4
5 6
7
8
9 10
11
12
2(N)
1(L)
3
N
L
2
(N)
3
1
(L)
Connection cable
Indoor unit side
terminal block
To power supply
and ground
Outdoor unit side
terminal block
Power supply cable
CN10
Connecting pipe
Blank cap
3-way valve
Hexagon wrench
Charging port
Outdoor unit
Service hose
with valve core
Cap
Use a 4 mm
hexagon wrench.
Loop
Insulation
Strip 25 mm (15/16")
Ring terminal
Insulation
Strip 10 mm (3/8")
Screw with
special washer
Cable
Loop or
ring terminal
Terminal blocks
Cable
Screw with
special
washer
Loop or
ring terminal
Screw
Wire cover
Screw
Cable clamp
Cable clamp
Hook
(Rear)
(E)Left
outlet
(G)Left rear
outlet
(D)Left bottom
outlet
(F)Center
outlet
(A)Rear
outlet
(C)Bottom
outlet
(B)Right
outlet
Connection pipe
heat insulation
Indoor unit pipe
heat insulation
Bind the pipes together
so that there is no gap.
[Example of the right piping]
Indoor unit (Rear)
Vinyl tape
Overlap
Connection pipe
heat insulation
Indoor unit pipe
heat insulation
Bind the pipes together
so that there is no gap.
[Example of the left piping]
Indoor unit (Rear)
Vinyl tape
Butting
connection
[Example of the left piping]
Indoor unit (Rear)
Cloth tape
Accommodates the rear
piping housing section
Indoor unit (Rear)
[Example of the left piping]
Vinyl tape
Connection cable
(Top of the pipe)
Small pipe
Large pipe
Drain hose
(Side)
Drain hose
Connection cable
Connection pipe
Wall pipe
(View from indoors)
(Saddle)
(Outside wall cap)
(Sealer putty)
Wall
(Outdoors)
Pipe
GOOD
PROHIBITED
Drain
hose
Saddle
Lifted up
Wave
End in water
Cable clamp
Screw
Screw
Wire cover
Intake grille
Front panel
Check the following:
CN9
Remote controller holder fi xing Remote controller mounting
Remote controller
holder
Tapping
screws
(small,
accessories)
Remote
controller
(1) Set
(2) Push
Transmitter section
TEST RUN button
Control cover
Screw
Connector
Screw
Display case
DISPLAY
Screw
Cable clamper
Conduit
holder
Screw
Cable clamper
Wire of
wired
remote
controller
Original cable
of control unit
Rib
Connect the cable
REMOCON
Hole
CAUTION
Use a clean gauge manifold
and charging hose for
R410A exclusively.
Lo
Hi
Gauge manifold
Vacuum pump
Service hose
2(N)
1(L)
3
4
2
(N)
1(L)
N
L
3
4
55
Connection cable
Indoor unit side
terminal block
To power supply
and ground
Outdoor unit side
terminal block
Power supply cable
12 3 4 5 6
Terminal block
Earth screw
Cable
clamp
Connection cable
25 mm
25 mm
35 mm
12 3 4 5 6
Terminal block
Earth screw
Cable
clamp
Connection cable
25 mm
35 mm
[Cooling model]
VACUUM PROCESS
CAUTION
(1) Do not purge the air with refrigerants but use a
vacuum pump to vacuum the installation! There is no
extra refrigerant in the outdoor unit for air purging!
(2) Use a vacuum pump for R410A exclusively. Using the
same vacuum pump for different refrigerants may
damage the vacuum pump or the unit.
1. VACUUM
(1) Remove the cap, and connect the gauge manifold and the vacuum
pump to the charging valve by the service hoses.
(2) Vacuum the indoor unit and the connecting pipes until the pressure
gauge indicates –0.1 MPa (–76 cmHg).
(3) When –0.1 MPa (–76 cmHg) is reached, operate the vacuum pump
for at least 15 minutes.
(4) Disconnect the service hoses and fi t the cap to the charging valve to
the specifi ed torque.
(5) Remove the blank caps, and fully open the spindles of the 2-way and
3-way valves with a hexagon wrench (Torque : 6 to 7 N · m (60 to 70
kgf · cm).
(6) Tighten the blank caps of the 2-way valve and 3-way valve to the
specifi ed torque.
2. ADDITIONAL CHARGE
Refrigerant suitable for a piping length of 7.5 m is charged in the outdoor
unit at the factory.
When the piping is longer than 7.5 m, additional charging is necessary.
For the additional amount, refer to the following table.
3. GAS LEAKAGE INSPECTION
WARNING
(1) During installation, make sure that the refrigerant pipe
is attached fi rmly before you run the compressor.
Do not operate the compressor under the condition of
refrigerant piping not attached properly with 2-way or
3-way valve open. This may cause abnormal pressure in
the refrigeration cycle that leads to breakage and even
injury.
(2) During the pump-down operation, make sure that
the compressor is turned off before you remove the
refrigerant piping.
Do not remove the connection pipe while the compressor
is in operation with 2-way or 3-way valve open.
This may cause abnormal pressure in the refrigeration
cycle that leads to breakage and even injury.
(3) When installing and relocating the air conditioner,
do not mix gases other than the specifi ed refrigerant
(R410A) to enter the refrigerant cycle.
If air or other gas enters the refrigerant cycle, the pressure
inside the cycle will rise to an abnormally high value and
cause breakage, injury, etc.
CAUTION
After connecting the piping, check the joints for gas
leakage with gas leak detector.
ELECTRICAL WIRING
WARNING
(1) Before starting work, check that power is not being
supplied to indoor unit and the outdoor unit.
(2) Match the terminal numbers and connection cable
colours of the indoor unit and the outdoor unit or
branch box. Erroneous wiring may cause burning of
the electric parts.
(3) Connect the connection cables fi rmly to the terminal
block. Imperfect installation may cause a fi re.
(4) Always fasten the outside covering of the connection
cable with the cable clamp. (If the insulator is chafed,
electric leakage may occur.)
(5) Always connect the ground wire.
HOW TO CONNECT WIRING TO TERMINALS
(1) Cut the cable end with a wire cutter or
wire-cutting pliers, then strip the insulation
to about 25 mm (15/16") to expose the
solid cable.
(2) Using a screwdriver, remove the terminal
screw(s) on the terminal board.
(3) Using pliers, bend the solid cable to form
a loop suitable for the terminal screw.
(4) Shape the loop cable properly, place it on the terminal board and
tighten securely with the terminal screw using a screwdriver.
A. For solid core wiring (or F-cable)
(1) Cut the cable end with a wire cutter or
wire-cutting pliers, then strip the insulation
to about 10 mm (3/8") to expose the
strand wiring.
(2) Using a screwdriver, remove the terminal
screw(s) on the terminal board.
(3) Using a ring terminal fastener or pliers,
securely clamp a ring terminal to each
stripped cable end.
(4) Position the ring terminal cable, and replace and tighten the terminal
screw using a screwdriver.
B. For strand wiring
Tightening torque [N·m (kgf·cm)]
M4 screw 1.2 to 1.8 (12 to 18)
M5 screw 2.0 to 3.0 (20 to 30)
1. CONNECTION DIAGRAM
2. INDOOR UNIT SIDE
(1) Open the intake grille. Remove the tapping screw for the wire cover
and remove the wire cover.
(2) Remove the tapping screw and while minding the cable clamp hook,
remove the cable clamp.
(3) Connect the end of the connection cable fully into the terminal block.
3. OUTDOOR UNIT SIDE
CAUTION
Use VW-1, 12 mm diameter, 0.5 to 1.0 mm thick,
connection PVC tube as the insulation tube.
Check that:
• When connected from the left rear, the drain hose is at the bottom
left of the wall pipe.
(For connection from the left rear)
FINISHING
1. CONNECTION PIPE, CABLE AND DRAIN HOSE
(1) Insulate between pipes.
(2) Temporarily fasten the connection cable along the connection pipe
with vinyl tape. (Wrap to about 1/3 the width of the tape from the
bottom of the pipe so that water does not enter.)
(3) Fasten the connection pipe to the outside wall with a saddle, etc.
(4) Fill the gap between the outside wall pipe hole and the pipe with
sealer so that rain water and wind cannot blow in.
[(A)Rear, (B)Right, and (C)Bottom piping]
• Overlap the connection pipe heat insulation and indoor unit pipe
heat insulation and bind them with vinyl tape so that there is no
gap.
[(D)Left bottom piping, (E)Left piping, (F)Center piping,
and (G)Left rear piping]
• Butt the connection pipe heat insulation and indoor unit pipe heat
insulation together and bind them with vinyl tape so that there is
no gap.
• Wrap the area which accommodates the rear piping housing
section with cloth tape.
• Bind the connection cable to the top of the pipe with vinyl tape.
Check that:
• The top and bottom hooks are hooked fi rmly and the indoor unit
does not move to the front and rear or left and right.
• The indoor unit is accurately positioned horizontally and vertically.
2. INSTALLING FINAL PARTS
(1) Secure the cable clamp with tapping screw.
(2) Secure the wire cover and tapping screw.
(3) Close the intake grille.
(5) Fasten the drain hose to the outside wall, etc.
REMOTE CONTROLLER
INSTALLATION
WIRED REMOTE CONTROLLER
INSTALLATION (Optional)
PUMP DOWN OPERATION
(FORCED COOLING OPERATION)
CAUTION
(1) Check that the indoor unit correctly receives the
signal from the remote controller, then install the
remote controller holder.
(2) Select the remote controller holder mounting location
by paying careful attention to the following:
• Avoid places in direct sunlight.
• Select a place that will not be affected by the heat
from a stove, etc.
REMOTE CONTROLLER HOLDER INSTALLATION
• Install the remote controller with in a distance of 7 m between the
remote controller and the signal receiver as the criteria. However, when
installing the remote controller holder, check that it operates correctly.
• Install the remote controller holder to a wall, pillar, etc. with the tapping
screw.
TEST RUN
CUSTOMER GUIDANCE
• Perform test operation and check items 1 and 2 below.
• For the test operation method, refer to the operating manual.
• The outdoor unit, may not operate, depending on the room
temperature. In this case, press the TEST RUN button on the remote
controller while the air conditioner is running, (Point the transmitter
section of the remote controller toward the air conditioner and press
the TEST RUN button with the tip of a ball-point pen, etc.)
• To end test operation, press the remote controller START/STOP
button. (When the air conditioner is run by pressing the TEST RUN
button, the OPERATION indicator lamp and TIMER indicator lamp will
simultaneously fl ash slowly.)
Before install wired remote controller
• The wired remote controller is an option.
It isn’t included in main body of air conditioner.
• When you use wired remote controller, some functions may not be
used.
• Please use the recommended wired remote controller.
CHECK ITEMS
1. INDOOR UNIT
(1) Is operation of each button on the remote controller normal?
(2) Does each lamp light normally?
(3) Do the airfl ow direction louvers operate normally?
(4) Is the drain normal?
(5) Is there any abnormal noise and vibration during operation?
2. OUTDOOR UNIT
(1) Is there any abnormal noise and vibration during operation?
(2) Will noise, wind, or drain water from the unit disturb the neighbours?
(3) Is there any gas leakage?
CAUTION
(1) Before installing, be sure to disconnect all power
supply.
(2) Don’t touch the heat exchanger.
(3) During installing or removing operation, be sure not
to have wire caught by parts or draw it hard.
Or it may result troubles to the air conditioner.
(4) Avoid place in direct sunlight.
(5) Select place that will not be affected by the heat from
a stove, etc.
(6) Insure the length of cable is not over the
recommended maximum length.
(7) Before setting up the wired remote controller, please
confi rm whether air conditioner can receive the
signal.
1. Front panel, control cover and display case
removal
(1) Refer to “1.4. FRONT PANEL REMOVAL AND INSTALLATION”
to remove the front panel.
(2) Remove the screw then remove the control cover.
(3) Remove the display case and connector.
2. Connecting to control unit of cable
(1) Pass the connector from the hole in the back.
(2) Connect the cable of wired remote controller to the board of Control
unit.
(3) Hook the cable to the rib.
(4) Use cable clamper and screw to fasten the cable.
3. Front panel, control cover and display case
installation
• Install front panel, control cover and display case by the reverse
procedures as stated in the step “1. Front panel, control cover and
display case removal”.
WARNING
During the pump-down operation, make sure that the
compressor is turned off before you remove the
refrigerant piping. Do not remove the connection pipe
while the compressor is in operation with opened 3-way
valve. This may cause abnormal pressure in the
refrigeration cycle that leads to breakage and even injury.
To avoid discharging refrigerant into the atmosphere at the time of
relocation or disposal, recover refrigerant by doing the cooling operation
or forced cooling operation according to the following procedure.
(When the cooling operation cannot start in winter, and so on, start the
forced cooling operation.)
(1) Do the air purging of the charge hose by connecting the charging
hose of gauge manifold to the charging port of 3 way valve (large)
and opening the low-pressure valve slightly.
(2) Close the valve stem of 2-way valve (small) completely.
(3) Start the cooling operation or following forced cooling operation.
When using the remote controller;
• Press the TEST RUN button after starting the cooling operation by
the remote controller.
• The operation indicator lamp and timer indicator lamp will fl ash
simultaneously during test run.
When using the MANUAL AUTO button of the indoor unit;
(The remote controller is lost, and so on.)
• Keep on pressing the MANUAL AUTO button of the indoor unit for
more than 10 seconds.
(The forced cooling operation cannot start if the MANUAL AUTO
button is not kept on pressing for more than 10 seconds.)
(4) Close the valve stem of 3-way valve (large) when the reading on the
compound pressure gauge becomes 0.05~0 MPa (0.5 ~ 0 kg/cm²).
(5) Stop the operation.
When using the remote controller;
• Press the START/STOP button of the remote controller to stop the
operation.
When using the MANUAL AUTO button of the indoor unit;
• Press the MANUAL AUTO button when stopping the operation
from indoor unit side.
(It is not necessary to press on keeping for more than 10 seconds.)
Explain the followings to the customer in accordance with the operating
manual:
(1) Starting and stopping method, operation switching, temperature
adjustment, timer, airfl ow switching, and other remote controller
operations.
(2) Air fi lter removal and cleaning, and how to use the airfl ow direction
louvers.
(3) Give the operating manual and installation manual to the customer.
(4) If the custom code is changed, explain to the customer how it
changed (the system returns to custom code A when the batteries in
the remote controller are replaced).
*(4) is applicable to using wireless remote controller.
FUNCTION SETTING
CAUTION
(1) When moving and installing the air conditioner, do not
mix gas other than the specifi ed refrigerant (R410A)
inside the refrigerant cycle.
(2) When charging the refrigerant R410A, always use an
electronic balance for refrigerant charging (to measure
the refrigerant by weight).
(3) When charging the refrigerant, take
into account the slight change in the
composition of the gas and liquid
phases, and always charge from the
liquid phase side whose composition
is stable.
Gas
Liquid
R410A
(4) Add refrigerant from the charging valve after the
completion of the work.
(5) If the units are further apart than the maximum pipe
length, correct operation cannot be guaranteed.
Pipe length
Less than
7.5 m
10 m 15 m 20 m g/m
Additional charge
amount
None 50 g 150 g 250 g 20 g/m
[Heating and Cooling model (Reverse cycle)]
[Heating and Cooling model (Reverse cycle)]
[Cooling model]
Insulation tube
Connection cable
Cable clamp
Insulation tube
Connection cable or
power supply cable
(1) Remove the outdoor unit service cover and valve cover.
(2) Put the connection cable through the insulation tube.
25 mm or less
25 mm or less
45 mm
45 mm
Terminal block
Control box
Cable clamp
Insulation tube
Connection cable
Power supply cable
[Cooling model]
25 mm or less
25 mm or less
25 mm or less
45 mm
45 mm
Terminal block
Control
box
Cable clamp
Insulation tube
Connection cable
Power supply cable
[Heating and Cooling model (Reverse cycle)]
(3) Process the end of the connection cables to the dimensions shown in
the following fi gure.
(4) Connect the end of the connection cable fully into the terminal block
and fasten with the screws.
(5) Secure the connection cables with the cable clamps to be mounted
on the insulation tubes.
(6) Remove the cover plate.
Cover plate
Insulation
(seal)
(7) Fix the power supply cable and connection cable with the cable clip
of the base of the valves.
Cable clip
Power supply cable
and Connection
cable
(8) Attach the cover plate.
Cover plate
CAUTION
Fix cables so that cables do not make contact with the
pipes (especially on high pressure side).
Do not make power supply cable and connection cable
come in contact with valve (Gas).
Gap
Valve
(Gas)
Power supply cable
and connection cable
(9) Put the service cover and valve cover back after completion of the
work.
Perform the “FUNCTION SETTING” according to the installation
conditions using the remote controller.
CAUTION
Confi rm whether the wiring work for Outdoor unit or
Branch box has been fi nished.
Confi rm that the cover for the electrical enclosure on the
outdoor unit is in place.
• This procedure changes to the function settings used to control the indoor
unit according to the installation conditions. Incorrect settings can cause
the indoor unit to malfunction.
• After the power is turned on, perform the “FUNCTION SETTING”
according to the installation conditions using the remote controller.
• The settings may be selected between the following two: Function
Number or Setting Value.
• Settings will not be changed if invalid numbers or setting values are
selected.
• Refer to the installation manual enclosed with the remote controller
when the wired remote controller (option) is used.
Entering the Function Setting Mode
While pressing the FAN button and SET TEMP. ( ) simultaneously,
press the RESET button to enter the function setting mode.
STEP 1
Selecting the remote controller custom code
Use the following steps to select the custom
code of the remote controller. (Note that the
air conditioner cannot receive a signal if the air
conditioner has not been set for the custom code.)
The custom codes that are set through this
process are applicable only during the FUNCTION
SETTING process. For details on how to set the
custom codes through the normal process, refer to
“Remote controller custom code setting”.
(1) Press SET TEMP. (
) ( ) button to change the custom code
between
A
B C D
. Match the code on the display to the air
conditioner custom code (initially set to A). (If the custom code does
not need to be selected, press the MODE button and proceed to
STEP 2.)
(2) Press the TIMER MODE button and check that the indoor unit can
receive signals at the displayed custom code.
(3) Press the MODE button to accept the custom code, and proceed to
STEP 2.
Remote controller custom code setting
When 2 or more air conditioners are installed in a room and the remote
controller is operating an air conditioner other than the one you wish to
set, change the custom code of the remote controller to operate only the
air conditioner you wish to set (4 selections possible).
• Confi rm the setting of the remote controller custom code and the
function setting. If these do not match, the remote controller cannot be
used to operate for the air conditioner.
Selecting the remote controller custom code
Use the following steps to select the custom code
of the remote controller.
(Note that the air conditioner cannot receive a
signal if the air conditioner has not been set for the
matching custom code.)
(1) Press the “START/STOP” button until only the
clock is displayed on the remote controller
display.
(2) Press the MODE button for at least fi ve seconds to display the
current custom code (initially set to A).
(3) Press SET TEMP. (
) ( ) button to change the custom code
between
A B C D
.
Match the code on the display to the air conditioner custom code.
(4) Press the MODE button again to return to the clock display. The
custom code will be changed.
NOTES:
• If no butto
ns are pressed within 30 seconds after the custom code is
displayed, the system returns to the original display. In this case, start
again from step 1.
• The air conditioner custom code is set to A prior to shipment.
• Depending on the remote controller, the custom code may return to
custom code A when the batteries are replaced. In this case, if you use
a code other than A, reset the code after replacing the batteries. If you
do not know the air conditioner custom code setting, try each code
(
A B C D
) until you fi nd the code which operates the air conditioner.
STEP 2
Selecting the Function Number and Setting Value
(1) Press the SET TEMP. (
) ( ) buttons
to select the function number. (Press
the MODE button to switch between the
left and right digits.)
(2) Press the FAN button to proceed to
setting the value. (Press the FAN button
again to return to the function number
selection.)
(3) Press the SET TEMP. (
) ( ) buttons to select the setting value.
(Press the MODE button to switch between the left and right digits.)
(4) Press the TIMER MODE button, then the START/STOP button in
order to fi x the settings.
(5) Press the RESET button to end the function setting mode.
(6) After completing the FUNCTION SETTING, be sure to disconnect
the power and reconnect it again.
Function number
Setting
value
CAUTION
After disconnecting the power, wait 30 seconds or more
before reconnecting it again.
The Function Setting does not become active unless the
power is disconnected then reconnected again.
Room temperature control for cooling
Depending on the installed environment, correction of the room
temperature sensor may be required. Select the appropriate control
setting according to the installed environment.
(♦... Factory setting)
Function Number Setting Value Setting Description
30
00 Standard
♦
01 Lower control
Auto Restart
Enable or disable automatic restart after a power interruption.
(♦... Factory setting)
Function Number Setting Value Setting Description
40
00 Enable
♦
01 Disable
* Auto restart is an emergency function such as for power outage etc.
Do not attempt to use this function in normal operation. Be sure to
operate the unit by remote controller or other external input device.
Room temperature sensor switching
(Only for wired remote controller)
When using the Wired remote controller temperature sensor, change the
setting to “Both” (01).
(♦... Factory setting)
Function Number Setting Value Setting Description
42
00 Indoor unit
♦
01 Both
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
* Remote controller sensor must be turned on by using the remote
controller
Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed.
Select the appropriate custom code.
(♦... Factory setting)
Function Number Setting Value Setting Description
44
00 A
♦
01 B
02 C
03 D
Setting record
Record any changes to the settings in the following table.
Function Setting Setting Value
Room temperature control for cooling
Auto restart
Room temperature sensor switching
Remote controller custom code
After completing the FUNCTION SETTING, be sure to disconnect the
power and reconnect it again.
9385991286-03_EN.indd 29385991286-03_EN.indd 2 10/18/2562 BE 5:07 PM10/18/2562 BE 5:07 PM