Code Explanation Code Explanation Code Explanation
OC1 Overcurrent trip during
acceleration L in Input phase loss protection OLU Overload protection
OC2 Overcurrent trip during
deceleration OPL Output phase loss protection Er1 Memory error
OC3 Overcurrent trip during steady
speed OH1 Overheat protection for
heat sink Er2 Remote keypad
communications error
OU1 Overvoltage trip during
acceleration OH2 External alarm input trip Er3 CPU error
OU2 Overvoltage trip during
deceleration OH4 PTC thermistor for motor
protection Er6 Operation protection
OU3 Overvoltage trip during steady
speed dbH Overheat protection for braking
resistor Er8 RS485 communications error
LU Undervoltage protection OL1 Electronic thermal overload
relay ErF Data save error during
undervoltage
Code Description Default Settings Comments/change to:-
F03 Maximum Frequency 50Hz (25.0 -400Hz), sets desired maximum motor speed.
F07 Acceleration Time 6.00 Seconds (0 -3600 Seconds), sets time for motor to accelerate
0hz to Maximum Frequency.
F08 Deceleration Time 6.00 Seconds (0-3600 Seconds), sets time for motor to decelerate
from Maximum Frequency to 0Hz.
F09 Torque Boost *according to Inverter
capacity (0.0 - 20.0), sets torque boost type for application.
F15 Frequency Limiter (high) 70.00Hz (0.0 - 400Hz), sets the Frequency upper limit.
F16 Frequency Limiter (low) 0.00Hz (0.0 - 400Hz), sets the Frequency lower limit.
F26 Carrier Frequency 15Khz (0.75 - 15Khz), sets the Motor sound level.
F37 Load Type Selection 1 (Constant Torque) (0-5), sets the load type required for application.
F42 Control Mode Selection 0 (0-4), sets V/f or Torque Vector mode options.
E52 Menu Display Mode 0 (0-2), sets which menus can be accessed.
H69 Automatic Deceleration 0 (0-4), sets deceleration mode for application.
Code Description Default Settings Comments/change to:-
F01 Frequency Command 0: UP/DOWN keys on Keypad 1: 0-10Vdc input (terminal 12)
2: 0/4-20mA input (terminal C1)
F02 Operation Method 0: RUN/STOP keys on keypad 1: PLC-FWD (run forward) PLC-REV (run
reverse)
F04 Motor Base Frequency 50.0Hz Frequency from Motor data plate (Hz)
F05 Motor rated voltage at Base
Frequency 230 (200v), 400(400v)
0: Output voltage ~ supply voltage
80-240v (for 200v rated drives)
160-500v (for 400v rated drives)
F11 Motor overload 1-135% inverter rated current Motor rated current from data plate (A)
P02 Motor Capacity Nominal Motor power (kw) Motor rated power from data plate (KW)
P03 Motor rated current *according to inverter capacity Motor rated current from data plate (A)
Single phase input Three phase input
InverterType(VXR) 3A-1 5A-1 8A-1 11A-1 1A5-4 2A5-4 3A7-4 5A5-4 9A-4 13A-4 18A-4 24A-4 30A-4
Output Ratings
Nominal Applied Motor Kw 0.4 0.75 1.5 2.2 0.4 0.75 1.5 2.2 45.5 7.5 11 15
Rated capacity KVA 1.1 1.9 34.1 1.1 1.9 2.8 4.1 6.8 9.9 13 18 22
Rated voltage V Three Phase 200v/50Hz, 200-230v/
60Hz Three Phase, 380-415v/50Hz 380-460/60Hz
Rated low PWM Freq. A 35811 1.5 2.5 3.7 5.5 913 18 24 30
Current high PWM Freq.A 2.5 4.2 710
Overload capacity A 150% of rated output current for 1 min 150% of rated output current for 1 min
200% of rated output current for 0.5s 200% of rated output current for 0.5s
Input Ratings
Min supply capacity KVA 0.7 1.3 2.4 3.5 0.6 1.1 22.9 4.9 7.4 10 15 20
Rated voltage V Single Phase 200-240v 50/60Hz Three Phase 380-480v, 50/60Hz
MCCB rating with DCR A 610 16 20 66610 10 15 20 30 40
without DCR A 10 16 20 32 10 16 20 30 40 50 60
Fuse rating with DCR A 20 20 32 40
without DCR A
Cable Sizes
Mains supply with DCR
mm2 2.5 2.5
2.5 4
2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
Mains supply without DCR 4 6
Motor cable
2.5
2.5
Earth cable 4
Braking resistor cable 2.5
Unscreened Cable Max 50 100 100
Screened cable Length 30 60 80
Braking resistor Ω100 40 200 160 130 80 60 40 35
Braking resistor W 200 400 200 400 800 900 1400 1400
Cooling Method Natural Cooling Fan Cooling Natural Cooling Fan Cooling
Enclosure IP IP20 IP20
Weight Kg 0.6 0.8 1.7 2.3 1.1 1.2 1.7 1.7 2.3 3.4 3.6 6.1 7.1
Essential Function codes for Quick basic set up
Application specific settings