy
(1flash=¼kWh)
Yellow warning light:whenlittheinstrumentdetects¼kWhnegative(probable
incorrectentry)andremainslituntil¼kWhpositiveisdetected
ChecktheinsertionofCT:connectL1,L2,L3frompowerpaneltoP1ofCTand
connectP2ofCTtotheload.
 Impulseoutput:Opticallyinsulated
 Electro-mechanicalimpulsecounter:resolution1kWh
GUIDE TO INSTALLATION
1)Beforeinstallingtheinstrument,selecttherequiredtransformationratio,asshownin
panel C)
2)ForEnergy-3x130PWRimodelonly,theCTsecondariesmaybeconnectedtoearth
3)TheinstrumentshouldbeconnectedasshowninthepanelB),inaccordancewiththe
CTcurrentdirections
4)Iftheerroristofallwithintheclasslimitsoftheinstrument,itisnecessarytousethe
current transformer in its linear operating field.
5)IftheinstrumentisactivethepowershouldbeswitchedofftochangetheCTratio.
6)Incaseofchangestothedip-switchwiththeinstrumentactived,theselocksinfault
conditionwithredandgreenlightsalwayson.Inthisconditiontheinstrumentdoesn’t
coun.
 Torestorethecorrectoperation,repositiontheDIPswitchesintheinitialconditionor
resettheinstrumentbyremovingandrestoringpower.
REFERENCE STANDARDS
ConformitytoEUdirective:
2004/22/EC (MID)
2006/95/EC (Low Voltage - LVD)
isdeclaredwithreferencetothefollowingharmonisedstandards:
EN 61010-1
EN50470-1andEN50470-3
V3IS00244-100_02-2013
Mod. ENERGY-400 PWR
Mod. ENERGY-3x130 PWR
ENERGY-3x130 PWRi
Dimensions (A)
Connection diagrams (B)
Instrument description (C)
+
1
2
3
4
5
6
10
11
12
13
14
15
7
8
9
16
17
18
L3
L1
L2
L3
L2
L1
2 CT connection (PWRi only) WITHOUT neutral (3 wires)
1 kWh/pulse
Pulse output
I 20 mA
24 VCC
PWRi
P1 P2
S1 S2
I
PWR
P1 P2
S1 S2
I
5
10
25
50
200
250
300
400
x/5 A
1 2 34x/5 A
1 2 34
75
100
125
150
500
600
800
1000
ON OFF
N
L3
N
L1
L2
5
6
7
8
9
14
15
16
17
18
1
2
3
4
10
11
12
13
+
L3
L2
L1
3 CT connection WITH or WITHOUT neutral (3 or 4 wires)
1 kWh/pulse
Pulse output
I 20 mA
24 VCC
72 60
87
45
14
60 0 0
14
60 0 0
  • Page 1 1

Vemer Energy-3x130 PWRi User manual

Type
User manual

Vemer Energy-3x130 PWRi is a three-phase energy meter designed to operate in environments with measurement category III and pollution level 2. It is used to read active energy in three-phase systems. Below you will find brief product information.

The device has a power supply of 3x130 V AC phase-neutral (230VAC phase-phase) (-15% ÷ +10%) and a frequency of 50/60 Hz. It has a rated current of 5 A, a maximum current of 6 A, and a minimum start-up current of 15 mA. The maximum power consumption is less than 2.5 VA for both voltage and current circuits.

The meter constant is 1 imp = ¼ kWh. The voltage inputs have an input impedance of 2 MΩ, while the current inputs use coils with galvanic insulation between primary and secondary.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI