User Guide Pump Optimization with the Danfoss ∆p Tool for Dynamic Valve™ (example)
Make sure: 1) the pump is set in constant pressure
2) all the valves in the system are fully open
10
9
8
7
6
5
4
3
2
1
__
__
__
__
__
__
__
__
__
CLOSE
OPEN
OK
PFM 100
+
-
open valve
150.0
kPa
OK
PFM 100
+
-
close valve
146.0
kPa
OK
PFM 100
+
-
delta P
4.0
kPa
XX
kPa
__
__
__
__
__
__
__
__
__
CLOSE
OPEN
OK
PFM 100
+
-
open valve
155.2
kPa
OK
PFM 100
+
-
close valve
150.2
kPa
OK
PFM 100
+
-
delta P
5.0
kPa
YY
kPa
If the differential pressure is constant
(XX=YY)* go one level down in the
pump setting DONE
If the differential pressure is not constant
(XX≠YY) increase the pump setting and
measure again. See 8 to 11.
OK
PFM 100
+
-
delta P
7.0
kPa
AA
kPa
10
9
8
7
6
5
4
3
2
1
__
__
__
__
__
__
__
__
__
__
CLOSE
OK
PFM 100
+
-
open valve
159.8
kPa
OK
PFM 100
+
-
close valve
152.8
kPa
OK
PFM 100
+
-
delta P
7.0
kPa
BB
kPa
Repeat 8-11 until the differential
pressure is constant (AA=BB)*.
Go one level down in the pump
setting DONE
* The measured value at constant differential pressure is between 6 to 10 kPa
1. 2. 3.
4. 5. 6.
8. 9.
10. 11.
Danfoss Installer App
Android Google Play
iPhone App Store
7.