Quick-Start Guide
MPH2
Rack-Mount PDU
Quick-Start Guide
In-Line
Bracket
... insert the
fasteners.
Position the MPH2
assembly and ...
Springnuts in
Rack Frame
Mount the MPH2
Using Button Mounts
1. Attach the factory-supplied button mounts to the
rear of the rack PDU.
Use only the mounting button provided with
the rack PDU. Using other mounting buttons
may damage the MPH2.
2. Find the keyhole slots in the rack frame or install
the rack manufacturer’s keyhole slot brackets in
the desired location in the rack.
3. Insert each of the attached mounting buttons into
the large opening of a keyhole slot.
4. Slide the assembly down into the narrow portion
of the keyhole slot to lock in place.
Insert the Button
Mount into the
Keyhole Slot
Back of MPH2
Button
Mount
Weight of MPH2 Seats
the Rack PDU in the Slot
The MPH2 rack PDU may be mounted in a rack by:
Attaching two in-line brackets to the ends of the rack PDU
Attaching two mounting buttons to the back of the MPH2
Determine which mounting method best suits your rack and install the necessary hardware in the rack. The hardware may
include spring nuts, cage nuts and the rack manufacturer’s mounting bracket.
The MPH2 rack PDU may be mounted so that its input power cord exits at the top or bottom.
Mount the MPH2 Using In-Line Brackets
1. Install the brackets by inserting the legs of the in-line brackets into the slots on each end of the MPH2 rack PDU. The
brackets will lock in place when upright and square with the rack PDU (see below, left).
2. Hold the top of the MPH2 assembly over the desired mounting holes in the rack frame or rack manufacturer’s bracket and
insert the fasteners into the top rack PDU bracket.
3. Use a Phillips head screwdriver to turn the screws. Leave the screws slightly loose.
4. Position the rack PDU bracket on the lower end of the MPH2 over the desired mounting holes and insert the screws.
5. Tighten all screws.
Rack PDU Setup
1. Connect to a Network
Connect an Ethernet cable from your
network to the RPC2 Communications
Module’s Network port.
Ensure that all devices to be powered
through the MPH2 are shut down and
unplugged from input power sources.
Connect the devices’ input power cables to
the rack PDU’s outlets.
Record where each piece of rack
equipment is connected using the branch
and receptacle numbers on the rack PDU
for reference.
2. Connect Devices’ Power Cords
Connect the link port of the first rack
PDU to the Network In port of the second
rack PDU with an Ethernet cable.
3. Create a Rack PDU Array
Use an RJ45 cable to connect the link
port of the first rack PDU to the Network
In port of the second rack PDU; repeat for
up to two more rack PDUs (total of four).
4. Connect a Liebert SN Sensor
Use an RJ45 cable to connect an approved
SN sensor to the sensor port of the RPC2.
5. Connect a Console Server or Switch
Connect a console server or switch to the
serial port of the RPC2 communications
module with an Ethernet cable.
6. Connnect a Basic Display Module
Use an RJ45 cable to connect a Basic
Display Module (BDM) to the display port
of the RPC2.
RPC2 Front
Serial Port Sensor Port Display Port Link Port Network Port
Turn on the MPH2 Rack PDU
1. Ensure that all circuit breakers on the unit are in the Off position.
2. Connect input power to the MPH2 rack PDU.
3. Press the circuit breaker down into the On position.
4. Verify that input power is present, that the LED’s are illuminated and
that the onboard display is powered up.
5. Turn on the connnected devices one at a time.
6. Verify that each is operating properly.
1
6
2
3
4
5
MPH2
RPC2 in MPH2
www.EmersonNetworkPower.Asia
While every precaution has been taken to ensure
accuracy and completeness herein, Emerson
Network Power assumes no responsibility, and
disclaims all liability, for damages resulting
from use of this information or for any errors or
omissions. Specications are subject to change
without notice.
Emerson Network Power and Liebert
®
are
trademarks of Emerson Electric Co. or one of its
afliated companies. All other names and logos
referred to are trade names, trademarks, or
registered trademarks of their respective owners.
©2015 Emerson Electric Co.
AU15ENT-MPH2V1-QG
Emerson Network Power Australia and New Zealand
Emerson Network Power Asia Pacific HQ
29/F Orient Square Bldg
F. Ortigas Jr. Road
Pasig City 1600, Philippines
Tel. No.: +63 2 620 3600
Australia
Head Office
Block P, Regents Park Estate, 391 Park Road
Regents Park, NSW 2143, Australia
Tel No.: +61 2 9743 8737
New South Wales – North Ryde
Suite A, Level 6, 15 Talavera Rd, North Ryde, NSW 2113
Queensland
Unit 3, 50 Borthwick Ave, Murarrie, QLD 4172
Australian Capital Territory
Unit 5, 164 Gladstone St, Fyshwick, ACT 2609
Victoria
Unit 11, 350 Bridge St, Port Melbourne, VIC 3207
Western Australia
Unit 4, 3 Abrams St, Balcatta, WA 6021
Toll-Free No.: 1 800 065 345
New Zealand
Auckland
2/14 Burleigh St, Grafton, Auckland 1023
Tel. No.: +64 9 443 5495
Christchurch
Unit 10/9 Print Place, Middleton,
Christchurch 8024
Tel. No.: +64 3 339 2060
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Liebert MPH2 Quick start guide

Category
Racks
Type
Quick start guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI