V3IS00384-011
Mod. ENERGY-400R PWR
Mod. ENERGY-400R PWRi
Static meter in standard dimensions 72x72 mm to read active energy
consumption in three-phase 400V systems:
-forENERGY-400RPWR:currentinputsbyshunt;
-forENERGY-400RPWRi:currentinputsbycoils with galvanic insulation
betweenprimaryandsecondary.
AmperometricconnectionbyCT x/5A.
SAFETY WARNINGS
To guarantee correct installation, proceed as follows:
1) The appliance should be installed by a competent operator
2) The appliance should be installed in a panel in such a way as to
guarantee that the terminals are inaccessible after fitting
3) A protection device against over-currents should be installed in the
electrical system, upstream of the energy meter
4) Connect the instrument as shown in the alongside diagrams
5) Before touching the connector terminals make sure that the wires to
be connected or already connected to the instrument are not live
6) Touch the dip-switches only when the instrument is not powered
7) Do not power or connect the instrument if any part of it is damaged
Code Model Description
VE010500 ENERGY-400RPWR Three-phaseenergymeter
VE011300 ENERGY-400RPWRi Three-phaseenergymeter
TECHNICAL SPECIFICATIONS
• Powersupplyvoltage:
3x230phase-neutral(400phase-phase)VCA(-15%/+10%)50/60Hz
• Inputcurrent:In = 5A; IMAX=6A
• Minimumstart-upcurrent:15mA
• Accuracy:class2tostandardsEN62053-21
• Maximumpowerconsumption:voltagecircuits<2,5VA
currentcircuits<2,5VA
• Galvanicallyisolatedamperometricinput(for PWRi model only)
• AmperometricconnectionbyCTx/5A
• Selectabletransformationratios(forCTx/5A):5-10-25-50-75-100-125-150-200-
250-300-400-500-600-800-1000/5
• Operatingtemperature:-10÷+45°C
• Relativehumidity:10%÷90%noncondensing
• Storagetemperature:-20÷+60°C
• Signalingleds:green=poweron
red = flashing at 1/4 kWh
yellow = when lit the instrument detects 1/4 kWh negative
(probableincorrectentry)andremainslituntil1/4kWh
positive is detected
• Optoinsulatedpulseoutputforenergyconsumptionremote-monitoring
(1kWh/pulse)
• Pulsespecications: duration=100ms±15%
voltage=9÷24VCC(±10%)
switchableoutputcurrent20mAmax
• Protectiondegree:IP20
• Enclosure:standarddimensions72x72mm
INSTRUMENT DESCRIPTION
7-digit mechanical counter: resolution 1 kWh
Green warning light: lights up to indicate power on
Red warning light: every flash corresponds to an energy count of 1/4 kWh
Yellow warning light: when lit the instrument detects 1/4 kWh negative
(probableincorrectentry)andremainslituntil1/4kWhpositiveisdetected
Dip-switch1-2-3-4forCTsetting.Dip-switch5-6notused
GUIDE TO INSTALLATION
1) Beforeinstallingtheinstrument,selectthetransformationratiorequired.
Useanx/5AouterCTwithatransformationratiofromamongthosesetout
inthedescriptionbox.For model PWRi only,theCTsecondariesmaybe
connected to earth.
2) Theinstrumentshouldbeconnectedasshownintheconnectiondiagrams,
inaccordancewiththeCTenergydirections.
3) Iftheerroristofallwithintheclasslimitsoftheinstrument,itisnecessaryto
usethecurrenttransformerinitslinearoperatingeld.
Seetheprecisionbox:
-MaximummeasurementerrorinaccordancewithEN62053-21forclass2
meters with cos ϕ=0,5inductive(A);
-MaximummeasurementerrorinaccordancewithEN62053-21forclass2
meters with cos ϕ = 1 and voltage and frequency reference conditions (B).
4) Iftheinstrumentisactive,thepowershouldbeswitchedofftochangetheCT
ratio.
REFERENCE STANDARDS
ConformitytotheEUdirectives:
73/23/ECCmodiedby93/68/ECC(LowVoltage)
89/336/ECCmodiedby92/31/ECC and 93/68/ECC(E.M.C.)
is declared with reference to the following harmonised standard:
EN61010-1,EN61000-6-2,EN61000-6-3,EN62053-21andEN62052-11
User Manual
ACTIVE ENERGY METER
Read all the instructions carefully
Dimensions
Connection diagrams
Description
Accuracy
72
&OFSHZ3183
L8I
0/ L8I
4XJUDI*O"_
$M
Y7_
)[
L8I*NQ
{£Èääää
0/
0''
105
5
66
8
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
"
5" 5" 5" 5"
0'' 0/
&OFSHZ3183
L8I
0/ L8I
4XJUDI*O"_
$M
Y7_
)[
L8I*NQ
{£Èääää
0/
0''
" #
6OEFUFSNJOFEFSSPS[POF 6OEFUFSNJOFEFSSPS[POF
L3
L1
L1
V1 N
I +1I -1
L2
L3
I +2I -2I +3I -3
V2V3
L2
N
N
I 20 mA≤
9 24 VCC÷
+Pulse output
1 kWh/pulse
3 CT connection ( )
WITH or WITHOUT neutral (3 or 4 wires)
PWR/PWRi
L3
L1
L1
V1
I +1I -1
L2
L3
I +2I -2I +3I -3
V2V3
L2 I ≤ 20 mA
9 24 VCC÷
+Pulse output
1 kWh/pulse
2 CT connection ( only)
WITHOUT neutral (3 wires)
PWRi
PWR
PWRi
P1 P2
S1 S2
P1 P2
S1 S2
I
I