WURM RHS950 Product information

Type
Product information
RHS950
Product information
RHS950_Vx.x_PI_2017-05_EN Subject to technical changes Page 1 of 4
1 Front view
Humidity sensor for sales rooms and cold rooms
2 Features
Standard current signal 4...20mA = 0...100%Rh
RHS950
Product information
Page 2 of 4 Subject to technical changes RHS950_Vx.x_PI_2017-05_EN
Writing conventions
Symbol
Meaning
CAUTION! Avoid the described hazard: otherwise minor or medium physical injury or
damage to property will result.
WARNING!
Avoid the described hazard: otherwise there is danger from electric voltage
that could lead to death or serious physical injury.
For your safety
For safe operation and to avoid personal injury and equipment damage through operating error, always
read these instructions, become familiar with the device, and follow all safety instructions on the product
and in this document, as well as the safety guidelines of Wurm GmbH & Co. KG Elektronische
Systeme. Keep these instructions ready to hand for quick reference and pass them on with the device if
the product is sold.
Wurm GmbH & Co. KG Elektronische Systeme accepts no liability in case of improper use or use for
other than the intended purpose.
Target group
These instructions are intended for service technicians.
Intended use
The RHS950 is a moisture sensor for sales and cold rooms.
CAUTION!
Damage to the device if handled incorrectly!
Do not open the device!
Do not repair the device yourself! If required, send it in for repair with an exact
description of the fault!
Validity of documentation
Functional upgrade
2017-05
Basis of documentation
Any software versions not listed are special solutions for individual projects and are not described in detail in this document. This
document automatically ceases to be valid if a new technical description is issued.
Manufacturer: Wurm GmbH & Co. KG Elektronische Systeme, Morsbachtalstraße 30, D-42857 Remscheid
For further information, see our website at www.wurm.de
RHS950
Product information
RHS950_Vx.x_PI_2017-05_EN Subject to technical changes Page 3 of 4
3 Connection diagram
4 Connection to devices from Wurm
RHS950
FIO001B
FIO-PAT
FKD003
FKE003
FKL003
FKV003
FKP002B
FKV001B
AHC-XP
1 / -
12
CB-C/AI-2.0
(brown)
CB-C/AI-2.0
(brown)
46
46
34
34
16
2 / +UB
11
CB-C/AI-7.0
(white)
CB-C/AI-7.0
(white)
47
47
35
35
17
In general, the connection should be made using shielded cable.
Cable length
Cross section
up to 100m
0.75mm²
up to 400m
1.5 mm²
5 Installing
Holes in the housing floor for wall installation and housing dimensions
Notes!
Do not install the sensor above radiators, near windows or doors, on surfaces that are
exposed to strong vibrations or direct sunlight, on exterior walls, on chimneys, or in a
wall or alcove.
Protect the sensors from dripping water or spray.
No air currents must be allowed to reach the inside of the housing through the in-wall
cable feed.
Do not use any silicone sealing compound to seal the cable feed.
The sensors must be installed so that the ambient air can flow freely through the air
slots in the housing cover from the bottom towards the top.
RHS950
Product information
Page 4 of 4 Subject to technical changes RHS950_Vx.x_PI_2017-05_EN
Maintenance and ambient conditions
If the circulating air is clean, the measuring element is maintenance-free. However, aggressive or
solvent-containing media (depending on type and concentration) can cause measurement errors or
failure. Condensates that form a water-repellent film over the sensor are harmful; these could be
caused, for example, by resin aerosols, lacquer aerosols, fumigants, etc.
6 Characteristics curve
I / mA
4
5
6
7
8
9
10
11
12
%Rh
0
6.25
12.5
18.75
25.00
31.25
37.50
43.75
50.00
I / mA
13
14
15
16
17
18
19
20
%Rh
56.25
62.50
68.75
75.00
81.25
87.50
93.75
100
7 Technical data
Power supply
15...24V=
Output
4...20mA, two-wire with power supply
Max. load resistance
For current output 500Ω
Measurement range
0...100%Rh
Working range
10...95%Rh
Measuring precision
±
3.5%Rh
Temperature coefficient
0.05%/K at 20°C and 50%Rh
Measurement medium
Air, pressureless, not corrosive, not condensing
Ambient temperature
Operation: 0...+55°C, storage: -25…+70°C
Permitted air speed
15m/s
Adjustment
With average air pressure 430m NN, ex works
Half-life
At v=2m/s, approx. 10s
Housing
Plastic
Dimensions
(WxHxD) 115 x 70 x 43mm
Weight
About 200g
Fastening
Holes in the housing floor for wall installation
Installation position
Any, preferably with ventilation slots perpendicular to the direction of
air flow
Contacting
Terminals in the housing
Connection terminals
For cable cross section 1.5mm²
CE conformity
EU conformity as defined in
- 2014/30/EU (EMC directive)
Note!
Please observe the detailed descriptions in the chapters of the FRIGOLINK system
manual.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

WURM RHS950 Product information

Type
Product information

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI