Socomec DIRIS A-20 Operating instructions

Type
Operating instructions

This manual is also suitable for

ON
1
COM
F D I
NL
GB
E P
DIRIS A20
RS485 – JBUS/MODBUS
®
Notice d’utilisation
Operating instructions - Bedienungsanleitung
Istruzioni per l’uso - Gebruiksaanwijzing
Instrucciones de servicio - Manual de instruções
2
SOCOMEC - Réf. : 876 581 D
OPERATIONS PREALABLES _____________________ 4
INFORMATIONS GENERALES____________________ 4
INSTALLATION _________________________________ 5
PROGRAMMATION _____________________________ 6
COMMUNICATION_____________________________ 11
CARACTERISTIQUES TECHNIQUES _____________ 17
LEXIQUE DES ABRÉVIATIONS ___________________17
PRELIMINARY OPERATIONS ___________________ 18
GENERAL INFORMATION ______________________ 18
INSTALLATION ________________________________ 19
PROGRAMMING ______________________________ 20
COMMUNICATION_____________________________ 25
TECHNICAL CHARACTERISTICS________________ 31
GLOSSARY OF ABREVIATIONS__________________31
VORAUSGEHENDE KONTROLLEN ______________ 32
ALLGEMEINE HINWEISE _______________________ 32
INSTALLATION ________________________________ 33
KONFIGURATION______________________________ 34
KOMMUNIKATION _____________________________ 39
TECHNISCHE DATEN __________________________ 45
GLOSSAR DER ABKURZUNGEN_________________45
OPERAZIONI PRELIMINARI_____________________ 46
INFORMAZIONI GENERALI _____________________ 46
INSTALLAZIONE_______________________________ 47
PROGRAMMAZIONE___________________________ 48
COMMUNICAZIONE ___________________________ 53
CARATTERISTICHE TECNICHE _________________ 59
ELENCO DELLE ABBREVIAZIONI ________________59
Contents
GB
Sommaire
F
Inhaltsverzeichnis
D
Sommario
I
3
SOCOMEC - Réf. : 876 581 D
VOORAFGAANDE HANDELINGEN_______________ 60
ALGEMENE INFORMATIE_______________________ 60
INSTALLERING ________________________________ 61
PROGRAMMERING____________________________ 62
COMMUNICATIE ______________________________ 67
TECHNISCHE EIGENSCHAPPEN________________ 73
LEXICON VAN DE AFKORTINGEN________________73
OPERACIONES PREVIAS_______________________ 74
INFORMACIONES GENERALES _________________ 74
INSTALACIÓN_________________________________ 75
PROGRAMACIÓN _____________________________ 76
COMUNICACIÓN ______________________________ 81
CARACTERíSTICAS TÉCNICAS _________________ 87
LEXICO DE LAS ABREVIACIONES _______________87
OPERAÇÕES PRELIMINARES __________________ 88
INFORMAÇÕES GERAIS _______________________ 88
INSTALAÇÃO _________________________________ 89
PROGRAMAÇÃO ______________________________ 90
COMUNICAÇÃO_______________________________ 95
CARACTERÍSTICAS TÉCNICAS ________________ 101
LEXICO DAS ABREVIATURAS __________________101
Indice
E
Indice
P
Inhoud
NL
DIRIS A20
- RS485 - JBUS/MODBUS
®
10
SOCOMEC - Réf. : 876 581 D
DIRIS A20
- RS485 - JBUS/MODBUS
®
PROGRAMMATION
BIT DE STOP DE COMMUNICATION
>
Exemple : stop = 2
PROG
/ TEST
x 1
PROG
/ TEST
x 1 (2 bits)
x 2 (1 bit)
PROG
/ TEST
x 1
confirm
13
SOCOMEC - Réf. : 876 581 D
DIRIS A20
- RS485 - JBUS/MODBUS
®
F
DIRIS A20
- RS485 - JBUS/MODBUS
®
COMMUNICATION
LISTE DES PARAMETRES A VISUALISER (FONCTION 3)
Tableau des Taux de Distorsions Harmoniques (THD)
Adresse Nombre Libellé Unité
Déc. Hex. de mots
2304 900 1 thd I1 0,1%
2305 901 1 thd I2 0,1%
2306 902 1 thd I3 0,1%
2307 903 1 Réservé constructeur
2308 904 1 thd U12 0,1%
2309 905 1 thd U23 0,1%
2310 906 1 thd U31 0,1%
2311 907 1 thd V1 0,1%
2312 908 1 thd V2 0,1%
2313 909 1 thd V3 0,1%
DIRIS A20
- RS485 - JBUS/MODBUS
®
PRELIMINARY OPERATIONS
18
SOCOMEC - Réf. : 876 581 D
Functions
The optional Communication module must be
connected to the
DIRIS A20
(ref. 4825 0A20). It pro-
vides an RS485 serial link (2 or 3 wires) with
JBUS/MODBUS
®
protocol for the use of
DIRIS A20
from a PC or PLC.
General points
For a standard configuration, an RS 485 link is used to
connect up to 31
DIRIS A20
or
COUNTIS Ci
with a
PC or a PLC over a distance of 1500 metres, using
JBUS/MODBUS
©
protocol.
N 1 N 2 N n
R = 120
1200 M
R = 120
Programmable
controllers
Other systems
N 1
R = 120
Programmable
controllers
Other systems
repetor
RS485
0+- -+0
N n
R = 120
1200 M 1200 M
DIRIS 109 E GB
DIRIS 110 E GB
Recommendations:
You should use a shielded twisted pair (LIYCY type). In
a disturbed environment or large network (in terms of
length) we recommend the use of a shielded twisted
pair (type LIYCY-CY).
A repeater (1 channel) or an arrestor (4 channels)
should be used if you intend to exceed the distance
(1200 m) and/or maximum number (31) of
DIRIS
.
Please contact us for more information.
NB :
A 120 ohm resistance (found on the additional module)
must be fixed at both ends of the link.
Other solutions are available (modem, TCP-IP, optical
fibre, etc.). Please contact us
For personnel and product safety please read the
contents of these operating instructions carefully
before connecting.
Check the following points as soon as you receive
the
Diris A 20
package:
• the packing is in good condition,
• the product has not been damaged during transit,
the product reference number conforms to your
order,
• the package contains the product and the operating
instructions.
GENERAL INFORMATION
GB
19
SOCOMEC - Réf. : 876 581 D
DIRIS A20
- RS485 - JBUS/MODBUS
®
INSTALLATION
CONNECTION
The module is fitted onto the back of the
DIRIS A20
in one of the two positions provided.
DIRIS 342 A
DIRIS 343 A
ON
1
O
N
1
0V - +
R
=
120
Ω
DIRIS 347 A
Fix the module in one of the two positions.
Follow indications when connecting the terminal.
Switch on voltage supply.
The
DIRIS A20
must be switched off
DIRIS A20
- RS485 - JBUS/MODBUS
®
PROGRAMMING
20
SOCOMEC - Réf. : 876 581 D
Previous menu
Following menu
PROG
/ TEST
PROG
/ TEST
PROG
/ TEST
PROG
/ TEST
PROG
/ TEST
p.19
p.20
p.21
p.22
DIRIS A20
- RS485 - JBUS/MODBUS
®
PROGRAMMING
22
SOCOMEC - Réf. : 876 581 D
COMMUNICATION SPEED
>
Example : bds = 38,4 kbauds
PROG
/ TEST
x 1
PROG
/ TEST
x 1 (19,2 kbauds)
x 2 (38,4 kbauds)
x 3 (2,4 kbauds)
x 4 (4,8 kbauds)
x 5 (9,6 kbauds)
PROG
/ TEST
x 1
confirm
23
SOCOMEC - Réf. : 876 581 D
DIRIS A20
- RS485 - JBUS/MODBUS
®
PROGRAMMING
GB
COMMUNICATION PARITY
>
Example : PAr = EvEn
PROG
/ TEST
x 1
PROG
/ TEST
x 1 (Odd = odd parity)
x 2 (Even = par parity)
x 3 (no = without parity)
PROG
/ TEST
x 1
confirm
DIRIS A20
- RS485 - JBUS/MODBUS
®
PROGRAMMING
24
SOCOMEC - Réf. : 876 581 D
COMMUNICATION STOP BIT
>
Example : stop = 2
PROG
/ TEST
x 1
PROG
/ TEST
x 1 (2 bits)
x 2 (1 bit)
PROG
/ TEST
x 1
confirm
25
SOCOMEC - Réf. : 876 581 D
DIRIS A20
- RS485 - JBUS/MODBUS
®
GB
LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)
Table of values with allocated current and voltage winf-ding ratios on 2 words
Decimal Hexa. Number Text Unit
address address of words
768 300 2 phase 1 current mA
770 302 2 phase 2 current mA
772 304 2 phase 3 current mA
774 306 2 neutral current mA
776 308 2 phase to phase voltage U12 V/100
778 30A 2 phase to phase voltage U23 V/100
780 30C 2 phase to phase voltage U31 V/100
782 30E 2 phase to neutral voltage phase 1 V/100
784 310 2 phase to neutral voltage phase 2 V/100
786 312 2 phase to neutral voltage phase 3 V/100
788 314 2 frequency Hz/100
790 316 2
Σ
active power kW/100
792 318 2
Σ reactive power
kvar/100
794 31A 2
Σ
apparent power kVA/100
796 31C 2
Σ power factor
-: leading and +: lagging 0,001
798…839 31E…347 Reserved manufacturer
838 346 2 average value I1 max mA
840 348 2 average value I2 max mA
842 34A 2 average value I3 max mA
844 34C 2
Σ
active power + max kW/100
846…855 34E…357 Reserved manufacturer
856 358 2 active energy + kWh
858 35A 2 reactive energy + kvarh
860…915 35C…393 Reserved manufacturer
916 394 2 average value In max mA
The JBUS/MODBUS
®
used by the
DIRIS A20
involves
a dialogue using a master-slave hierarchical structure.
There are two possible dialogues:
the master communicates with a slave (
DIRIS
) and
waits for its reply
• the master communicates with all the slaves (
DIRIS
)
without waiting for their reply.
The mode of communication is the RTU (Remote
Terminal Unit) using hexadecimal characters of at least
8 bits.
According to the JBUS/MODBUS
®
protocol, transmission
time must be less than 3 silences, i.e. the emission time
of 3 characters so that the message is processed by
the
DIRIS
.
To correctly use information, the following functions are
important:
3: to read n words (maximum 128).
6: to write one word.
8: to diagnose exchanges between the master and
the slave via meters 1, 3, 4, 5 and 6.
16 : to write n words (maximum 128).
NB:
When selecting slave address 0, a message is sent to
all the instruments present on the network (only for
functions 6 and 16).
THE STANDARD COMMUNICATIONS FRAME
Slave address Function code Address Data CRC 16
DIRIS A20
- RS485 - JBUS/MODBUS
®
COMMUNICATION
The standard communications frame consists of:
DIRIS A20
- RS485 - JBUS/MODBUS
®
26
SOCOMEC - Réf. : 876 581 D
DIRIS A20
- RS485 - JBUS/MODBUS
®
COMMUNICATION
Table of values with allocated current and voltage winf-ding ratios on 1 word
LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)
Table of values with allocated current and voltage winf-ding ratios on 1 word
Decimal Hexa. Number Text Unit
address address of words
2816 B00 1 phase 1 current mA
2817 B01 1 phase 2 current mA
2818 B02 1 phase 2 current mA
2819 B03 1 neutral current mA
2820 B04 1 phase to phase voltage U12 V/100
2821 B05 1 phase to phase voltage U23 V/100
2822 B06 1 phase to phase voltage U31 V/100
2823 B07 1 phase to neutral voltage phase 1 V/100
2824 B08 1 phase to neutral voltage phase 2 V/100
2825 B09 1 phase to neutral voltage phase 3 V/100
2826 B0A 1 frequency Hz/100
2827 B0B 1
Σ active power
kW/100
2828 B0C 1
Σ reactive power
kvar/100
2829 B0D 1
Σ
apparent power kVA/100
2830 B0E 1
Σ power factor
-: leading and +: lagging 0,001
2831 B0F 1 average value I1 max mA
2832 B10 1 average value I2 max mA
2833 B11 1 average value I2 max mA
2834 B12 1 average value In max mA
2835 B13 1
Σ
active power + average value max kW/100
2836 B14 1
active power
+ < 10 000 kWh
2837 B15 1
active power
+ > 10 000 kWh
2838 B16 1
reactive power
+ < 10 000 kvarh
2839 B17 1
reactive power
+ > 10 000 kvarh
Decimal Hexa. Number Text Unit
address address of words
1792 700 1 phase 1 current mA
1793 701 1 phase 2 current mA
1794 702 1 phase 3 current mA
1795 703 1 neutral current mA
1796 704 1 phase to phase voltage U12 V/100
1797 705 1 phase to phase voltage U23 V/100
1798 706 1 phase to phase voltage U31 V/100
1799 707 1 phase to neutral voltage phase 1 V/100
1800 708 1 phase to neutral voltage phase 2 V/100
1801 709 1 phase to neutral voltage phase 3 V/100
1802 70A 1 frequency Hz/100
1803 70B 1
Σ
active power kW/100
1804 70C 1
Σ
reactive power kvar/100
1805 70D 1
Σ
apparent power kVA/100
1806 70E 1 Σ power factor
-: leading and +: lagging 0,001
1807…1826 710…722 Reserved manufacturer
1827 723 1 average value I1 max mA
1828 724 1 average value I2 max mA
1829 725 1 average value I3 max mA
1830 726 1
Σ
active power + average value max kW/100
1831…1834 727…72A Reserved manufacturer
1835 72B 1 active power + < 10 000 kWh
1836 72C 1 active power + > 10 000 kWh
1837 72D 1 reactive power + < 10 000 kvarh
1838 72E 1 reactive power + > 10 000 kvarh
1889…1890 72F…762 Reserved manufacturer
1891 763 1 average value In max mA
27
SOCOMEC - Réf. : 876 581 D
DIRIS A20
- RS485 - JBUS/MODBUS
®
GB
DIRIS A20
- RS485 - JBUS/MODBUS
®
COMMUNICATION
LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)
Total harmonic distorsion table
Decimal Hexa. Number Text Unit
address address of words
2304 900 1 thd I1 0,1%
2305 901 1 thd I2 0,1%
2306 902 1 thd I3 0,1%
2307 903 1 Reserved manufacturer
2308 904 1 thd U12 0,1%
2309 905 1 thd U23 0,1%
2310 906 1 thd U31 0,1%
2311 907 1 thd V1 0,1%
2312 908 1 thd V2 0,1%
2313 909 1 thd V3 0,1%
DIRIS A20
- RS485 - JBUS/MODBUS
®
COMMUNICATION
28
SOCOMEC - Réf. : 876 581 D
Decimal Hexa. Number Text Unit
address address of words
256 100 1 0 : no option
1 : metering option
2 : communication option /
257 101 / Reserved manufacturer
258 102 1 option slot 1
0xFF : no option
0x0 : metering option
0x1 :communication option /
259 103 1 option slot 2
0xFF : no option
0x0 : metering option
0x1 : communication option /
LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)
Option recognition table
NB: if several options are used, the number corres-
ponding to the option must be added.
Example : metering + communication will correspond
at number 3, that’s to say 1 + 2.
29
SOCOMEC - Réf. : 876 581 D
DIRIS A20
- RS485 - JBUS/MODBUS
®
COMMUNICATION
GB
Decimal Hexa. Number Text Unit
address address of words
512 200 1 Network type :
0 : 1BL
1 : 2BL
2 : 3BL
3 : 3NBL
4 : 4BL
5 : 4NBL /
513 201 1 CT secondary :
5 : 5A A
514 202 1 CT primary A
515…518 203…206 Reserved manufacturer
519 207 1
Synchronisation of I MAX :
2 : 2 sec
5 : 5 minutes
8 : 8 minutes
10 : 10 minutes
15 : 15 minutes
20 : 20 minutes
30 : 30 minutes
60 : 60 minutes /
520 208 1
Synchronisation of P MAX :
2 : 2 sec
5 : 5 minutes
8 : 8 minutes
10 : 10 minutes
15 : 15 minutes
20 : 20 minutes
30 : 30 minutes
60 : 60 minutes /
521 209 1 OUT allocation :
0 : kWh +
1 : kvarh + /
LIST OF PARAMETERS TO BE DISPLAYED OR PROGRAMMED (FUNCTIONS 3, 6 AND 16)
DIRIS A20
- RS485 - JBUS/MODBUS
®
30
SOCOMEC - Réf. : 876 581 D
DIRIS A20
- RS485 - JBUS/MODBUS
®
COMMUNICATION
Decimal Hexa. Number Text Unit
address address of words
1024 400 1 R.A.Z de :
Max 4I : 0x1
Max P+ : 0x2
kWh+ : 0x80
kvarh+ : 0x100
All parameters : 0x1000 /
RESET TO ZERO: ENERGY METERS AND MAX. VALUES (FUNCTION 6 )
LIST OF PARAMETERS TO BE DISPLAYED OR PROGRAMMED (FUNCTIONS 3, 6 AND 16)
522 20A 1 OUT impulse value :
0 : 0,1 kWh/kvarh
1 : 1 kWh/kvarh
2 : 10 kWh/kvarh
3 : 100 kWh/kvarh
4 : 1000 kWh/kvarh
5 : 10000 kWh/kvarh /
523 20B 1 OUT impulse duration :
1 : 100 ms
2 : 200 ms
3 : 300 ms
4 : 400 ms
5 : 500 ms
6 : 600 ms
7 : 700 ms
8 : 800 ms
9 : 900 ms /
Decimal Hexa. Number Text Unit
address address of words
Slave
05
Function
06
High-order
address
02
Low-order
address
00
High-order
value
00
Low-order
value
05
CRC 16
49F5
Example:
Configuration of a 4-wired unbalanced network
(4 NBL) for
DIRIS
number 5.
DIRIS A20
reply: Identical to message sent
NB:
To reset several parameters to zero, add the
corresponding figure indicated in the “text” column.
Example:
Reset Max P+ and kvarh + to zero: 2 + 100 = 102 (Hex).
DIRIS A20
reply: identical to the message sent.
Slave
05
Function
06
High-order
address
04
Low-order
address
00
High-order
value
01
Low-order
value
02
CRC 16
092F
31
SOCOMEC - Réf. : 876 581 D
DIRIS A20
- RS485 - JBUS/MODBUS
®
GB
DIRIS A20
- RS485 - JBUS/MODBUS
®
COMMUNICATION /
TECHNICAL CARACTERITICS
COMMUNICATION
SAVED COMMAND (RESET)
The following command should be done to save
programming parameters changes for
DIRIS
number 5.
NB:
DIRIS A20
will not reply to this command.
Slave
05
Function
06
High-order
address
06
Low-order
address
00
Values
0000
CRC 16
88C6
TECHNICAL CARACTERISTICS
RS485 2 or 3 wires half duplex
Protocol JBUS/MODBUS
®
protocol / RTU mode
Speed 2400 to 38400 Bauds
Galvanic insulation 2.5 kV
GLOSSARY OF ABBREVIATIONS
COM Communication
ADR Slave address
BDS Speed of communication in bauds
PAR Communication frame parity
NO Without parity
Even Even parity
Odd Odd parity
STOP Frame-stop beep
1 1 stop bit
2 2 stop bits
UL - CSA APPROVAL
Standard UL 61010-1
CSA-C22.2 No. 61010-1
Certificate UL file No: E257746
CSA report No. for DIRIS A20: 1810571
CSA report No. for DIRIS A40: 1810577
41
SOCOMEC - Réf. : 876 581 D
DIRIS A20
- RS485 - JBUS/MODBUS
®
D
DIRIS A20
- RS485 - JBUS/MODBUS
®
KOMMUNIKATION
LISTE DER ANZUZEIGENDEN PARAMETER (FUNKTION 3)
Tabelle der Klirfaktor
Dezimale Hexadez. Anzahl Bezeichnung Einheit
Adresse Adresse der Wörte
2304 900 1 thd I1 0,1%
2305 901 1 thd I2 0,1%
2306 902 1 thd I3 0,1%
2307 903 1 Reservierter Hersteller
2308 904 1 thd U12 0,1%
2309 905 1 thd U23 0,1%
2310 906 1 thd U31 0,1%
2311 907 1 thd V1 0,1%
2312 908 1 thd V2 0,1%
2313 909 1 thd V3 0,1%
55
SOCOMEC - Réf. : 876 581 D
DIRIS A20
- RS485 - JBUS/MODBUS
®
I
DIRIS A20
- RS485 - JBUS/MODBUS
®
COMUNICAZIONE
LISTA DEI PARAMETRI IN LETTURA (FUNZIONE 3)
Quadro delle armoniche corrente e tensione
Indirizzo Indirizzo Numero Descrizione Unità
decimale esadec. di parole
2304 900 1 thd I1 0,1%
2305 901 1 thd I2 0,1%
2306 902 1 thd I3 0,1%
2307 903 1 Fornitore riservato
2308 904 1 thd U12 0,1%
2309 905 1 thd U23 0,1%
2310 906 1 thd U31 0,1%
2311 907 1 thd V1 0,1%
2312 908 1 thd V2 0,1%
2313 909 1 thd V3 0,1%
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104

Socomec DIRIS A-20 Operating instructions

Type
Operating instructions
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI