LED Blink on Motion Transmission
– Red LED under PIR lense
will blink whenever motion is transmitted (disabled by default)
- To enable/disable press and hold the Menu button for 3
seconds (green Menu LED will blink once)
o Enabled – 3 blinks from Green Menu LED
o Disabled – blinks form Red Set button LED
– unoccupied heartbeat message will
be sent at 1 hour intervals with no motion (disabled by
default).
- To enable/disable press and hold the Menu button for 5
seconds (both red and green LEDs will blink once)
o Enabled – 3 blinks from Green Menu LED
o Disabled – blinks form Red Set button LED
The Occupancy Sensor package contains two lenses: a wide
angle lens and a long range lens. The wide angle lens is
installed by default and can be distinguished from the long
range lens by the pattern.
NOTE: Ensure smooth side of the lens faces out
Wide Angle Long Range
To Change the Lens:
1.
If the sensor is mounted, press the top tab and remove the
sensor from the mounting plate
2. Unscrew the small screw on the back at
the bottom and remove the front cover.
3. Remove the installed lens by gently
squeezing it to ease one side out
of its groove, and then the other.
4. Insert the lens you want to use by
aligning the notch with the top on
the front cover. Orient the smooth
side facing out and the textured side
facing the sensor.
5. Hold both edges of the lens, flex it
gently and push until it pops into the
grooves. Make sure the edges are
flush. NOTE: If the lens is out of
position, the sensor will not detect
motion properly.
6. Replace the top edge of the front cover
and then close it on the sensor. Ensure
the antenna is properly seated before
replacing the front cover.
7. Replace the bottom screw and remount
© Lauren Illumination, 2015 Page 4
Occupancy Sensor – Wall Mounted Installation Guide
Supplemental Power (optional):
In areas with consistently low lighting, or prolonged periods of
darkness, battery power (CR2032) or an auxiliary 3-5VDC
power source can be used to supplement the solar energy
harvester.
1. Remove the sensor from the mounting
plate and identify the battery holder
and auxiliary power connector on the
circuit board
2. Insert the battery under the clip with
the positive pole (+) up and press it in
place OR insert the 3-5 VDC positive (+)
and negative (-) leads into the
appropriate screw terminals
3. Remount the sensor on the mounting plate
Sensor does not
generate a wireless
message
- Press SET button to transmit message
- Verify the LED blinks when motion is
detected during the Walk Test
- Verify the solar cell is charging properly
Sensor is activated
when there is
nothing to detect
- Verify there is 4 ft. clearance from heat
sources that may disturb setting
- Reduce sensitivity by moving the PIR
sensitivity switch on the back from REG to
LOW (the left-hand position)
Linked device does
not respond to
wireless message
- Force motion message by pressing Set
button
- Check for environment of range issues
- Verify the device is linked
- Check the WLVD (or other transceiver)
connection and the wiring for errors
- Check if the appropriate devices are linked
according to good system planning
Contains:
FCC: SZV-STM300U
IC: 5713A-STM300U
This device complies with part 15 of the FCC rules and Industry Canada ICES-003.
Operation is subject to the following two conditions: (1) This device may not cause
harmful interference, and (2) this device must accept any interference received, including
interference that may cause undesired operation.
IMPORTANT! Any changes and or modifications not expressly approved by the party
responsible for compliance could void the user’s authority to operate this equipment.
Le present appareil est conforme aux CNR d’Industrie Canada applicables aux appereils
radio exempts de licence. L’exploitation est autorisee aux deux conditions suivantes: (1)
l’appareil ne doit pas produire de brouillage, et (2) l’utilisateur de l’appareil doit accepter
tout brouillage radioelectrique subi, meme si le brouillage est susceptible d’en
compromettre le fronctionnement.
IMPORTANT! Tous les changements ou modificantions pas expressement approuves par la
partie responsible do la conformite ont pu vider l’autorite de l’utilisanteur pour actioner
cet equipment.