LP5 / LP10 Maintenance Guide Version 1.2
CONTENT
Tool Kit and Replacement Parts
Lifting and collapsing the enclosure top part (flame shield)
Troubleshooting steps and contact information
Basic functional Test WITHOUT gas
Basic functional Test WITH gas
Connecting the hose / regulator assembly
Cleaning the burners orifices and slotted caps
Removing the enclosure top part (flame shield) for maintenance
Closing the enclosure top part (flame shield) after maintenance
A- IMPORTANT WARNINGS
Unit works with PROPANE ONLY. Connectors and fittings will not connect to
NATURAL GAS line.
RAISE the FLAME SHIELD before using the burner, see Section D
It is NOT SAFE to use the generator WITHOUT the FLAME SHIELD. However, it is
possible to use the burner without the shield for maintenance purpose, in a SAFE
AND VENTILATED LOCATION. In this case, use the generator away from
combustible or explosive material.
B- TOOL KIT AND REPLACEMENT PARTS
TOOL KIT
0.020 Orifice Cleaning Drill
White Grease “Gimme the White Stuff”
Burner and Cap Cleaning Brush
1/2 inch Key to screw/unscrew slotted cap burner on manifold
3/4 inch Key to screw/unscrew hose on gas intake
Robertson (Square or socket head) Screwdriver (#2 or Red)
REPLACEMENT PARTS
3000 BTU/hr Slotted Cap Burner
10-ft Hose / Regulator Assembly
1A SLOW BLOW Fuse (do not use Fast Blow Type)