Mitsubishi Electronics FX2N-8AD User manual

Category
Dishwashers
Type
User manual
USER’S MANUAL
FX
2N
-8AD Analog input block
FX2N-8AD Analog input block
Foreword
This manual contains text, diagrams and explanations which will guide the reader in the correct installation
and operation of the FX
2N
-8AD Analog input block. It should be read and understood before attempting to
install or use the unit.
Further information can be found in the FX
0N
/FX
1N
/FX
2N
/FX
2NC
Series Hardware Manual for connecting main
unit, and the FX Series Programming Manual(
ΙΙ
).
If in doubt at any stage of the installation of FX
2N
-8AD Analog input block always consult a professional
electrical engineer who is qualified and trained to the local and national standards that applies to the
installation site.
If in doubt about the operation or use of FX
2N
-8AD Analog input block please consult the nearest Mitsubishi
Electric distributor.
This manual is subject to change without notice.
FX
2N
-8AD Analog input block
USER’S MANUAL
FX2N-8AD Analog input block
Manual number : JY992D86001
Manual revision : C
Date : April 2003
FX2N-8AD Analog input block
ii
FX2N-8AD Analog input block
iii
Guidelines for the Safety of the User and Protection of the FX
2N
-8AD Analog
input block.
This manual provides information for the use of the FX
2N
-8AD Analog input block. The manual
has been written to be used by trained and competent personnel. The definition of such a
person or persons is as follows:
a) Any engineer who is responsible for the planning, design and construction of automatic
equipment using the product associated with this manual, should be of a competent
nature, trained and qualified to the local and national standards required to fulfill that
role. These engineers should be fully aware of all aspects of safety with regards to
automated equipment.
b) Any commissioning or service engineer must be of a competent nature, trained and
qualified to the local and national standards required to fulfill that job. These engineers
should also be trained in the use and maintenance of the completed product. This
includes being completely familiar with all associated documentation for said product. All
maintenance should be carried out in accordance with established safety practices.
c) All operators of the completed equipment (see Note) should be trained to use this
product in a safe manner in compliance to established safety practices. The operators
should also be familiar with documentation which is associated with the actual operation
of the completed equipment.
Note :
The term ‘completed equipment’ refers to a third party constructed device which
contains or uses the product associated with this manual.
FX2N-8AD Analog input block
iv
Notes on the Symbols Used in this Manual
At various times throughout this manual certain symbols will be used to highlight points which
are intended to ensure the users personal safety and protect the integrity of equipment.
Whenever any of the following symbols are encountered its associated note must be read and
understood. Each of the symbols used will now be listed with a brief description of its meaning.
Hardware Warnings
1) Indicates that the identified danger
WILL
cause physical and property damage.
2) Indicates that the identified danger could
POSSIBLY
cause physical and property
damage.
3) Indicates a point of further interest or further explanation.
Software Warnings
4) Indicates special care must be taken when using this element of software.
5) Indicates a special point which the user of the associate software element should
be aware.
6) Indicates a point of interest or further explanation.
FX2N-8AD Analog input block
v
Under no circumstances will Mitsubishi Electric be liable responsible for any consequential
damage that may arise as a result of the installation or use of this equipment.
All examples and diagrams shown in this manual are intended only as an aid to understanding
the text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual
use of the product based on these illustrative examples.
Please contact a Mitsubishi Electric distributor for more information concerning applications
in life critical situations or high reliability.
FX2N-8AD Analog input block
vi
FX2N-8AD Analog input block Contents.
vii
Guideline............................................................................................................................iii
1. Introduction .........................................................................................1-1
2. External Dimensions...........................................................................2-1
3. Part Name...........................................................................................3-1
4. Installation...........................................................................................4-1
5. Connection to PLC..............................................................................5-1
6. Wiring..................................................................................................6-1
6.1 Caution.............................................................................................................6-1
7. Specifications......................................................................................7-1
8. Buffer Memory (BFM).........................................................................8-1
8.1 Buffer Memories (BFM) lists ............................................................................8-3
8.2 Details of buffer memories.............................................................................8-13
8.2.1 BFM #0, #1: Specifies input mode. ...................................................................8-13
8.2.2 BFM #2 to BFM #9: Number of times of averaging...........................................8-15
8.2.3 BFM #10 to BFM #17: Channel data.................................................................8-17
8.2.4 BMF #19: Disables setting change....................................................................8-17
8.2.5 BFM #20: Initializes functions............................................................................8-17
8.2.6 BFM #21: Writes I/O characteristics..................................................................8-18
8.2.7 BFM #22: Sets convenient functions.................................................................8-19
8.2.8 BFM #24: Specifies high-speed conversion channel ........................................8-20
8.2.9 BFM #26: Upper/lower limit value error status..................................................8-21
8.2.10 BFM #27: A/D data sudden change detection status........................................8-22
8.2.11 BFM #28: Scale over status..............................................................................8-23
8.2.12 BFM #29: Error status.......................................................................................8-25
8.2.13 BFM #30: Model code.......................................................................................8-26
FX2N-8AD Analog input block Contents.
viii
8.2.14 BFM #32: Operating time..................................................................................8-26
8.2.15 BFM#33 disconnection detection (Only goods: since V1.10)............................8-27
8.2.16 BFM #41 to BFM #48: Offset data
BFM #51 to BFM #58: Gain data.......................................................................8-28
8.2.17 BFM #61 to BFM #68: Addition data.................................................................8-30
8.2.18 BFM #71 to BFM #78: Lower limit, error set value
BFM #81 to BFM #88: Upper limit, error set value............................................8-31
8.2.19 BFM #91 to BFM #98: Sudden change detection set value..............................8-33
8.2.20 BFM #99: Clears upper/lower limit value error and sudden change detection error
..........................................................................................................................8-35
8.2.21 BFM #101 to BFM #108: Peak value (minimum value)
BFM #111 to BFM #118: Peak value (maximum value)....................................8-36
8.2.22 BFM #109: Peak value reset flag (minimum value)
BFM #119: Peak value reset flag (maximum value)..........................................8-37
8.2.23 BFM #198: Data history sampling time .............................................................8-38
8.2.24 BFM #199: Resets or stops data history...........................................................8-40
8.2.25 BFM #200 to BFM #3399: Data history.............................................................8-41
9. Adjustment of I/O Characteristics........................................................9-1
9.1 Standard I/O characteristics.............................................................................9-2
9.2 Adjustment of I/O characteristics.....................................................................9-7
10. Example program..............................................................................10-1
Appendix A
Associated Manuals List...........................................................................A-1
Introduction 1
1-1
1. Introduction
The FX
2N
-8AD analog input block (hereafter referred to as "FX
2N
-8AD") converts 8 points of
analog input values (voltage input, current input and temperature input) into digital values, and
transfers them to the PLC main unit.
The FX
2N
-8AD can be connected to FX
0N
, FX
1N
, FX
2N
and FX
2NC
Series PLC.
1) Analog inputs can be selected from the voltage input, the current input and the thermocouple
input (temperature input) by the input mode setting by the TO instruction given by the PLC
main unit and the connection method.
At this time, a different analog input can be selected for each channel.
2) The voltage input can be selected within the range from -10 to +10 V. The current input can
be selected within the range from -20 to +20 mA and from +4 to +20 mA. The input
characteristics can be adjusted for each channel (except while the analog value direct
display is used).
The thermocouple input can be selected among the K type, J type and T type. (The input
characteristics cannot be adjusted when the thermocouple input is used.)
3) The resolution is 0.63 mV (20 V
×
1/32,000) or 2.50 mV (20 V
×
1/8,000) when the voltage
input is used, 2.50
µ
A (40 mA
×
1/16,000) or 5.00
µ
A (40 mA
×
1/8,000) when the current
input is used, and 0.1
°
C when the thermocouple input is used.
FX2N-8AD Analog input block
FX2N-8AD Analog input block Introduction 1
1-2
4) Up to two FX
2N
-8AD units can be connected to FX
0N
main unit, FX
0N
extension unit, FX
1N
main unit.
Up to eight FX
2N
-8AD units can be connected to one FX
2N
Series PLC. Up to four FX
2N
-
8AD units can be connected to one FX
2NC
Series PLC.
(For connection to the FX
2NC
Series PLC, an FX
2NC
-CNV-IF is required.)
Data transfer with the PLC is performed to buffer memories of the FX
2N
-8AD by FROM/TO
instructions.
External Dimensions 2
2-1
2. External Dimensions
Figure 2.1: External Dimensions
COM2
I8+
I4+
V3+
I3+
COM3COM1
COM5
COM8
I5+
24+ 24-
POWER
24V
V2+
I2+
V4+
V7+
V1+
I1+
COM4
V5+
V6+
I7+
I6+
COM6
COM7
V8+
7.5(0.30)
7.5(0.30)
105(4.13)
8(0.31)
75(2.95)
90(3.54)
67(2.64)
(installation dimension)
75(2.95)
8(0.31)
FX
2N
-8AD
98(3.86)
(installation dimension)
Dimensions: mm(inch)
Mass(Weight): 0.3 kg(0.66 lbs)
FX2N-8AD Analog input block
FX2N-8AD Analog input block External Dimensions 2
2-2
MEMO
Part Name 3
3-1
3. Part Name
For wiring, refer to Section 6.
Never perform wiring to terminals.
Table 3.1: Status indicator LED
Indication Description
POWER
Lit while 5 V power is normally
supplied from PLC.
24 V
Lit while 24 V power is normally
supplied to “24+” and “24-”
terminals of FX
2N
-8AD.V
V1+ I1+
COM1
V3+ I3+
24+ 24- V2+ I2+ V4+ I4+
COM4
COM3
COM2
I6+
COM5
V7+ I7+
V6+
V5+ I5+
V8+ I8+
COM8
COM7
COM6
V8+
COM7
COM6
I6+
I7+
V6+
V5+
COM4
I1+V1+
V7+
V4+I2+V2+
24V
POWER
24-24+
I5+
COM8
COM5
COM1 COM3
I3+V3+
I4+
I8+
COM2
FX
2N
-8AD
Installation hole (screw M4)
Status indicator LED
M3
(terminal screw)
Hook for DIN rail
Extension
cable
Extension
connector
Terminal arrangement
Figure 3.1: Part name
FX2N-8AD Analog input block
FX2N-8AD Analog input block Part Name 3
3-2
MEMO
Installation 4
4-1
4. Installation
Install the FX
2N
-8AD to the right side of a main unit, extension unit, extension block or special
block of the FX
0N
/FX
1N
/FX
2N
/FX
2NC
Series PLC.
The FX
2N
-8AD can be installed with a DIN rail (DIN46277 of 35 mm in width) or directly
installed with screws M4. For the details, refer to the handy manual supplied together with the
PLC main unit.)
FX2N-8AD Analog input block
FX2N-8AD Analog input block Installation 4
4-2
Figure 4.1: Installation with DIN rail
The FX
2N
-8AD can be installed on a DIN rail
(DIN46277) of 35 mm in width as it is. For
removal, pull down on the DIN rail mounting
hook, then remove the FX
2N
-8AD.
Figure 4.2: Direct installation
•The FX
2N
-8AD can be installed directly by
inserting screws (M4) into installation holes.
For the pitch and the position of installation
holes, refer to the figure on the left.
V8+
COM7
COM6
I6+
I7+
V6+
V5+
COM4
I1+V1+
V7+
V4+
I2+
V2+
24V
POWER
24-
24+
I5+
COM8
COM5
COM1 COM3
I3+
V3+
I4+
I8+
COM2
FX
2N
-8AD
Hook for DIN rail
Installation
screw M4
67(2.64)
98(3.86)
Dimensions: mm(inch)
Connection to PLC 5
5-1
5. Connection to PLC
Connect the FX
2N
-8AD to the right side of a main unit, extension unit or extension block of
FX
0N
, FX
1N
, FX
2N
, FX
2NC
Series PLC with an extension cable.
For connection to a basic unit or extension block of the FX
2NC
Series PLC, use an FX
2NC
-CNV-
IF.
Please check power supply availability to determine the number of FX
2N
-8AD blocks that can
be connected to the FX
0N
, FX
1N
, FX
2N
or FX
2NC
PLCs.
A unit No. 0 to 7 is automatically assigned to each special unit or special block connected to a
PLC basic unit from the one nearest to the basic unit.
The data is read from and written to the FX
2N
-8AD by FROM/TO instructions given by the
basic unit.
FX2N-8AD Analog input block
FX2N-8AD Analog input block Connection to PLC 5
5-2
MEMO
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88

Mitsubishi Electronics FX2N-8AD User manual

Category
Dishwashers
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI