M-system M3LM User manual

Type
User manual
M3LM
P. 1 / 7EM-2663-A
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone:
+
81
(
6
)
6659-8201 Fax:
+
81
(
6
)
6659-8510 E-mail: info@m-system.co.jp
POTENTIOMETER TRANSMITTER
(eld- and PC-congurable)
MODEL
M3LM
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
PACKAGE INCLUDES:
Signal conditioner ......................................................... (1)
I/O range and tag name label sheet ............................ (1)
MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures. For detailed information,
refer to the operating manual (EM-2663-B).
The M3LM with Option /A is programmable using the PC
configurator software. For detailed information on the PC
configuration, refer to the M3CON instruction manual. The
M3CON PC Configurator Software and operating manual
are downloadable at M-System’s web site: http://www.m-
system.co.jp.
POINTS OF CAUTION
CONFORMITY WITH UL
•ThisequipmentissuitableforuseinaPollutionDegree2
environment.
•Thisequipmentistobeusedwiththemaximumoperat-
ingvoltage30Vrmsand42.4Vpeakor60VDC.
•Theequipmentmustbemountedinsideasuitablereen-
closure.
•Operatingtemperature:-25to+55°C(-13to+131°F)
CONFORMITY WITH EU DIRECTIVES
•Theequipmentmustbemountedinsideapanel.
•Insertnoiseltersforthepowersource,inputandoutput
connectedtotheunit.COSELModelNAC-04-472,TDK
ModelZCAT3035-1330orequivalentisrecommended.
•Installlightningsurgeprotectorsforthosewiresconnect-
ed to remote locations.
•Theactualinstallationenvironmentssuchaspanelcon-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
POWER INPUT RATING & OPERATIONAL RANGE
•Locatethepowerinputratingmarkedontheproductand
confirm its operational range as indicated below:
10–32VDCrating:9–36V,approx.3W
SAFETY PRECAUTION
•Beforeyouremovetheunitormountit,turnoffthepower
supply and input signal for safety.
ENVIRONMENT
•Indooruse
•Whenheavydustormetalparticlesarepresentintheair,
install the unit inside proper housing with sufficient ven-
tilation.
•Donotinstalltheunitwhereitissubjectedtocontinuous
vibration.Donotsubjecttheunittophysicalimpact.
•Environmentaltemperaturemustbewithin-25to+65°C
(-13to+149°F)withrelativehumiditywithin0to95%RH
in order to ensure adequate life span and operation.
•Besurethattheventilationslitsarenotcoveredwithca-
bles, etc.
WIRING
•Do not install cables (power supply, input and output)
close to noise sources (relay drive cable, high frequency
line, etc.).
•Do not bind these cables together with those in which
noisesarepresent.Donotinstalltheminthesameduct.
AND ....
•Theunitisdesignedtofunctionassoonaspowerissup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
M3LM
P. 2 / 7EM-2663-A
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone:
+
81
(
6
)
6659-8201 Fax:
+
81
(
6
)
6659-8510 E-mail: info@m-system.co.jp
COMPONENT IDENTIFICATION
Body
SW Setting
Specifications
(side)
HOW TO OPEN THE COVER WHEN SETTING DIP SW
Holdatthetopandbottomoftheunitasshownbelowand
slide the housing cover gently to open until it hits the latch-
ing inside the unit.
• Housing Cover Fully Opened
Caution:
Handle the cover carefully to protect internal components from damage.
DO NOT pull beyond where the housing cover is latched. The plastic
housing may be damaged.
HOW TO SEPARATE THE EURO TYPE CONNECTOR
TERMINAL BLOCKS
Whenyouneedtoseparatetheeurotypeconnectortermi-
nal blocks from the transmitter body for wiring, insert a mi-
nus driver between the euro type connector terminal block
and the housing body, pull up the driver and pull out the
euro type connector terminal block.
INSTALLATION
DIN RAIL MOUNTING
SettheunitsothatitsDINrailadaptorisatthebottom.
Position the upper hook at the rear side of the unit on the
DINrailandpushinthelower.Whenremovingtheunit,
push down the DIN rail adaptorutilizinga minus screw-
driver and pull.
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the con-
nection diagram on the side of the unit.
+
+
CONFIGURATOR
JACK
7
8
11
12
OUTPUT
POWER
4
5
1
+
3
2
1
POTENTIOMETER
max.
min.
WIRING INSTRUCTIONS
•Applicablewiresize
Solid: 0.2to2.5mm
2
(0.55to1.75dia.)
Stranded: 0.2to2.5mm
2
Tinning wire ends may cause contact failure
and therefore is not recommended.
Ferruled: 0.2to1.5mm
2
(0.55to1.35dia.)
The following Phoenix Contact terminals are
recommended:
AI0,25-8YE 0.2to0.25mm
2
AI0,34-8TQ 0.25to0.34mm
2
AI0,5-8WH 0.34to0.5mm
2
AI0,75-8GY 0.5to0.75mm
2
AI1,0-8RD 0.75to1.0mm
2
AI1,5-8BK 1.0to1.5mm
2
•Exposewireconductorsby8mm(0.31”).
8 mm 8 mm
4 mm dia.
max.
4 mm dia.
max.
Wire exposure Recommended
ferruled wire
M3LM
P. 3 / 7EM-2663-A
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone:
+
81
(
6
)
6659-8201 Fax:
+
81
(
6
)
6659-8510 E-mail: info@m-system.co.jp
EXTERNAL DIMENSIONS mm (inch)
10 11 12
789
456
123
106 (4.17)
18 (.71) 110.5 (4.35)
62 (2.44)
[5 (.20)]
• When mounting, no extra space is needed between units.
DIN RAIL
35mm wide
EXTERNAL & INTERNAL VIEWS
Configuration DIP SW
8
SW2
SW1
SW3
7654321
ON
OFF
ON
OFF
4321
ON
OFF
4321
10 11 12
789
456
123
Configurator Jack
DOWN Button
UP Button
MODE Button
LED3 (LD3)
LED2 (LD2)
LED1 (LD1)
FRONT VIEW SIDE VIEW
ForM3LM-R4/A,theDIPswitchsettingisrequiredtoselectoutputtypesbeforesettingapreciseoutputrangeusingthePC
configurator software.
M3LM
P. 4 / 7EM-2663-A
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone:
+
81
(
6
)
6659-8201 Fax:
+
81
(
6
)
6659-8510 E-mail: info@m-system.co.jp
CONFIGURATION MODE & DIP SW SETTINGS
Whenyouprogramthetransmittermodule,twocongurationmodesareavailable:FieldCongurationusingDIPSW/con-
trol buttons, and PC Software. (The Option B type is for the field configuration only.)
TheinternalDIPswitchesareusedtocongureinputandoutputtype.Oncethemoduleiscongured,preciserangesare
set up with the front control buttons using a simulator connected to the input terminals and a multimeter connected to the
output terminals as a reference.
Thecalibratedinputandoutputrangesarestoredintheinternalmemory.ThemodulereadstheDIP-switch-calibratedcon-
figuration only once after the power supply is turned on. Set the switches with the power supply removed.
SelectableI/OtypeandrangesarelistedinTable7and8.
DIP SW CONFIGURATION MODE
TurntheSW2-8OFFtoenabletheDIPSW(FieldConguration)modeasshowninTable1.
SeeTable3toconguretheinputandTable5fortheoutput.
PC CONFIGURATION MODE
TurntheSW2-8ONtoenablethePCCongurationmodeasshowninTable1.Allprogrammablefeaturescanbesetupon
aPCregardlessofotherDIPSWsettingexceptthattheoutputtypemustbeselectedwiththeDIPSW1-1throughSW1-4
(See Table 6).
For detailed information on the PC configuration, refer to the M3CON instruction manual.
CONFIGURATION MODE (SW2) Table 1
MODE SW2-8
Configuration mode can be Confirmed
withthefrontLED.
DIPSW
PC
OFF
ON
FRONT CONTROL BUTTON LOCK (SW2) Table 2
Table 2 setting is applicable to firmware version 2.02 or
higher (marking on the product).
LOCK SW2-1
PC Configuration is not disabled when
the front control button function is
locked.
Unlock
Lock
OFF
ON
POTENTIOMETER (SW2) Table 3
RESISTANCE SW2-7 SW2-6 SW2-5 SW2-4
0 – 20kΩ
0 – 1000Ω
0 – 400Ω
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
0 – 200Ω
0–90Ω
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
BURNOUT (SW3) Table 4
BURNOUT SW3-2 SW3-1
No burnout
Upscale
Downscale
OFF
OFF
ON
ON
OFF
OFF
OUTPUT TYPE (SW2 & 1) Table 5
OUTPUT
SW2-3 SW2-2 SW1-4 SW1-3 SW1-2 SW1-1
0 – 20mA
-2.5–+2.5V
-10–+10V
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OUTPUT TYPE / PC CONFIG (SW1) Table 6
OUTPUT
SW1-4 SW1-3 SW1-2 SW1-1
0 – 20mA
-2.5–+2.5V
-10–+10V
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
INPUT TYPE & RANGE Table 7
INPUT TYPE MINIMUM SPAN MAXIMUM RANGE
Potentiometer
2.5Ω
10Ω
10Ω
0–90Ω
0 – 200Ω
0 – 400Ω
0 – 1000Ω
0 – 20kΩ
OUTPUT TYPE & RANGE Table 8
OUTPUT TYPE MINIMUM SPAN MAXIMUM RANGE CONFORMANCE RANGE
DCCurrent
DCVoltage,NarrowSpans
DCVoltage,WideSpans
1mA
250mV
1V
0 to 20mA
-2.5to+2.5V
-10to+10V
0 to 24mA
-3to+3V
-11.5to+11.5V
M3LM
P. 5 / 7EM-2663-A
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone:
+
81
(
6
)
6659-8201 Fax:
+
81
(
6
)
6659-8510 E-mail: info@m-system.co.jp
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2)DIPSWsetting:Checkthattheswitchesaresettoap-
propriate positions.
3) Power input voltage: Check voltage across the terminal
11 – 12 with a multimeter.
4) Input:Checkthattheinputsignaliswithin0–100%of
full-scale.
If the potentiometer or its extension wires are broken,
the output goes over 100% (below 0% with downscale
protection) due to burnout function. Confirm the status
indicator LED pattern and check leadwires in such a
case.
5) Output: Check that the load resistance meets the de-
scribed specifications.
I/O RANGING & FINE ADJUSTMENTS
After the DIP SW setting is complete, set up the precise
input and output range using the front control buttons. Be
sure that the front control button function is enabled with
theDIPswitchsetting.
The front LEDs’ colors and blinking patterns help you to
easily identify the transmitter’s status and confirm the set-
up actions in each step of Calibration Modes. Please read
the following explanations referring to “Calibration Flow
Chart”inPage5.
PREPARATION (e.g. M3LM-R4/A)
1) MounttheDIP-SW-conguredM3LMontoaDINrail.
2) Connect the M3LM to a potentiometer and a multimeter
andtoaDCpowersourceasshownbelow.
3) Turn the power supply on and wait for 10 minutes.
7
8
11
12
M3LM
Multimeter
+
DC Power Source
+–
4
5
1
+
3
2
1
POTENTIOMETER
max.
min.
INPUT & OUTPUT RANGING
[Example] Setting the input to 0 – 1000Ω and the output to
1–5VDC
1) RunMode:ConrmthatthegreenLEDisblinking(mod-
elM3LM-x/A)orthegreenLEDturnson(modelM3LM-
x/B).
2) InputCongurationMode:PressMODEbuttonforlong-
erthan5secondsuntiltheLD1redLEDisONandthe
LD2redLEDisblinking.
3) 0% Input Ranging: Apply the desired minimum input
level(e.g.0Ω)fromthepotentiometerandpushDOWN
buttonuntiltheLD1blinksforapprox.2sec.andthen
turnsOFF.Whenyoureleasethebutton,theLD1isre-
turned to ON.
TheblinkingLD1meansthatthevalueisstoredinthe
memory.IftheLEDdoesnotchange,theenteredlevel
may be inappropriate: too small a span, or out of usable
range (same for all steps).
4) 100%InputRanging:Applythedesiredmaximuminput
level (e.g. 1000Ω) from the potentiometer and push UP
buttonuntiltheLD1blinksforapprox.2sec.andthen
turnsOFF.Whenyoureleasethebutton,theLD1isre-
turned to ON.
5) Output Conguration Mode: Push MODE button and
conrmthattheLD3redlightinsteadofLD2isblinking.
6) 0%OutputRanging:Increaseordecreasethesimulated
input until the meter shows the desired minimum out-
put level (e.g. 1V). Push DOWN button until the LD1
blinksforapprox.2sec.andthenturnsOFF.Whenyou
releasethebutton,theLD1isreturnedtoON.
7) 100% Output Ranging: Increase or decrease the simu-
lated input until the meter shows the desired maximum
output level (e.g. 5V). Push UP button until the LD1
blinksforapprox.2sec.andthenturnsOFF.Whenyou
releasethebutton,theLD1isreturnedtoON.
8) RunMode:Programmingcomplete,pushMODEbutton
andconrmthatonlytheLD1greenLEDisblinking.
ZERO & SPAN ADJUSTMENTS
Afterthetransmitterisinstalledandoperational,nezero
and span tuning can be performed as explained below. Both
zeroandspanareadjustablewithin±15%.
1) RunMode:ConrmthatthegreenLEDisblinking(mod-
elM3LM-x/A)orthegreenLEDturnson(modelM3LM-
x/B).
2) FineZero Calibration Mode:Press MODE button for 1
or2secondsuntiltheLD1redLEDisONandtheLD2
greenLEDisblinking.
3) UseUP(increase)andDOWN(decrease)buttonstoad-
justtheoutputto0%.
4) Fine Span Calibration Mode: Push MODE button and
conrmthattheLD3greenLEDinsteadofLD2isblink-
ing.
5) UseUP(increase)andDOWN(decrease)buttonstoad-
justtheoutputto100%.
6) RunMode:PushMODEbuttonandconrmthatonlythe
LD1greenLEDisblinking.
Note 1: Calibration steps can be skipped when not needed
byrepeatingpushingMODEbuttons.
Note 2: There is no stated order of setting 0% and 100%
levels or no limitation of entering values for multiple times
within one step of Calibration Mode. Signal level is stored
eachtimetherespectiveUPorDOWNbuttonispressed.
M3LM
P. 6 / 7EM-2663-A
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone:
+
81
(
6
)
6659-8201 Fax:
+
81
(
6
)
6659-8510 E-mail: info@m-system.co.jp
I/O RANGE LABEL
Blank I/O range labels are included in the product pack-
age.Writeintheconguredrangesandputthelabelon
the side as shown below.
INPUT
OUTPUT
I/O Range Label (included in the product package)
POWER ON
Amber LED
Green LED
Control
Buttons
Red LED
OFF
ON
Blink
RUN MODE
LD2
LD3
A
G
RUN MODE
LD2
LD3
G
R
LD1
LD2
LD3
LD1
LD2
LD3
0% INPUT
CONFIGURED
100% INPUT
CONFIGURED
INPUT
CALIBRATION
MODE
LD1
OUTPUT
CALIBRATION
MODE
LD2
LD3
LD1
LD2
LD3
0% OUTPUT
CONFIGURED
100% OUTPUT
CONFIGURED
G
G R
R
R
R
G
R
R
G
Fine Adjustments ? I/O Ranging ?
PUSH
MODE
1 – 2 s PRESS & HOLD
MODE
> 5s
PUSH
MODE
PUSH
MODE
PUSH
MODE
PUSH
MODE
PUSH
DOWN
PUSH
UP
DOWN
UP
MODE
PUSH
DOWN
PUSH
UP
When you set 0% or 100% input/output ranges,
keep pressing UP or DOWN button until the
LD1 blinks for approx. 2 seconds and turns off,
which indicates the setup is complete.
When you release the button, the LD1 is returned
to ON.
If the LED does not change, the entered level may
be inappropriate: e.g. out of usable range.
*
For the model M3LM-x/A, the green LED is blinking.
For the model M3LM-x/B, the green LED turns on.
FINE ZERO
CALIBRATION MODE
UP or DOWN
FINE SPAN
CALIBRATION MODE
UP or DOWN
Apply simulated 0% input signal.
Apply simulated 100% input signal.
Adjust simulated input until the output meter
shows desired 0% output.
Adjust simulated input until the output meter
shows desired 100% output.
Once the transmitter
enters the fine zero
calibration mode,
the output goes to
preadjusted 0%
value regardless
of the present input
signal.
Once the transmitter
enters the fine span
calibration mode,
the output goes to
preadjusted 100%
value regardless
of the present input
signal.
LD1*
LD1*
CALIBRATION FLOW CHART
M3LM
P. 7 / 7EM-2663-A
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone:
+
81
(
6
)
6659-8201 Fax:
+
81
(
6
)
6659-8510 E-mail: info@m-system.co.jp
LD1
LD2
LD3
A
A
A
LD1
LD2
LD3
G
LD1
LD2
LD3
G
LD1
LD2
LD3
LD1
LD2
LD3
A
LD1
LD2
LD3
A
G
G
LD1
LD2
LD3
A
G
LD1
LD2
LD3
A
A A
R
R
R
G
NORMAL OPERATION (RUN) MODE
ERROR MODE
System Error
Indicates the CPU’s communication error.
DIP SW Error
DIP SW configuration is inappropriate.
Check the DIP SW setting referring to Tables 2 – 6.
Burnout in PC Configuration Mode (Option A) Burnout in DIP SW Configuration Mode
PC Configuration RUN Mode (Option A)
The transmitter is configured via PC and
is in normal operating conditions.
DIP SW Configuration RUN Mode
The transmitter is configured via DIP SW and
is in normal operating conditions.
Output Saturated in PC Configuration Mode
(Option A)
The output is below -15% or above +115%.
Output Saturated in DIP SW Configuration Mode
The output is below -15% or above +115%.
Amber LED
Green LED
Red LED
OFF
ON
Blink
A
G
R
STATUS INDICATOR LED
CombinationsofthethreefrontLEDs(LD1,LD2,LD3)in-
dicate the transmitter’s operating status by different blink-
ing patterns.
Examples are shown below.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7