10
Selection of Installation Location and Precautions
Model Power supply
(V,Ph,Hz)
Capability
of circuit
breaker
(A)
Min.
sectional
area of earth
lead (mm2)
Min.
sectional
area of
power cord
(mm2)
The number
of the
cord(N)
GMV-Pdhm224W/Na-M 380~415,3 ,50 32 6.0 6.0 5
GMV-Pdhm280W/Na-M 380~415,3 ,50 32 6.0 6.0 5
GMV-Pdhm335W/Na-M 380~415,3 ,50 40 10.0 10.0 5
GMV-Pdhm400W/Na-M 380~415,3 ,50 40 10.0 10.0 5
GMV-Pdhm450W/Na-M 380~415,3 ,50 40 10.0 10.0 5
GMV-Pdhm504W2/Na-M 380~415,3 ,50 63 25.0 25.0 5
GMV-Pdhm560W2/Na-M 380~415,3 ,50 63 25.0 25.0 5
GMV-Pdhm615W2/Na-M 380~415,3 ,50 80 35.0 35.0 5
GMV-Pdhm680W2/Na-M 380~415,3 ,50 80 35.0 35.0 5
GMV-Pdhm730W2/Na-M 380~415,3 ,50 80 35.0 35.0 5
GMV-Pdhm800W2/Na-M 380~415,3 ,50 80 35.0 35.0 5
GMV-Pdhm850W2/Na-M 380~415,3 ,50 80 35.0 35.0 5
GMV-Pdhm900W2/Na-M 380~415,3 ,50 80 35.0 35.0 5
GMV-Pdhm960W3/Na-M 380~415,3 ,50 100 50.0 50.0 5
GMV-Pdhm1010W3/Na-M 380~415,3 ,50 100 50.0 50.0 5
GMV-Pdhm1065W3/Na-M 380~415,3 ,50 125 70.0 70.0 5
GMV-Pdhm1130W3/Na-M 380~415,3 ,50 125 70.0 70.0 5
GMV-Pdhm1180W3/Na-M 380~415,3 ,50 125 70.0 70.0 5
GMV-Pdhm1250W3/Na-M 380~415,3 ,50 125 70.0 70.0 5
GMV-Pdhm1300W3/Na-M 380~415,3 ,50 125 70.0 70.0 5
GMV-Pdhm1350W3/Na-M 380~415,3 ,50 125 70.0 70.0 5
GMV-Pdhm1410W4/Na-M 380~415,3 ,50 160 95.0 95.0 5
GMV-Pdhm1460W4/Na-M 380~415,3 ,50 160 95.0 95.0 5
GMV-Pdhm1515W4/Na-M 380~415,3 ,50 160 95.0 95.0 5
GMV-Pdhm1580W4/Na-M 380~415,3 ,50 160 95.0 95.0 5
GMV-Pdhm1630W4/Na-M 380~415,3 ,50 160 95.0 95.0 5
GMV-Pdhm1700W4/Na-M 380~415,3 ,50 160 95.0 95.0 5
GMV-Pdhm1750W4/Na-M 380~415,3 ,50 160 95.0 95.0 5
GMV-Pdhm1800W4/Na-M 380~415,3 ,50 160 95.0 95.0 5
Note:The specification of power cord mentioned hereby is defined as the required specification when wiring
with BV single core cable (2 ~ 4 pieces) under the cover of PVC pipe, and environment temperature shall be
at 40℃; Air switch shall be selected according to 40℃ temperature condition, and shall in “D” type. if the
installation conditions on site change, please consider the modification on the required specification of
Power cord and Air switch, according to the specification manual provided by manufacture.
● Grounding Requirement
As air☆-conditioning unit is of Class 1 electrical appliance, reliable grounding measures must be taken for