ROOTECH Accura 2500 User guide

Category
Measuring, testing & control
Type
User guide
ACCURA 2500
High Accuracy Digital Power Meter
Gives simple power measurements
User Guide[English]
Rev 1.7 2016/01/12
Page 2
Page 3
Notice
Danger
Indicates the presence of
dangerous voltage which can cause severe injury or death
to persons if proper precautions are not followed.
Warning
Alerts
the user to the presence of hazards which can cause somewhat injury to
pe
rsons, damage to property or damage to the device itself, if proper precautions
are not followed.
Note
Indicates the users attention to installation, operating and maintenance instructions.
Electrical Symbols
Indicates alternative voltage or current.
Indicates direct voltage or current.
Installation Considerations
Installation and operation of Accura 2500 meter should be performed only by qualified,
competent personnel that have appropriate training and experience with high voltage and current
devices.
Danger
Failure to observe the following instructions may result in severe injury or death.
During normal operation of the Accura 2500 meter, hazardous voltages are present on
its terminal strips.
Standard safety precautions are followed while performing any installation or service
work[removing PT fuses, shorting CT secondaries, etc].
Do not access to terminal strips of the Accura 2500 meter after installation.
Page 4
Warning
Observe the following instructions, or permanent damage to the meter may occur.
Do not apply Accura 2500 to voltages and currents that exceed Input ratings of PT and
CT.
Limitation of Liability
Rootech Inc. reserves the right to make changes in the device specifications shown in this Users
Guide without notice. Rootech Inc. advises customers to obtain the latest specifications of device
before giving orders to confirm that the information being relied on by the customer is up to date.
In the absence of written agreement to the contrary, Rootech Inc. assumes no liability for Rootech
Inc. applications assistance, customers system design, or infringement of patents or copyrights of
third parties by or arsing from the use of devices described herein.
Except to the extent prohibited by applicable law, under no circumstances shall Rootech Inc. be
liable for consequential damages sustained in connection with said product and Rootech Inc.
neither assumes nor authorizes any representative or other person any obligation or liability other
than such as is expressly set forth herein.
2006 Rootech Inc.
The information contained in this document is believed to be accurate at the time of publication,
however, Rootech Inc. assumes no responsibility for any errors which may appear here and
reserves the right to make changes without notice.
Page 5
Standard Compliance
CE Approved
EN61326 and IEC61010
MEASURING EQUIPMENT
35DX
E258934
QMS-1347 KAB-QC-09
Page 6
Warranty Information
For products and software that are sold or licensed by Rootech Inc. during the period from the
date of receipt by you until the present, Rootech warrants only to the original purchaser
The purchased products other than software shall be substantially free from material defects in
material and workmanship by Rootech for two years from the date receipt by you.
The software itself is provided as is without any warranty of any kind.
Limitation of Warranty
These limited Warranties shall not apply to any product that has been subject to alteration,
accident, misuse, abuse, neglect or failure to exactly follow Power Measurement's instructions for
operation and maintenance.
In order for the original purchaser to make a claim under the warranties described above, the
original purchaser must promptly contact Rootech headquarter. After receiving such notice,
Rootech may either in Rootechs sole discretion, examine the product at the original purchasers
site or issue shipping instructions to the original purchaser to return the relevant product to
Rootech for examination at the original purchasers expense, transportation charges prepaid.
If after examining the product Rootech reasonably confirms that such examined product does not
meet the warranties, then the original purchasers sole remedy and Rootechs sole obligation or
liability shall be, at Rootechs option, to repair, replace or refund the price paid for that product.
Regardless of whether any remedy set forth herein fails of its essential purpose, except to the
extent the following limitation is prohibited by applicable law, Rootech shall not, in any event or
under any legal claim or theory, be liable to the original purchaser or any other person or entity
for special, indirect, incidental, punitive, liquidated, special or consequential damages whatsoever
with respect to any purchased product, including, without limitation, business interruption, loss of
use, profit or revenue, even if Rootech has been advised of the possibility of such damages. To the
extent that a limitation or exclusion of consequential damages are prohibited by applicable law,
then Rootechs liability shall be limited to twice the amount of the relevant purchased product.
Rootech shall not be liable for any claim- other than a claim solely for the breach of one of the
Page 7
above warranties that is made in accordance with the above described procedures- made by the
original purchaser, its employees, agents, or contractors for any loss, damage, or expense
incurred due to, caused by, or related to any purchased product
Any technical assistance provided by Rootech's personnel or representatives in system design shall
be deemed to be a proposal and not a recommendation. The responsibility for determining the
feasibility of such proposals rests with the original purchaser and should be tested by the original
purchaser.
It is the original purchaser’s responsibility to determine the suitability of any product and
associated documentation for its purposes. The original purchaser acknowledges that 100% "up"
time is not realizable because of possible hardware or software defects. The original purchaser
recognizes that such defects and failures may cause inaccuracies or malfunctions.
Only the terms expressed in these limited Warranties shall apply and no distributor, corporation or
other entity, individual or employee of Rootech or any other entity is authorized to amend, modify
or extend the Warranties in any way.
Page 8
Revision History
The following versions of the Accura 2500 Users Guide have been released.
Revision #
Description
Revision 1.0 2006. 06. 30 Initial draft
Revision 1.1 2007. 07. 13 Mounting modified
Revision 1.2 2009. 11. 26 Voltage input range modified
Revision 1.3 2012. 05. 22 Address modified
Revision 1.5 2015. 03. 02 Demand display added
Revision 1.6 2015. 06. 12 Standard Logo Image modified
Revision 1.7 2016. 01. 12 IrDA deleted
Page 9
Contents
Chapter 1 Introduction .................................................................................................................... 12
Overview ....................................................................................................................................... 12
Power Measurements .............................................................................................................. 12
Accuracy ................................................................................................................................ 12
CE/UL Safety and Reliability .................................................................................................... 12
Display Easy to Read .............................................................................................................. 12
Features ........................................................................................................................................ 13
Measurement ......................................................................................................................... 13
Power Supply.......................................................................................................................... 13
Applications ................................................................................................................................... 14
True RMS Measurements robust to harmonics .......................................................................... 14
Compatibility with Analog Meters ............................................................................................ 14
Parameters .................................................................................................................................... 15
Chapter 2 Mounting ........................................................................................................................ 16
Environmental Conditions ....................................................................................................... 16
Enclosure Considerations ........................................................................................................ 16
Before You Begin ........................................................................................................................... 17
Meter Overview ...................................................................................................................... 17
Meter Dimensions .................................................................................................................. 18
Step 1: Mounting ......................................................................................................................... 19
Sequence ............................................................................................................................... 19
Step 2: Voltage and Current Inputs ............................................................................................... 20
Voltage Input .......................................................................................................................... 20
Current Input ......................................................................................................................... 21
Wiring Diagram Using External PTs ......................................................................................... 22
Direct Diagram Using No PTs .................................................................................................. 25
Step 3: Wire the Power Supply and Ground Terminal ....................................................................... 28
Power Supply.......................................................................................................................... 28
Ground Terminal .................................................................................................................... 28
Step 4: Add a Cover/Power Up the Meter ..................................................................................... 29
Add a Cover .......................................................................................................................... 29
Power Up the Meter ................................................................................................................ 29
Chapter 3 Meter Operation/Setup .................................................................................................. 30
Display Mode ................................................................................................................................ 30
Page 10
Setup Mode ................................................................................................................................... 34
Reset Mode .................................................................................................................................... 35
System Mode ................................................................................................................................. 36
Reactive Calculation Method ................................................................................................... 37
APPENDIX A Standard Specification ................................................................................................ 39
APPENDIX B Standard Compliance ................................................................................................. 40
APPENDIX C Test Report ................................................................................................................ 41
Measurement Test .......................................................................................................................... 41
Reliability Test ................................................................................................................................ 42
INDEX............................................................................................................................................ 43
Page 11
Figures
Fig 1.1 Front Side ................................................................................................................... 17
Fig 1.2 Rear Side .................................................................................................................... 17
Fig 1.3 Front View .................................................................................................................. 18
Fig 1.4 Rear View ................................................................................................................... 18
Fig 1.5 Side View ................................................................................................................... 18
Fig 1.6 ANSI 4” ...................................................................................................................... 19
Fig 1.7 DIN96 ........................................................................................................................ 19
Fig 1.8 Voltage and Current Connector ................................................................................... 20
Fig 1.9 Single Phase 2 Wires, Wiring Mode = 1P2U ................................................................ 22
Fig 1.10 Three Phase 3 Wire Open Delta Using 2CTs, Wiring Mode = 3P3O ............................ 23
Fig 1.11 Three Phase 3 Wire Open Delta Using 3CTs, Wiring Mode = 3P3O ............................ 23
Fig 1.12 Three Phase 4 Wires Using 3 PTs and 3 CTs, Wiring Mode = 3P4U ............................. 24
Fig 1.13 Single Phase 2 Wire Direct , Wiring Mode = 1P2U ..................................................... 25
Fig 1.14 Single Phase 3 Wire Direct Using 2 CTs, Wiring Mode = 1P3U ................................... 26
Fig 1.15 Three Phase 3 Wire Open Delta Direct, Wiring Mode = 3P3O .................................... 26
Fig 1.16 Three Phase 3 Wire Open Delta Direct Using 3 CTs, Wiring Mode = 3P3O ................. 27
Fig 1.17 Three Phase 4 Wire Direct Using 3 CTs, Wiring Mode = 3P4U .................................... 27
Fig 1.18 Wiring of Power Supply and Ground Terminal ............................................................ 28
Fig 1.19 Cover ....................................................................................................................... 29
Fig 2.1 Measurement Groups ................................................................................................. 30
Fig 3.2 P, Q[according to general calculation] .......................................................................... 37
Page 12
Chapter 1 Introduction
Overview
Power Measurements
Accura 2500 is a high accuracy digital power meter, suited to power measurements. The device is
applied to a variety of applications, electrical facilities, intelligent building system, factory,
generator and etc, making measurements of voltage, current, power, frequency, power factor, and
demand.
Accuracy
The measuring accuracy is the most important criterion to evaluate the reliability of energy
management system. Actually low accuracy makes it hard for customers to precisely manage
energy, causing inequality of energy between incoming feeder and sum of load sides. Accura
2500 makes ±0.2% high accuracy measurements for voltage and current, and conforms to
IEC62053-22 class 0.5S for power and energy. This makes it possible to solve the problem with
energy inequality.
CE/UL Safety and Reliability
The structure- framework, circuit, fire - of Accura 2500 conforms to safety standard,
CE[IEC61010], UL[UL61010-2, 2nd edition]. Particularly the device provides pass-through busbar,
allowing CT leads to be terminated on the device. This eliminates any possible point of failure at
the device.
Display Easy to Read
Accura 2500 is implemented with large-size 7 segments[3 line 0.56] distinguished with the other
models. This makes customers easily read voltage, current, power at the same time.
Page 13
Features
Measurement
64 Sampling/Cycle True RMS
IEC 62053-22 Class 0.5S
50, 60Hz
Phase voltage, line to line voltage, current
Power, energy[active], power factor, frequency
Fundamental component, True RMS of current
4 Quadrant Power
Maximum, minimum
Power Supply
AC 85 ~ 265V, 50/60Hz
DC 100 ~ 300V
Burden: 10VA
Page 14
Applications
True RMS Measurements robust to harmonics
Most of energy environments consist of nonlinear loads, such as industrial load, rectifier, power
electronic device, electric furnace and etc. this causes fatal distortion of voltage and current
waveforms. Accura 2500 makes high accuracy True RMS measurements for voltage and current
distorted with harmonics.
Compatibility with Analog Meters
Accura 2500 mounts directly in ANSI C39.1[4” Round] or DIN 96. this is perfect for new
installations and for existing panels. In new installations, simply use existing DIN or ANSI punches.
For existing panels, pull out old analog meters and fit the device in its cutout.
Page 15
Parameters
Realtime
1
Average
2
Total
3
Maximum
4
Minimum
5
Phase voltage
Line to line voltage
Current
Power Active
Reactive
Apparent
Energy Active
Frequency
Power factor
1Instaneous measuring. 2Average of three phase parameters. 3Total sum of three phase parameters.
4If realtime measurements exceed maximums, the maximums will be updated, the measurements being
ignored within 10msecs after power up.
5If realtime measurements is less than minimums, the minimums will be updated, the measurements being
ignored within 10msecs after power up.
Note
The Maximums and minimums will not be updated with no power-up.
Page 16
Chapter 2 Mounting
Environmental Conditions
The Accura 2500 should be mounted in a dry, dirt free location away from heat sources and very
high electric fields. To operate properly and effectively, environmental conditions should range
within the following guidelines
Items Acceptable Range
Position Indoor use
Operating Temp -20 ~ 70°C[-4 ~ 158]
Storage Temp -40 ~ 85°C[-40 ~ 185]
Operating Humidity 5 ~ 95% Non condensing
Enclosure Considerations
The enclosure the Accura 2500 is mounted in (typically a switchgear cabinet) should protect the
device from atmospheric contaminants such as oil, moisture, dust, and corrosive vapors, or other
harmful airborne substances. The mounting enclosure should be positioned such that the doors
may be opened fully for easy access to the Accura 2500 wiring and related components to allow
for convenient troubleshooting.
Warning
T
he meter should be installed in a switchgear cabinet or similar enclosure to ensure the terminal
strips on the meter base are not user accessible after installation.
Mount the meter in a dry location free from dirt and corrosive vapors. Once installed, no cleaning
of the device is necessary.
Page 17
Before You Begin
Before installing the meter, observe the instructions in this guide and read the safety precautions
presented on the Installation Considerations page.
Danger
Power up after the voltage and current wiring is completed.
Meter Overview
Fig 1.1 Front Side Fig 1.2 Rear Side
Page 18
Meter Dimensions
Fig 1.3 Front View Fig 1.4 Rear View
Fig 1.5 Side View
Page 19
Step 1: Mounting
Sequence
1. Remove connector on the bottom of the meter.
2. fit the meter into cutout[ANSI 4 or DIN96]
Fig 1.6 ANSI 4 Fig 1.7 DIN96
Note
The meter is mounted on switchgear boards (metal cabinet) in electrical facilities.
Page 20
Step 2: Voltage and Current Inputs
Fig 1.8 Voltage and Current Connector
Voltage Input
Pin name V1, V2, V3, Vn
Connector Terminal block
Wire 2.1 to 3.5 mm2[ 14 to 12 AWG]
Rating1 0 ~ 600V 3 ~ L-L[Line to line], 0 ~ 457V 3 ~ L-N[Line to neutral]
Burden 0.02VA/phase @220V
Impedance 3MΩ/phase
Compliance Pollution degree 2, Installation Category
Warning
In three phase 3 wire open delta direct, line to line voltage should not exceed 457V because the
voltage is applied to the inputs of phase voltage.
PT[Potential Transformer]
PTs are required for all systems with voltage levels greater than these above. The meter inputs can
be used with PTs that have secondaries rated between AC 0V and 457V. PTs should comply with
IEC61010-1 2nd Edition, Pollution Degree 2, Overvoltage Category .
Warning
In case where PTs are required, the secondaries should be fused.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44