Hoshizaki SRC-10H User manual

Category
Ice cube makers
Type
User manual

This manual is also suitable for

Hoshizaki
“A Superior Degree
of Reliability”
www.hoshizaki.com
Model
FS-1022MLH-C
Including
Condensing Unit Model
SRC-10H
Modular Cubelet
Serenity Series
Hoshizaki America, Inc.
Number: 73186
Issued: 6-9-2011
SERVICE MANUAL
2
IMPORTANT
Only qualied service technicians should install, service, and maintain the
icemaker. No service or maintenance should be undertaken until the technician
has thoroughly read this Service Manual. Failure to service and maintain
the equipment in accordance with this manual may adversely affect safety,
performance, component life, and warranty coverage.
Hoshizaki provides this manual primarily to assist qualied service technicians in the
service and maintenance of the icemaker.
Should the reader have any questions or concerns which have not been satisfactorily
addressed, please call, write, or send an e-mail message to the Hoshizaki Technical
Support Department for assistance.
HOSHIZAKI AMERICA, INC.
618 Highway 74 South
Peachtree City, GA 30269
Attn: Hoshizaki Technical Support Department
Phone: 1-800-233-1940 Technical Support
(770) 487-2331
Fax: 1-800-843-1056
(770) 487-3360
E-mail: techsuppor[email protected]
Web Site: www.hoshizaki.com
NOTE: To expedite assistance, all correspondence/communication MUST include the
following information:
•ModelNumber________________________
•SerialNumber________________________
•Completeanddetailedexplanationoftheproblem.
3
IMPORTANT
This manual should be read carefully before the icemaker is serviced or
maintenance operations are performed. Only qualied service technicians
should install, service, and maintain the icemaker. Read the warnings contained
in this booklet carefully as they give important information regarding safety.
Please retain this booklet for any further reference that may be necessary.
CONTENTS
Important Safety Information ................................................................................................. 5
I. Specications ...................................................................................................................... 7
A. Icemaker ....................................................................................................................... 7
B. Condensing Unit ............................................................................................................ 8
II. General Information ........................................................................................................... 9
A. Construction .................................................................................................................. 9
1. Icemaker .................................................................................................................. 9
2. Condensing Unit .................................................................................................... 10
3. Icemaking Unit ........................................................................................................11
B. Sequence of Operation ............................................................................................... 12
1. Sequence Cycles and Shutdown ........................................................................... 12
a) Fill Cycle .......................................................................................................... 12
b) Ice Purge Cycle ................................................................................................ 12
c) Freeze Cycle .................................................................................................... 12
d) Drain Cycle ..................................................................................................... 13
e) Shutdown Cycle ............................................................................................... 14
2. Sequence Flow Chart ............................................................................................ 15
C. Control Board .............................................................................................................. 16
1. Control Board Layout ............................................................................................. 17
2. LED Lights and Audible Alarm Safeties ................................................................. 18
3. Controls and Adjustments ...................................................................................... 19
a) Default Dip Switch Settings .............................................................................. 19
b) Infrared Sensor Shutdown Delay (S1 dip switch 1, 2, 3) .................................. 19
c) Drain Frequency Control (S1 dip switch 4) ....................................................... 20
d) Continuous Dispensing Timer (S1 dip switch 5 & 6) ........................................ 20
e) Bin Control Selector (S1 dip switch 7) .............................................................. 20
f) Mechanical Bin Control Shutdown Delay (S1 dip switch 8) .............................. 21
g) Factory Use (S1 Dip Switch 9 & 10) ................................................................. 21
III. Technical Information ...................................................................................................... 22
A. Water Circuit and Refrigeration Circuit ........................................................................ 22
B. Wiring Diagrams .......................................................................................................... 23
1. FS-1022MLH-C ...................................................................................................... 23
2. SRC-10H ............................................................................................................... 24
C. Performance Data ....................................................................................................... 25
4
IV. Service Diagnosis ........................................................................................................... 26
A. Ice Production Check .................................................................................................. 26
B. Diagnostic Procedure .................................................................................................. 26
C. Control Board Check ................................................................................................... 30
D. Bin Control Check ....................................................................................................... 33
1. Infrared Sensor Check ........................................................................................... 33
2. Mechanical Backup Bin Control Check .................................................................. 34
E. Float Switch Check and Cleaning ............................................................................... 36
1. Float Switch Check ................................................................................................ 36
2. Float Switch Cleaning ............................................................................................ 36
F. Diagnostic Charts ........................................................................................................ 38
V. Removal and Replacement of Components .................................................................... 41
A. Service for Refrigerant Lines ....................................................................................... 41
1. Refrigerant Recovery ............................................................................................. 42
2. Brazing .................................................................................................................. 42
3. Evacuation and Recharge (R-404A) ...................................................................... 42
B. Important Notes for Component Replacement ............................................................ 43
1. Upper Bearing Wear Check ................................................................................... 45
2. Removal and Replacement of Cutter ..................................................................... 45
3. Removal and Replacement of Extruding Head ...................................................... 46
4. Removal and Replacement of Auger ..................................................................... 46
5. Removal and Replacement of Evaporator ............................................................. 47
6. Removal and Replacement of Mechanical Seal and Lower Housing ................... 48
7. Removal and Replacement of Gear Motor ............................................................. 49
VI. Cleaning and Maintenance ............................................................................................. 51
A. Cleaning and Sanitizing Instructions ........................................................................... 51
1. Cleaning Solution ................................................................................................... 51
2. Cleaning Procedure ............................................................................................... 51
3. Sanitizing Solution ................................................................................................. 53
4. Sanitizing Procedure - Initial .................................................................................. 53
5. Sanitizing Procedure - Final ................................................................................... 54
B. Maintenance ................................................................................................................ 55
C. Preparing the Icemaker for Long Storage ................................................................... 57
5
Important Safety Information
Throughout this manual, notices appear to bring your attention to situations which could
result in death, serious injury, or damage to the unit.
WARNING Indicates a hazardous situation which could result in death or
serious injury.
CAUTION Indicates a situation which could result in damage to the unit.
IMPORTANT Indicates important information about the use and care of the
unit.
WARNING
This icemaker should be destined only to the use for which it has been
expressly conceived. Any other use should be considered improper and
therefore dangerous. The manufacturer cannot be held responsible for injury or
damage resulting from improper, incorrect, and unreasonable use.
To reduce the risk of death, electric shock, serious injury, or re, follow
basic precautions including the following:
•Thisunitshouldbedisassembledorrepairedonlybyqualiedservice
personnel to reduce the risk of electric shock, injury, or re.
•Movethepowerswitchtothe"OFF"position.Unplugtheicemakerfromthe
electrical outlet and turn off the power supply to the condensing unit before
any servicing is undertaken. Place the disconnect (if applicable) in the off
position. Lockout/Tagout to prevent the power supply from being turned back
on inadvertently.
•Makesuretheicemakerpowerswitchisinthe"OFF"positionbeforeplugging
in or unplugging the icemaker to reduce the risk of electric shock.
•Donotmakeanyalterationstotheicemakerorcondensingunit.Alterations
could result in electric shock, injury, re, or damage to the units.
For FS
•Theicemakerrequiresanindependentpowersupplyofpropercapacity.See
the nameplate for electrical specications. Failure to use a properly sized
breaker or fuse can result in a tripped breaker, blown fuse, or damage to
existing wiring. This could lead to heat generation or re.
•THIS UNIT MUST BE GROUNDED. This unit is equipped with a 3-prong
grounding plug to reduce the risk of potential shock hazards. It must be
plugged into a properly grounded, independent wall outlet. If the outlet is a
2-prong outlet, it is your personal responsibility to have a qualied electrician
replace it with a properly grounded, independent 3-prong wall outlet. Do not
remove the ground prong from the power cord and do not use an adapter plug.
•Donotuseanextensioncord.
•Toreducetheriskofelectricshock,makesurethepowerswitchisinthe"OFF"
position before plugging in or unplugging the unit.
6
For FS - Continued
•Toreducetheriskofelectricshock,donottouchtheplugorpowerswitchwith
damp hands.
•Donotuseaunitwithadamagedpowercord.Thepowercordshouldnotbe
altered, jerked, bundled, weighed down, pinched, or tangled. Such actions
could result in electric shock or re. To unplug the unit, be sure to pull the plug,
not the cord, and do not jerk the cord.
•Donotplacengersoranyotherobjectsintotheicedischargeopening.
For SRC
•Electricalconnectionmustbehard-wiredandmustmeetnational,state,and
local electrical code requirements. Failure to meet these code requirements
could result in death, electric shock, serious injury, re, or severe damage to
equipment.
•Theremotecondensingunitrequiresanindependentpowersupplyofproper
capacity. See the nameplate for electrical specications. Failure to use a
properly sized breaker or fuse can result in a tripped breaker, blown fuses, or
damage to existing wiring. This could lead to heat generation or re.
•THIS UNIT MUST BE GROUNDED. Failure to properly ground the remote
condensing unit could result in death or serious injury.
•Lockout/Tagouttopreventthepowersupplyfrombeingturnedbackon
inadvertently.
7
AC SUPPLY VOLTAGE 115/60/1
GEAR MOTOR 120 V 3 FLA 1/4 HP
OTHER 120 V 0.03A
MAXIMUM FUSE SIZE 15 A
MAX. HACR BREAKER (USA ONLY) 15 A
MAX. CIRC. BREAKER (CANADA ONLY) 15 A
MINIMUM CIRCUIT AMPACITY 15 A
APPROXIMATE ICE PRODUCTION Ambient WATER TEMP. (°F)
PER 24 HR. Temp.(°F) 50 70 90
lb./day (kg/day) 70 *830 (380) 805 (365) 785 (355)
Reference without *marks 80 765 (350) 750 (340) 730 (330)
90 710 (325) *705 (320) 680 (310)
100 660 (300) 650 (295) *600 (275)
SHAPE OF ICE Cubelet
ICE QUALITY Approx. 80%, Ice (90/70°F, Conductivity 200 µs/cm)
APPROXIMATE STORAGE CAPACITY N/A
ELECTRIC & WATER CONSUMPTION 90/70°F 70/50°F
ELECTRIC W (kWH/100 lbs.) 1745 (5.96) 1713 (4.94)
FS-1022MLH-C & SRC-10H
ELECTRIC W (kWH/100 lbs.) 331 (1.13) 345 (1.00)
FS-1022MLH-C ONLY
POTABLE WATER 84 (12) 100 (12)
gal./24HR (gal./100 lb.)
EXTERIOR DIMENSIONS (WxDxH) 22"x16.5"x26" (560x417x657mm)
EXTERIOR FINISH Stainless Steel
WEIGHT Net 126 lb. (57 kg), Shipping 166 lb. (75 kg)
CONNECTIONS - ELECTRIC Cord Connection
- WATER SUPPLY Inlet 1/2" FPT
- DRAIN Outlet 3/4" FPT
- REFRIGERATION Suction line 1-1/16-12 UNF Fitting (#10 PARKER)
CIRCUIT Liquid line 5/8-18 UNF Fitting (#6 PARKER)
ICE MAKING SYSTEM Auger type
HARVESTING SYSTEM Direct Driven Auger (1/4 HP Gear Motor)
ICE MAKING WATER CONTROL Float Switch
COOLING WATER CONTROL N/A
BIN CONTROL SYSTEM (Primary) Photoelctric Sensor
BIN CONTROL SYSTEM (Secondary) Mechanical Bin Control (Proximity Switch)
CONDENSING UNIT Air-Cooled Remote Condensing unit SRC-10H Required
EVAPORATOR Copper Tube on Cylinder
REFRIGERANT CONTROL Thermostatic Expansion Valve
Headmaster (C.P.R.) on SRC-10H (210 PSI)
REFRIGERANT CHARGE R-404A, 8 lb. 6 oz. (3800 g)
Icemaker: 4 oz. (113 g)
Condensing Unit: 8 lb. 2 oz. (3687 g)
DESIGN PRESSURE High 427 PSIG, Low 230 PSIG
P.C. BOARD CIRCUIT PROTECTION Fuse (1A)
GEAR MOTOR PROTECTION Fuse (3A)
LOW WATER PROTECTION Float Switch and Timer
ACCESSORIES -SUPPLIED Spare Fuse
-REQUIRED Ice Storage Bin
Condensing Unit: SRC-10H
OPERATING CONDITIONS VOLTAGE RANGE 104-127VAC
AMBIENT TEMP. 45-100°F
WATER SUPPLY TEMP. 45-90°F
WATER SUPPLY PRESSURE 10-113 PSIG
ENG.F-013.0.1196
I. Specications
A. Icemaker
1. FS-1022MLH-C
Note: We reserve the right to make changes in specications and design without prior
notice.
8
Note: We reserve the right to make changes in specications and design without prior
notice.
B. Condensing Unit
1. SRC-10H
AC SUPPLY VOLTAGE 208-230/60/1 (3 Wire w/Neutral for 115VAC)
COMPRESSOR 208-230V 9.6 RLA 46 LRA
FAN MOTOR 120 V 3 A MAX
OTHER 120 V 0.5 A
MAXIMUM FUSE SIZE 20 A
MAX. HACR BREAKER (USA ONLY) 20 A
MAX. CIRC. BREAKER (CANADA ONLY) 20 A
MINIMUM CIRCUIT AMPACITY 20 A
EXTERIOR DIMENSIONS (WxDxH) 28"x23"x19" (711x280x485mm)
DIMENSIONS WITH LEGS (WxDxH) 28"x23"x36" (711x280x915mm)
EXTERIOR FINISH Galvanized Steel
WEIGHT (Approximate) Net 143 lb. (65 kg), Shipping 169 lb. (77 kg)
CONNECTIONS - ELECTRIC Permanent - Connection
- REFRIGERATION Suction Line 1 1/16"-12 UNF Fitting (#10 PARKER)
CIRCUIT Liquid Line 5/8"-18 UNF Fitting (#6 PARKER)
COMPRESSOR Hermetic, Model RS80-C2E-CAV
CONDENSER Air-Cooled Fin and Tube Type
FAN MOTOR PROTECTION Thermal Protector
REFRIGERATION PROTECTION Auto-Reset High-Pressure Switch, Manual Low-Pressure Switch
REFRIGERANT CONTROL Headmaster (C.P.R.) (210 PSI)
PUMPDOWN CONTROL Auto-Reset Low-Pressure Switch
REFRIGERANT CHARGE R-404A, 8 lb. 6 oz. (3800 g)
Condensing Unit: 8 lb. 2 oz. (3687 g)
Icemaker: 4 oz. (113 g)
DESIGN PRESSURE High 427 PSIG, Low 230 PSIG
COMPRESSOR PROTECTION Internal Protector
ACCESSORIES -SUPPLIED Leg 2 pcs.
Hex Head Bolt w/ Washer 8X16 8 pcs.
Hex Nut 8 pcs.
OPERATING CONDITIONS VOLTAGE RANGE 187-253 VAC
AMBIENT TEMP. -4-122°F
HEAT OF REJECTION 10500 BTU/hr
ENG.F-013.0.1196
9
II. General Information
A. Construction
1. Icemaker
a) FS-1022MLH-C
Inlet Water Valve
Reservoir
Control Box
Mechanical Backup
Bin Control
Spout
Float Switch
Gear Motor
Thermostatic
Expansion Valve
Ice Chute
Infrared Sensor
Icemaking Unit:
Cutter
Extruding Head
Evaporator
Power Cord
Drain Valve
Pump-Down
Solenoid Valve
High-Side
Service Valve
Low-Side
Service Valve
Evaporator Heater
Strainer
10
2. Condensing Unit
a) SRC-10H
Condenser
Receiver
Fan Motor
Headmaster (C.P.R.)
High-Side
Service Valve
Compressor
High-Pressure
Switch
Liquid Line
Connection
Suction Line
Connection
Control Low-Pressure Switch
Control Box
Safety Low-Pressure Switch
11
3. Icemaking Unit
Cutter
Extruding Head
Upper Bearing
Evaporator Heater
Auger
Mechanical Seal
O-Ring
Housing-Lower Bearing
Spline Coupling
Gear Motor
Hex Bolt and Washer
Evaporator
Seal Bolts and Washers
Socket Head Cap Screw
and Split Lock Washer
Washer
Socket Head Cap Screw
and Split Lock Washer
12
B. Sequence of Operation
The steps in the sequence are as outlined below. This unit utilizes a control board to
switch the icemaker components on and off as needed. When power is supplied, the
powerswitchisinthe"ON"position,andthecontrolswitchisinthe"ICE"position,
controlboard"POWEROK"LEDandinfraredsensorgreenLEDcomeon.The"POWER
OK"LEDremainsonconstantly.IftheinfraredsensoryellowLEDisonorashing,move
ice away from the infrared sensor lens.
This system utilizes a pump-down solenoid valve in the icemaker and a control
low-pressure switch in the condensing unit to control the operation of the Comp and
FMR. This eliminates the need for an electrical connection between the 2units. When
calling for ice, the control board (X1 on control board) energizes the pump-down
solenoid. The low-side refrigerant pressure rises to 29 PSIG, the control low-pressure
switch (located in the condensing unit) closes, energizing the Comp and FMR. When the
ice level satises the infrared sensor bin control (bin full), the unit goes into the shutdown
cycle. The control board de-energizes the pump-down solenoid valve (X1 on CB). The
low-side refrigerant pressure drops (unit pumping down). When the low-side pressure
drops to 9 PSIG, the control low-pressure switch opens, de-energizing Comp and FMR.
Control Low-Pressure Switch Settings: Cut-Out: 9PSIG. Differential: 20 PSIG.
Cut-In: 29 PSIG.
1. Sequence Cycles and Shutdown
a) Fill Cycle
"WTRIN" LED is on. WV energizes and ll cycle begins. 90-second low water safety
timer starts. When UF/S closes, WV de-energizes, and 90-second low water safety timer
resets. 30-second GM delay timer starts. If 90-second low water safety timer terminates
before UF/S closes, WV remains energized, and a 1-beep alarm sounds.
b) Ice Purge Cycle
"GM" LED is on. 30-second GM delay timer terminates. GMR (X2 on CB), GM, GMPR,
and EH energize. 5-minute ice purge timer starts: GM runs for 5 minutes to clear any
icefromtheevaporator.Tobypass,pressthe"SERVICE"buttononCBafterGMstarts.
WARNING! Risk of electric shock. Care should be taken not to touch live terminals.
Note: UF/S must be closed before GMR will energize.
c) Freeze Cycle
"COMP" and "GM" LEDs are on. 5-minute ice purge timer terminates. GMR (X2 on
CB), GM, GMPR, and EH continue. CR (X1 on CB) and PDS energize. When CLPS (in
SRC) closes, MC energizes, allowing Comp and FMR to energize. CCH de-energizes.
As water in the evaporator cools, ice starts forming within 4 to 6 minutes. This time frame
depends on the inlet water and ambient temperature conditions. UF/S and LF/S operate
WV as needed to continue the ice making process. This continues until IS activates
allowing CB to de-energize X1 on CB and PDS. The unit goes into pump-down, CLPS
opens, MC de-energizes, de-energizing Comp and FMR. CCH energizes.
13
d) Drain Cycle
(1) 1-in-1 Drain Cycle: DV energizes for 2 seconds once every hour when the
1-in-1drain cycle is activated (S1 dip switch 4 in the off position (factory default
position)). 1-hour drain cycle timer terminates, 2-second DT starts. DV energizes for
2seconds. 2-second DT terminates, 1-hour DT resets. All components and icemaking
continue. This setting is recommended for optimum icemaker performance. The
1-in-1drain cycle allows any sediment to drain from the evaporator without interrupting
the icemaking process.
(2) 1-in-12 Drain Cycle (optional): DV energizes for ten minutes once every
12hourswhenthe1-in-12draincycleisactivated(S1dipswitch4inthe"ON"
position (optional)). 12-hour drain cycle timer terminates, CR (X1 on CB) and PDS
de-energize, GMR (X2on CB), GM, GMPR, and EH continue. Unit is in pump-down
mode. Once the low-side pressure drops to 9 PSIG, CLPS opens, de-energizing MC,
Comp, and FMR. 5-minute ice purge timer begins. When the 5-minute ice purge timer
terminates, GMR (X2 on CB), GM, GMPR, and EH de-energize. 10-minute DT begins,
DV energizes. After 10-minute DT terminates, 12 hour drain cycle timer starts.
(3) Manual Drain: Manual drain is used when servicing evaporator components and
cleaning and sanitizing the unit. When the unit is making ice and the control switch is
movedtothe"DRAIN"position,thereisa3-seconddelay,thenCR(X1onCB)and
PDS de-energize. Unit is in pump-down mode. Once the low-side pressure drops to
9 PSIG, CLPS opens, de-energizing MC, Comp, and FMR. 5-minute ice purge timer
begins. When the 5-minute ice purge timer terminates, GMR (X2 on CB), GM, and
GMPR de-energize. DV energizes to drain the evaporator and reservoir. To avoid the
5-minute shutdown delay, turn off the icemaker power supply, then move the control
switchtothe"DRAIN"position.DVde-energizeswhenthecontrolswitchismovedto
the"ICE"position.
14
e) Shutdown Cycle
(1) Infrared Sensor: When power is supplied to the icemaker, the green LED on IS
turns on. The green LED remains on constantly. As ice lls the storage bin to the
levelofactivatingIS,ISyellowLEDturnson(ashingorsteady).TheyellowLED
asheswheniceisattheouterlimitofitsrangeandturnssteadyasicenears.After
theyellowLEDturnson(ashingorsteady),ISshutdowndelaytimer(S1dipswitch
1, 2, 3) begins. For a typical dispenser unit application, a 100-second shutdown delay
is recommended. When used with a standard Hoshizaki storage bin, any shutdown
delaysettingisacceptable.See"II.C.3.b)InfraredSensorShutdownDelay(S1dip
switch1,2,3)."OnceISshutdowndelaytimerterminates,CR(X1onCB)andPDS
de-energize and the 5-minute ice purge timer begins. Unit is in pump-down mode.
Once the low-side pressure drops to 9PSIG, CLPS opens, de-energizing MC, Comp,
and FMR. When the 5-minute ice purge timer terminates, GMR (X2 on CB), GM, and
GMPR de-energize.
Note: If IS fails to shut down the icemaker, MBC opens, CB shuts down the icemaker,
and a 9-beep alarm sounds.
(2) Mechanical Backup Bin Control: CB shuts down the entire unit within 10 seconds
when MBC opens (actuator paddle engaged), and sounds a 9-beep alarm.
Legend: CB–control board; CCH–crankcase heater; CLPS–control low-pressure
switch; Comp–compressor; CR–compressor relay (pump-down solenoid);
DT–drain timer; DV–drain valve; EH–evaporator heater; FMR–fan
motor-remote; F/S–oatswitch;GM–gear motor; GMPR–gear motor protect
relay; GMR–gear motor relay; IS–infrared sensor; LF/S–loweroatswitch;
MBC–mechanical backup bin control; MC–magnetic contactor;
PDS–pump-down solenoid valve; UF/S–upperoatswitch; WV–inlet water
valve
15
1-in-1 drain cycle. DV opens for 2 seconds every
hour (S1 Dip Switch 4).
"F-A" Control Board Sequence Flow Chart
FS-1022MLH-C/SRC-10H
LF/S closed
UF/S closed
FT terminates
WV de-energizes
3. 1-in-12 Drain Cycle
& Restart (optional)
3. Icemaker Off
UF/S open
LF/S open
FT starts (90 sec.)
WV energizes
Comp continues
EH continues
FMR continues
GM continues
PDS continues
1. Startup
2. Ice Purge Cycle
WV energizes
FT starts (90 sec.)
PDS energizes
CLPS closes
Comp energizes
FMR energizes
EH continues
GM continues
PowerSwitch"ON"
ControlSwitchin"ICE"
POWER OK LED on
IS Green LED on
IS Yellow LED off
2. Infrared Sensor Shutdown & Restart
1. Bin Full
IS activated or DC starts
PDS de-energizes
CLPS opens
Comp de-energizes
FMR de-energizes
GM continues
1. Fill Cycle
3. Freeze Cycle
LF/S closed
UF/S closed
FT terminates
WV de-energizes
Comp continues
EH continues
FMR continues
GM continues
PDS continues
Low Water Safety
UF/S open
FT exceeded
1-beep alarm sounds
PDS de-energizes
CLPS opens
Comp de-energizes
FMR de-energizes
EH continues
GM continues
WV continues
DV energizes (DC only)
GM de-energizes
2. Ice Purge Cycle
10-min. DT terminates (DC only)
DV de-energizes (DC only)
1-in-12 DT reset (DC only)
IS Green LED on
IS Yellow LED(ashingorsteady)
IS delay determined by S1 dip switch
1, 2, 3
4. Icemaker Restart
5 minutes
Note: If IS fails to shutdown the
icemaker, MBC opens and a
9-beep alarm sounds.
4. Icemaker Restart
2. Ice Purge Cycle
3. 10-Minute
Drain
Legend:
CLPS-control low-pressure switch
Comp-compressor
DC-drain cycle
DT-drain timer
DV-drain valve
EH-evaporator heater
FMR-fan motor-remote
FT-ll timer (low water safety)
GM-gear motor
IS-infrared sensor bin control
If Fill > 90 sec.
FT1-beep alarm
sounds.
When UF/S
closes alarm
resets and
2. Ice Purge
Cycle starts.
Maximum
90 seconds
4. 1-in-12 Drain Cycle - Although the factory default 1-in-1 drain cycle
is recommended, a 1-in-12 drain cycle is available. For 1-in-12 drain
cyclesequence,see"3.1-in-12HourDrainCycle&Restart(optional)."
Rell
FT Maximum
90 seconds
90 sec. FT exceeded
1-beep alarm sounds
90 sec. PT begins
When UF/S closes,
alarm resets and
2. Ice Purge Cycle
starts.
1-beep alarm continues
WV continues
EH de-energizes
GM de-energizes
IS Green LED on
IS Yellow LED off
IS Green LED on
IS Yellow LED off
1. DT Initiates DC
To bypass, press the
"SERVICE"button
after GM starts.
5 minutes
to"2.IcePurgeCycle"above
to"1.FillCycle"above
90 seconds
(S1 dip switch 4)
FT terminates
(90 sec.)
FT exceeded
PT terminates
30 sec.
EH energizes
GM energizes
LF/S-loweroatswitch
MBC-mechanical backup
bin control
PDS-pump-down solenoid valve
PT-purge timer
UF/S-upperoatswitch
WV-water valve
Icemaker status
does not change.
2. Sequence Flow Chart
16
C. Control Board
A Hoshizaki exclusive control board is employed in Hoshizaki Modular Flakers.
All models are pre-tested and factory set.
CAUTION
1. The control board is fragile; handle very carefully.
2. The control board contains integrated circuits, which are susceptible to failure
due to static discharge. It is especially important to touch the metal part of
the icemaker before handling or replacing the control board.
3. Do not touch the electronic devices on the control board or the back of the
control board.
4. Do not change wiring and connections. Do not misconnect terminals.
5. Do not short out power supply to test for voltage.
6. Always replace the whole control board assembly if it goes bad.
17
"F-A" Control Board
"F-A" Control Board
Part Number
2A4296-01
•"FLUSH" LED
(X3 Relay)
Drain Valve
"COMP" LED
(X1 Relay)
Pump-Down
Solenoid Valve
"GM" LED
(X2 Relay)
Gear Motor
Evaporator Heater
•K1 Connector
(115VAC)
#3 115VAC Input
#2 Gear Motor,
Evaporator
Heater
•"WTRIN" LED
(X4 Relay)
Inlet Water Valve
•K6 Connector (20VDC)
Infrared Sensor Bin Control
"SERVICE" Button
(Ice Purge Cycle Bypass)
#5 & #6 Gear Motor Protect
Relay Circuit
#3 & #4 Jumper
#1 & #2 Control Switch
Open: Icemaking
Closed: Drain
"POWER OK" LED
S1 Dip Switch
1. Control Board Layout
•K9 Connector (5VDC)
•K8 Connector
(24VAC and 5VDC)
#1 Transformer 24VAC Input
#2 Transformer 24VAC Neutral
#3 & #4 Mechanical Backup Bin
Control (5VDC)
#5 Float Switch Common (5VDC)
#6 Upper Float Switch
#7 Lower Float Switch
K7 Connector-Open
•K2 Connector
(24VAC)
#10 Drain Valve
#9 Transformer
24VAC Input
#8 Inlet Water Valve
#7 Transformer
24VAC Input
Water Dispensing
Valve, Agitation
Motor, and Ice
Dispensing LEDs
(not used on this
model)
K3 Connector-Open
K4 Connector-Open
K5 Connector-Open
J2 Connector-Open
Brown (ground)
White (signal) (common)
Dark Blue
18
2. LED Lights and Audible Alarm Safeties
The"POWEROK"LEDindicatespropercontrolvoltageandwillremainonunlessa
controlvoltageproblemoccurs.Forfurtherdetails,see"II.B.SequenceofOperation."
Sequence Step LED
Energized
Components Min. Max.
Fill Cycle WTRIN WV - -
Ice Purge Cycle GM GM, EH 5 min. 5 min.
Freeze Cycle (with rell) GM, COMP,
WTRIN* (rell),
GM, EH, PDS, Comp,
FMR,
WV* (rell)
- *On until UF/S closes.
Alarm sounds after
90 sec.
1-in-1 Drain Cycle
(S1 dip switch 4 off)
FLUSH (Drain)
GM, COMP
(only if IS not
satised)
DV
Comp, GM, EH, PDS,
FMR (only if IS not
satised)
2 sec. 2 sec.
1-in-12 Drain Cycle
(S1 dip switch 4 on)
FLUSH (Drain) DV 10 min. 10 min.
The built-in alarm safeties shut down the unit.
No. of Beeps
(every 5 sec.)
Type of Alarm Reset Options
1 Low Water Safety
UF/S open > 90 seconds after WV energized.
Automatic reset once water supply is restored
and UF/S closes.
2 Control Switch
In"DRAIN"positionlongerthan15minutes.
Automatic reset once the control switch is
movedtothe"ICE"position.
3 High-Pressure Switch: N/A on this model. See"III.B.2.SRC-10H"forhigh-pressure
switch operation.
4 High-Pressure Switch: N/A on this model.
5 Freeze Timer
WV off > 30 minutes since last WV activation.
Manual reset. Turn power off and on again.
6 Low Voltage
(92VAC±5% or less)
"POWEROK"LEDturnsoffifvoltage
protection operates.
The control voltage safeties automatically
reset when voltage is corrected.
7 High Voltage
(147VAC±5% or more)
8 Gear Motor
GMPR contacts fail to close.
Manual reset. Turn power off and on again.
9 Infrared Sensor (S1 dip switch 7)
MBC actuator paddle engaged.
Manual reset. Turn power off and on again.
Legend: DV–drain valve; EH–evaporator heater; FMR–fan motor-remote; GM–gear
motor; IS–infrared sensor bin control; MBC–mechanical backup bin control;
PDS-pump-down solenoid valve; WV–inlet water valve
19
3. Controls and Adjustments
CAUTION
Dip switches are factory set. Failure to maintain factory settings may adversely
affect performance and warranty coverage. For more information, contact
Hoshizaki Technical Support at 1-800-233-1940.
a) Default Dip Switch Settings
The S1 dip switch settings are factory-set to the following positions:
S1 Dip Switch No. 1 2 3 4 5 6 7 8 9 10
FS-1022MLH-C ON OFF OFF OFF OFF OFF ON ON OFF OFF
Infrared Sensor Shutdown Delay
Continuous Dispensing Timer
(DCM models only, do not adjust on modular icemakers)
Drain Frequency Control
Bin Control Selector
Mechanical Backup Bin Control Shutdown Delay
Normally off (factory use)
b) Infrared Sensor Shutdown Delay (S1 dip switch 1, 2, 3)
Infrared sensor shutdown delay is the delay between the infrared sensor detecting ice
(yellowLEDashingorsteady)andthestartoftheshutdownsequence.Fordispenser
unit applications, the ice level at shutoff may need to be adjusted depending on the
dispenser agitation or dispense method. Increasing the shutdown delay setting allows for
a higher level of ice in the bin before the icemaker shuts down. For a typical dispenser
unit application, a 100-second shutdown delay is recommended. When used with a
standard Hoshizaki storage bin, any shutdown delay setting is acceptable.
WARNING
Increasing the shutdown delay allows a higher level of ice in the dispensing
unit/storage bin before shutdown. This could lead to icemaker movement or ice
overow.
S1 Dip Switch Setting
Infrared Sensor Shutdown Delay
No. 1 No. 2 No. 3
OFF OFF OFF 0 Seconds
ON OFF OFF 100 Seconds (1.6 minutes) (Factory Default)
OFF ON OFF 1100 Seconds (18.3 minutes)
OFF OFF ON 1650 Seconds (27.5 minutes)
ON ON OFF 2200 Seconds (36.7 minutes)
OFF ON ON 0 Seconds
ON ON ON 0 Seconds
20
c) Drain Frequency Control (S1 dip switch 4)
This unit is factory set for optimum performance with the 1-in-1 drain cycle (S1 dip
switch4inthe"OFF"position).Thissettingallowsforremovalofsedimentfromthe
evaporator without interrupting the icemaking process. An optional 1-in-12 drain cycle is
available.
S1 Dip Switch Setting
Drain Timer Interval Drain Valve Open
No. 4
OFF (1-in-1) 1 Hour 2 Seconds
ON (1-in-12) 11 Hours 45 Minutes 10 Minutes
d) Continuous Dispensing Timer (S1 dip switch 5 & 6)
DCMmodelsonly.ThedispensemodeswitchonDCMsmustbeinthe"CONTINUOUS"
position for this setting to apply. The factory setting allows ice to be dispensed
continuously as long as the dispense solenoid is activated.
S1 Dip Switch Setting
Dispense Time
No. 5 No. 6
OFF OFF No Limit
ON OFF 20 Seconds
OFF ON 60 Seconds
ON ON No Limit
e) Bin Control Selector (S1 dip switch 7)
This unit is factory set for infrared sensor bin control operation. No adjustment is
required. When used on a standard ice storage bin, the mechanical bin control may be
used instead of the infrared sensor by moving S1 dip switch 7 to the off position. In the
factory default position (S1 dip switch 7 in the on position), the gear motor delay after the
upperoatswitchclosesis30seconds.Whenthemechanicalbincontrolisused(S1
dipswitch7intheoffposition),thegearmotordelayaftertheupperoatswitchclosesis
5 seconds. WARNING! Do not place S1 dip switch 7 in the off position on dispenser
unit applications.
S1 Dip Switch
Setting
Bin Control Application Gear Motor Delay
No. 7
OFF Mechanical Bin Control (Standard Ice Storage Bins Only) 5 seconds
ON
Infrared Sensor with
Mechanical Bin Control Backup
30 seconds
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57