Regency Energy E33-LP10 Owners & Installation Manual

Category
Fireplaces
Type
Owners & Installation Manual
Tested by:
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
Energy E33 Gas Insert
Owners & Installation Manual
MODELS: E33-NG10 Natural Gas E33-LP10 Propane
- Do not store or use gasoline or other ammable vapors and liquids in the vicinity of this or any other
appliance.
- WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch: do not use any phone in your building.
Leave the building immediately.
Immediately call your gas supplier from a neighbour's phone. Follow the gas supplier's
instructions.
• If you cannot reach you gas supplier, call the re department.
- Installation and service must be performed by a qualied installer, service agency or the gas supplier.
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious
injury, death, or property damage.
919-379c FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4 03.01.17
2 | E33-10 FPI Direct Vent Gas Insert
|
2
REGENCY GAS FIREPLACE INSERT
TO THE NEW OWNER
Congratulations! You are the owner of a state-of-the-art Gas Insert by Regency.
The E33 Gas Insert has been designed to provide you with all the warmth and charm of a replace, at
the ick of a switch. The E33-NG10 and E33-LP10 have been approved by Warnock Hersey/Intertek
for both safety and eciency. As it also bears our own mark, it promises to provide you with economy,
comfort and security for many trouble free years to follow. Please take a moment now to acquaint yourself
with these instructions and the many features of your Regency Fireplace.
Energy E33 Video
E33-10 FPI Direct Vent Gas Insert | 3
| 3
dimensions
28
11
16
"
42 7
16
"
26 3
4
"
16 1
4
"
23 3
4
"
11 1
16
22 3
4
"
46 1
2
"
(1181mm)
(1078mm)
(679mm)
(729mm)
(281mm)
(413mm)
(603mm)
(578mm)
"
31
4
"
13
4
(83mm)
(44mm)
32-1/4
819mm
24-1/2
(622mm)
UNIT DIMENSIONS
LOW PROFILE FACEPLATE
This appliance does not have the capability to adjust the fan speed using the supplied remote—even though the remote transmitter allows
this function. The appliance fan is controlled by a fan speed controller (rheostat) or on/o switch depending on the model.
4 | E33-10 FPI Direct Vent Gas Insert
|
4dimensions
UNIT DIMENSIONS
OPTIONAL VIGNETTE FACEPLATE WITH SPACER
E33-10 FPI Direct Vent Gas Insert | 5
| 5
dimensions
UNIT DIMENSIONS
OPTIONAL VIGNETTE FACEPLATE WITHOUT SPACER
6 | E33-10 FPI Direct Vent Gas Insert
|
6dimensions
UNIT DIMENSIONS
OVERSIZE BACKINGPLATE WITH SPACER
E33-10 FPI Direct Vent Gas Insert | 7
| 7
dimensions
UNIT DIMENSIONS
OPTIONAL 4 SIDED VIGNETTE FACEPLATE
(813 mm)
24-1/2
(622mm)
46-1/2”
(1181mm)
39-5/16”
(999mm)
30-7/8”
(784mm)
26-7/16”
(672mm)
2-3/16”
(56mm)
5”
(127mm)
22 13/16”
(579mm)
23 3/4”
(603mm)
4 SIDED VIGNETTE FACEPLATE
2-1/2”
(64mm)
2-3/16
(54mm)
8 | E33-10 FPI Direct Vent Gas Insert
|
8table of contents
Dimensions
Unit dimensions .............................................................3
Low Prole Faceplate ....................................................3
Unit dimensions .............................................................4
Optional vignette faceplate with spacer ......................... 4
Unit dimensions .............................................................5
Optional vignette faceplate without spacer .................... 5
Unit dimensions .............................................................6
Oversize backing plate with spacer ...............................6
Unit dimensions .............................................................7
Optional 4 sided vignette faceplate ...............................7
Installation
Copy of Safety Label .....................................................9
MA Code - CO Detector...............................................10
Important Message .................................................... 11
For Your Safety ............................................................ 11
Before You Start .......................................................... 11
Specications ..............................................................12
Installation Checklist .................................................... 12
Materials Required ......................................................12
Gas Pressure Testing ..................................................13
Factory-Built (Metal) Wood-Burning Fireplace
Requirements ..............................................................13
Minimum Fireplace Opening........................................14
Combustible Mantel Clearances..................................15
Minimum Clearances To Combustibles .......................15
Gas Connection .......................................................... 16
Venting.........................................................................16
Flue Liner Installation ..................................................16
Gas Pipe Pressure Testing ..........................................17
SIT 829 Valve Description ...........................................17
DC Spark Igniter Battery installation............................17
Gas Insert Aeration System .........................................17
Optional Brick Panel ....................................................18
Brick Panel Installation ................................................18
Log Set Installation ......................................................19
Conversion kit 342-969 from NG to LP ........................22
for E33-10 using SIT 829 NOVA Gas Valve.................22
Optional vignette Faceplate installation ....................... 23
Spacer installation for 3 sided vignette faceplate ........24
Oversize backing plate installation ..............................25
Optional vignette inlay installation ...............................26
Optional hearth trim installation- vignette faceplate with
Spacer and low prole faceplate .................................28
Optional hearth trim installation-
Vignette faceplate without spacer ...............................29
Optional hearth trim installation- Low prole ..............30
Safety screen Installation /
removal - low prole faceplate ..................................... 31
Standard Flush Door removal / installation..................31
Wiring Diagram ............................................................ 32
Optional Wall Thermostat ...........................................32
First Fire ......................................................................33
Operating Instructions
Operating Instructions .................................................33
Lighting Procedure ......................................................33
Shutdown Procedure ...................................................33
Copy of Lighting Instruction Plate ................................ 34
Automatic Convection Fan Operation..........................34
Normal Operating Sounds Of Gas Appliances ............34
Maintenance
Maintenance Instructions.............................................35
General Vent Maintenance .......................................... 35
Log Replacement ........................................................35
Glass Gasket ...............................................................35
Door Glass ..................................................................36
Fan Maintenance ......................................................... 36
Valve Assembly Removal And Installation ................... 37
Parts
Main Assembly ............................................................38
Burner & Log Assembly ...............................................39
Vignette faceplate .......................................................40
Warranty
Warranty .....................................................................42
E33-10 FPI Direct Vent Gas Insert | 9
| 9
safety decal
This is a copy of the labels that accompany each E33 Gas Insert. We have printed a copy of the contents here for your review. The safety label is located
on a plate inside the base of the unit visible when the bottom louver is opened. Ensure that the safety label is attached to the unit.
NOTE: Regency units are constantly being improved. Check the label on the unit and if there is a dierence, the label on the unit is the correct one.
COPY OF SAFETY LABEL
10 | E33-10 FPI Direct Vent Gas Insert
|
10 requirements
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for
residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than
seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall
be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled
equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is
installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery
operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of
qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of
thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions
shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight
(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The
sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation
unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by
the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or
structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product
Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the
instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a
Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies
"special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and
detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions,
all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of
the installation.
MA Code - CO Detector
(for the State of Massachusetts only)
E33-10 FPI Direct Vent Gas Insert | 11
| 11
installation
Fuel Gas Code ANSI Z223.1 in the U.S.A. This
appliance should be installed by a qualied gas
tter technician only.
2) Installation and repair should be done by a
qualied service person.
3) The appliance should be inspected before use
and at least annually by a professional service
person. More frequent cleaning may be required
due to excessive lint from carpeting, bedding
material, animal hair, etc. It is imperative that
control compartments, burners and circulating
air passageways of the appliance be kept clean.
4) See general construction and assembly
instructions. This appliance may only be
installed in a vented, noncombustible replace.
5) This appliance is Listed for bedroom installations
when used with a Listed Millivolt Thermostat.
Some areas may have further requirements,
check local codes before installation.
6) Always connect this insert to a vent system
venting to the outside of the building envelope.
Never vent to another room or inside a building.
Make sure that the vent is properly sized and is
of adequate height to provide the proper draft.
7) Inspect the venting system annually for
blockage and any signs of deterioration.
8) Any glass removed for servicing must be
replaced prior to operating the appliance.
9) To prevent injury, do not allow anyone who is
unfamiliar with the operation to use the replace.
10) Due to high temperatures, the appliance should
be located out of high trac areas and away
from furniture and draperies. Children and
adults should be alerted to the hazards of high
surface temperatures, especially the replace
glass and gold trims, and should stay away to
avoid burns or clothing ignition. Young children
should be carefully supervised when they are
in the same room as the appliance. Clothing or
other ammable material should not be placed
on or near the appliance.
Emissions from burning wood or gas could
contain chemicals known to the State of
California to cause cancer, birth defects or
other reproductive harm.
IMPORTANT MESSAGE
SAVE THESE
INSTRUCTIONS
The Regency Gas Insert must be installed in
accordance with these instructions. Carefully read
all the instructions in this manual rst. Consult the
building authority having jurisdiction to determine
the need for a permit prior to starting the installation.
NOTE: Failure to follow the instructions could cause
a malfunction of the heater which could result in
death, serious bodily injury, and/or property damage.
Failure to follow these instructions may also void
your re insurance and/or warranty.
FOR YOUR SAFETY
This appliance requires air for proper combustion.
Always provide adequate combustion and
ventilation air. Follow instructions and information
in CAN/CGA B149 (in Canada) or the National Fuel
Gas Code ANSI Z223.1 (in the USA), regarding
requirements for combustion and ventilation air.
CLOTHING OR OTHER FLAMMABLE
MATERIAL SHOULD NOT BE PLACED
ON OR NEAR THE APPLIANCE.
CHILDREN AND ADULTS SHOULD BE
ALERTED TO THE HAZARDS OF HIGH
SURFACE TEMPERATURES, ESPE-
CIALLY THE FIREPLACE GLASS, AND
SHOULD STAY AWAY TO AVOID BURNS
OR CLOTHING IGNITION.
INSTALLATION AND REPAIR SHOULD
BE DONE BY AN AUTHORIZED
SERVICE PERSON. THE APPLIANCE
SHOULD BE INSPECTED BEFORE
USE AND AT LEAST ANNUALLY BY A
PROFESSIONAL SERVICE PERSON.
MORE FREQUENT CLEANING MAY
BE REQUIRED DUE TO EXCESSIVE
LINT FROM CARPETING, BEDDING
MATERIAL, ETC. IT IS IMPERATIVE THAT
CONTROL COMPARTMENTS, BURNERS
AND CIRCULATING AIR PASSAGEWAYS
OF THE APPLIANCE BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES, THE
APPLIANCE SHOULD BE LOCATED
OUT OF TRAFFIC AND AWAY FROM
FURNITURE AND DRAPERIES.
WARNING: FAILURE TO INSTALL THIS
APPLIANCE CORRECTLY WILL VOID
YOUR WARRANTY AND MAY CAUSE A
SERIOUS HOUSE FIRE.
YOUNG CHILDREN SHOULD BE CARE-
FULLY SUPERVISED WHEN THEY ARE
IN THE SAME AREA AS THE APPLI-
ANCE. TODDLERS, YOUNG CHILDREN
AND OTHERS MAY BE SUSCEPTIBLE
TO ACCIDENTAL CONTACT BURNS. A
PHYSICAL BARRIERS IS RECOMMEND-
ED IF THERE ARE AT RISK INDIVIDUAL
IN THE HOUSE. TO RESTRICT ACCESS
TO A FIREPLACE OR STOVE, INSTALL
AN ADJUSTABLE SAFETY GATE TO
KEEP TODDLERS, YOUNG CHILDREN
AND OTHER AT RISK INDIVIDUALS OUT
OF THE ROOM AND AWAY FROM HOT
SURFACES.
BEFORE YOU START
Safe installation and operation of this appliance
requires common sense, however, we are required
by the Canadian Safety Standards and ANSI Stand-
ards to make you aware of the following:
General Safety Information
1) The appliance installation must conform with
local codes or in the absence of local codes,
with CAN/CGA B149 (in Canada) or the National
A BARRIER DESIGNED TO REDUCE
THE RISK OF BURNS FROM THE HOT
VIEWING GLASS IS PROVIDED WITH
THIS APPLIANCE AND SHALL BE
INSTALLED FOR THE PROTECTION
OF CHILDREN AND OTHER AT-RISK
INDIVIDUALS
IF THE BARRIER BECOMES DAMAGED,
THE BARRIER SHALL BE REPLACED
WITH THE MANUFACTURER'S BARRIER
FOR THIS APPLIANCE.
ANY SAFETY SCREEN, GUARD, OR
BARRIER REMOVED FOR SERVICING
AN APPLIANCE MUST BE REPLACED
PRIOR TO OPERATING THE APPLIANCE. For the State of Massachusetts, installation
and repair must be done by a plumber or
gastter licensed in the Commonwealth of
Massachusetts.
For the State of Massachusetts, exible con-
nectors shall not exceed 36 inches in length.
For the State of Massachusetts, the appliances
individual manual shut-o must be a t-handle
type valve.
The State of Massachusetts requires the
installation of a carbon monoxide alarm in
accordance with NFPA 720 and a CO alarm
with battery back up in the same room where
the gas appliance is installed.
12 | E33-10 FPI Direct Vent Gas Insert
|
12 installation
SPECIFICATIONS
At pressures over 1/2 psig, the pipe to the unit
must be disconnected.
Gas Input Capacity:
Natural Gas 38,000 Btu/h
Propane 35,500 Btu/h
Min. Input:
Natural Gas 20,000 Btu/h
Propane 19,000 Btu/h
Fuels: Approved for use with both natural gas,
and propane. Approved as is for use at 0' to 4,500'
(0-1370m).
Electrical: 120V A.C. system.
Circulation Fan: Variable speed, 127 CFM.
Log Set: Ceramic bre, 8 per set.
Vent System: 3" co-linear aluminum ex.
INSTALLATION
CHECKLIST
Before installing vent system ensure that the damper
plate is open and secure to prevent the damper plate
from falling down and crushing the liner.
The Regency Gas Insert is installed as listed below.
1) Check all clearances to combustibles. Refer
to the following sections where applicable:
a. Minimum Clearances to Combustibles.
b. Combustible Mantel Clearances
2) Make the gas connection. Refer to the "Gas
Connection" section.
3) Install the 3" ue liner to the sliding connector
plate. Refer to the "Flue Liner Installation"
section.
4) Slide the unit half way into the replace.
5) Pull the vent connector plate through the tapered
brackets and fasten to the front plate. Refer to
the "Flue Liner Installation" section.
6) Slide the unit fully into the replace.
7) Install 4 AA batteries into receiver. Hook
receiver to wire marked receiver, this will enable
operation of the appliance manually when
position in "ON" position.
8) Test gas pressure, refer to the "Gas Pipe
Pressure Testing" section. Check aeration
system, refer to "Gas Insert Aeration System"
section.
9) Install standard and optional features. Refer
to the following sections where applicable:
a. Brick Panels
b. Log Installation
c. Faceplate
d. Standard Flush Door
e. Remote Control
10) Final check. Refer to the "Operating
Instructions" section. Before leaving this unit
with the customer, the installer must ensure that
the appliance is ring correctly. This includes:
a) Clocking the appliance to ensure the
correct ring rate.
b) Adjusting the primary air, if required, to
ensure that the ame does not carbon.
Refer to the "Gas Insert Aeration
System" section.
c) Ensuring that the appliance is venting
correctly.
MATERIALS
REQUIRED
No electrical power supply is required for the gas
control to operate. A 120 Volt AC power cord is
hooked up to the fan. Plug the 3 wire cord into
a suitable receptacle. Do not cut the ground
terminal o under any circumstances. When
connected with 120 volts, the appliance must be
electrically grounded in accordance with local
codes, or in the absence of local codes, with current
version of the Canadian Electrical Code CSA C22.1
(in Canada) or with the National Electrical Code
ANSI/NFPA 70.
NOTE: This unit is equipped with a heat sensor
thermodisc which will prevent the blower from
operating until the unit reaches the correct
temperature.
E33-10 FPI Direct Vent Gas Insert | 13
| 13
installation
GAS PRESSURE
TESTING
The appliance must be isolated from the gas sup-
ply piping system by closing its individual manual
shut off valve during any pressure testing of the
gas supply piping system at test pressures equal
to or less than 1/2 psig. (3.45 kPa).
INSTALLATION INTO A SOLID FUEL
BURNING FIREPLACE OR FACTORY
BUILT FIREPLACE
The E33 Gas Inserts have been tested and ap-
proved to be vented into any masonry fireplace or
approved solid fuel burning factory built fireplace that
will allow the insert to physically fit into the firebox.
Refer to "Minimum Fireplace Dimensions" section
for minimum fireplace clearances.
If the factory built replace* height is too low for
your Insert, you may remove the smoke bae
plate, damper, refractory (rebricks), glass doors,
screen rails, screen mesh and log grates from the
factory built replace as long as these items are
saved and are reinstalled in the event that the Insert
is removed. The replace ue damper can be fully
blocked open or removed for installation of the gas
replace insert.
Smoke shelves, shields and baes may be removed
if attached by mechanical fasteners. If any part is
removed it must not weaken the structural integrity
of the factory built replace.
The replace and replace chimney must be clean
and in good working order and constructed of non-
combustible materials.
The surround panels should not seal ventilation
openings on the replace.
Chimney clean outs should t properly.
NOTE: Any alterations made to the listed solid fuel
burning factory built replace may void the listing
of the replace.
Cutting any sheet metal part of the replace, in
which the gas replace insert is to be installed is
prohibited.
*Check with your local inspector before commencing
with this installation.
Installer must mechanically attach the supplied
label to the inside of the rebox of the replace into
which the gas replace insert is installed.
"WARNING: This replace has been converted
for use with a gas replace insert only and cannot
be used for burning wood or solid fuels unless all
original parts have been replaced, and the replace
re-approved by the authority having jurisdiction."
FACTORY-BUILT (METAL) WOOD-
BURNING FIREPLACE
REQUIREMENTS
NOTE: Any parts that are removed must be removed
in a way that would allow them to be re-installed if
the insert is ever removed (removal of rivets or
screws is acceptable).
To reference parts—see illustration below.
Must be removed:
1 -Damper
2- Grate (with log set)
May be removed (if applicable):
3- Smoke shelf
4- Internal baes
5 - Screen
6 & 7 - Masonry lining or refractory
8 - Metal or glass doors
The replace must be permanently marked to
indicate that it has been altered and is no longer
suitable for burning solid fuel (wood), unless the
removed parts are re-installed. Cutting of any sheet
metal parts is prohibited.
May be removed (in certain cases):
9 -Metal oor of the rebox
10 - The insulation and any structured rigid frame
members must not be removed or altered (side and
top of door frame, side and top of the face of the
replace, metal sides, etc.).
If the factory-built replace has no gas access
hole(s) provided, an access hole of 1.5 inch (37.5
mm) or less may be drilled through the lower sides
or bottom of the rebox in a proper workmanship
like manner. This access hole must be plugged
with non-combustible insulation after the gas
supply line has been installed.
CAUTION:
Firebox oor removal is not covered under the
appliance safety standard (ANSI Z21.88, CSA
2.33) used in the safety certication of this ap-
pliance. The Intertek safety certication does
not apply to this method of installation. Before
installing the appliance using this method, contact
the Authority Having Jurisdiction to determine if
this installation is acceptable in your area. The
sheet metal base of the replace must be left in
place and a minimum 1/2" cement board sheet
placed under the entire length and width of the
appliance.
14 | E33-10 FPI Direct Vent Gas Insert
|
14 installation
A
B
C
Max Lintel Bar Depth
A
Height
B
Depth
C
Width (Rear)
D
Width (Front)
E
Width
F
Front Depth
Prior to Taper
G
Low Prole Faceplate
with Spacer 8" 24 3/16" 16 3/4" 25" N/A 32 1/4" N/A
Low Prole Faceplate
without Spacer 9 1/4" 25 1/2" 18" 25" N/A 35 1/4" N/A
Vignette faceplate
with Spacer
9 1/2" 24" 16 3/4" 25" N/A 32 1/2" N/A
Vignette Faceplate
Without Spacer 12" 25 1/2" 19 1/8" 25" 34 5/8" 35 3/4" 2"
MINIMUM FIREPLACE OPENING
The minimum replace opening for the Regency gas replace insert is shown in the following diagram and the table:
E33-10 FPI Direct Vent Gas Insert | 15
| 15
installation
MINIMUM CLEARANCES TO COMBUSTIBLES
From Unit
Side Walls * A 8" (203 mm)
Ceiling B 47" (1194 mm)
Min. Mantel Height C 15" (381 mm)
Max. Mantel Depth D 12" (305 mm)
Alcove Width E 76" (1930 mm)
Alcove Depth F 36" (914 mm)
Hearth Height G 1-1/4" (32 mm)
Hearth Width H 45-1/2" (1156 mm)
Hearth Depth I 13" (330 mm)
* Alcove side wall must have a min. of 8"
clearance on one side.
* Measured from edge of glass frame.
COMBUSTIBLE MANTEL CLEARANCES
The minimum combustible mantel clearances from the top of the insert are shown in the following diagram:
Because of the extreme heat this replace emits, the mantel clear-
ances are critical.
Note: A non-combustible mantel may be installed at a lower height
if the framing is made of metal studs covered with a non-
combustible board.
Mantel can be installed anywhere in shaded area or higher using the
above scale.
Note: Ensure the paint that is used on the mantel and the facing is
"heat resistant" or the paint may discolour.
16 | E33-10 FPI Direct Vent Gas Insert
|
16 installation
GAS CONNECTION
1) If the appliance is to be installed into an existing
chimney system, thoroughly clean the masonry
or factory built replace.
2) The appliance is provided with an opening on
the left hand side of the control compartment.
A 3/8" NPT gas supply pipe must be brought
near this inlet hole.
3) Locate the center point where the vent will pass
through the chimney above the appliance. Move
the appliance into the exact location where it is
to be installed. Ensure that the Insert is level.
5) Install ashing.
6) Insert both liners into chimney, passing through
the damper opening.
7) Install termination cap.
8) Remove vent connector plate by removing
screw located on top/front of appliance.
9) Connect the marked end of the liner to the
exhaust collar of the vent connector plate
marked with an "E", seal connection with high
temperature silicone. Secure with 3 screws.
10) Connect the 2nd liner to the intake collar, seal
connection with high temperature silicone.
11) Align vent connector plate with guides on unit.
12) Slide unit into masonry opening, while ensuring
that the slot at the rear of the connector plate
mates up with the hold down plate on the unit.
13) Secure with Screw–removed from Step 8.
Secure with 3 screws.
NOTE:
1) Final gas connection should be made after
unit is in place to avoid damage to line when
pushing the unit into position.
2) Mill-pac may be used instead of high tempture
silicone and screws may be used instead of
gear clamps at connections of liner to inlet and
vent collars.
THE APPLIANCE MUST NOT BE
CONNECTED TO A CHIMNEY FLUE
SERVING A SEPARATE SOLID FUEL
BURNING APPLIANCE.
GAS CONNECTION
WARNING:
Only persons licensed to work
with gas piping may make the
necessary gas connections to
this appliance.
VENTING
This appliance is designed to be attached to two
3" (76mm) co-linear aluminium ex running the full
length of the chimney. The ue length must be a
minimum length of 8 ' (2.44m) and a maximum
of 35' (10.7m). See chart above for minimum
distances from roof. Periodically check that the
vent is unrestricted.
Masonry chimneys may take various contours
which the exible liner will accommodate. However,
keep the exible liner as straight as possible,
avoid unnecessary bending.
Part # Description
948-305 3" Flex - 35 ft.
946-529 Regency Co-linear DV Vertical
Termination Cap
Alternate Approved Caps
46dva-VC Vertical Termination Cap
46dva-VCH High Wind Cap
46dva-GK 3" Co-linear Adaptor with ashing
In areas of consistently high winds, we recommend
using the Simpson Dura-Vent System (46dva-GK
adapter and 46dva-VCH high-wind cap).
The Air Intake pipe must be attached to the inlet air
collar of the termination cap.
FLUE LINER
INSTALLATION
1) Cut the ex liner as required.
2) Mark the end of one liner with an "E" to
indicate Exhaust.
3) Connect the other end of the above liner to
the exhaust side of the termination adaptor,
seal connection with high temperature silicone.
Secure with 3 screws.
4) Connect the 2nd liner to the inlet side of the
adaptor, seal connection with high temperature
silicone. Secure with 3 screws.
E33-10 FPI Direct Vent Gas Insert | 17
| 17
installation
GAS PIPE
PRESSURE TESTING
The appliance must be isolated from the gas supply
piping system by closing its individual manual shut-
o valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 1/2 psig. (3.45 kPa). Disconnect piping
from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
NOTE: To properly check gas pressure, both
inlet and manifold pressures should be
checked using the valve pressure ports
on the valve.
1) Make sure the valve is in the "OFF" position.
2) Loosen the "IN" and/or "OUT" pressure tap(s),
turning counterclockwise with a 1/8" wide at
screwdriver.
3) Attach manometer to "IN" and/or "OUT"
pressure tap(s) using a 5/16" ID hose.
4) Light the pilot and turn the valve to "ON" position.
5) The pressure check should be carried out with
the unit burning and the setting should be within
the limits specied on the safety label.
6) When nished reading manometer, turn o the
gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" at screwdriver.
Note: Screw should be snug, but do not
over tighten.
SIT 829 VALVE DESCRIPTION
1) Gas on/o knob
2) Electronically Operated Hi/Lo
3) Pilot Adjustment
4) Thermocouple Connection - option
5) Outlet Pressure Tap
6) Inlet Pressure Tap
7) Pilot Outlet
8) Main Gas Outlet
9) Alternative TC Connection Point
REMOTE RECEIVER INSTALLATION
1) Install the heat shield to the receiver with two screws.
2) Attach to the oor of the unit with a velcro pad. Locate the
receiver at the far right hand side of unit as shown below.
3) See Remote Control installation instructions for information on
coding the handheld transmitter to the receiver
Install the supplied battery into the DC Sparker Box
by opening the battery compartment.
NOTE: The battery in the DC Sparker Box will
need to be replaced annually.
DC SPARK IGNITER BATTERY
INSTALLATION
GAS INSERT
AERATION SYSTEM
The air shutter can be adjusted by moving the
adjusting wire up or down. The wire is accessed
through the bottom louver opening. Open the air
shutter for a blue ame or close for a yellower
ame. The burner aeration is factory set but may
need adjusting due to either the local gas supply
or altitude.
Minimum Air Shutter Opening:
5/16" Natural Gas
7/16" Propane
CAUTION: Carbon will be produced if air
shutter is closed too much.
Note: Any damage due to carboning resulting
from improperly setting the aeration
controls is NOT covered under warranty.
Note: Aeration Adjustment should only be
performed by an authorized Regency
Installer at the time of installation.
18 | E33-10 FPI Direct Vent Gas Insert
|
18 installation
Diagram 1
BRICK PANEL INSTALLATION
1) Remove safety screen and glass door if
installed.
2) Remove the logs if they are already installed.
Note: the grate must be removed in order to
remove the bottom log. Ensure you slide the
bottom coal o to the right-hand side to avoid
chipping.
3) Unwrap the brick pattern panels from the
protective wrapping. Handle the panels with
care as they can break easily.
Bottom Clips
Top Bracket
5) Place the top bracket onto the top edge of
the top panel (refer to Diagram 2).
Diagram 2
6) Slide the top panel and bracket assembly
carefully onto the bae plate ensuring the
panel is centered. Make sure the tabs of the
top bracket t into the bae openings (refer to
Diagram 3).
7) Insert the back panel by sliding it between the
sidewalls of the rebox and the rear log support.
Diagram 3
8) Before installing the side brick panels, remove
the screws from the side brick clips (refer to
Diagram 4).
Diagram 4
9) Insert the side panel by positioning it at against
the side walls. Tilt the panel
towards the middle of the rebox, then insert
the bottom front corner. Repeat on the other
side.
10) Install the 2 brick retaining clips, one on each
side.
Completed Installation
4) Remove the two screws from the bottom of
the bae plate. Install the bottom clips onto
the bae plate (refer to Diagram 1).
OPTIONAL
BRICK PANEL
Optional Brick Panel Set:
Part # Description Qty
Top (brick) panel 1
Back (brick) panel 1
Left (brick) panel 1
Right (brick)panel 1
340-043 Top bracket 1
340-094 Bottom clips 2
511-031 Brick clips 2
E33-10 FPI Direct Vent Gas Insert | 19
| 19
installation
DIRECT VENT FIREPLACE
E33
918-416a 12/18/07
LOG INSTALLATION
Gas Log Kit #340-930 contains the following:
03-17 Bottom Log
03-18 Center Top Log
03-19 Front Log
03-20 Left Log
03-21 Right Log
03-22 Left top Log
03-23 Rear Log
03-24 Right Top Log
946-669 Platinum Embers (supplied in packaged manual)
WARNING:
Dangerous operating conditions may occur if these
logs are not positioned in their correct certifi ed loca-
tions. Read the following instructions carefully and
refer to the attached diagrams.
1) Remove and carefully unwrap the logs from the
box. Please handle with care and do not force
them into position to avoid chipping.
3) Remove the grate by removing the two Phillips
screws. Slide the grate outwards to remove it from
the unit (refer to Diagram 1).
Diagram 1
2) Remove the safety screen and glass door if al-
ready installed.
Page 1 of 3
4) Angle log 03-17 and slide it between the top and
bottom burner tube under the "T" section until it
touches the left grate support bracket (refer to
Diagram 2).
5) Re-install the grate.
Diagram 2
03-17
03-17
03-20
03-23
03-21
03-22 03-24
03-18
03-19
The "03" reference numbers (i.e. 03-23) are molded
into the rear of each log.
6) Line up the pin holes (located at the bottom of log
03-23) to the pins of the rear log support and posi-
tion them into place. (refer to Diagram 3)
Diagram 3
Locating Pins
03-23
LOG SET INSTALLATION
20 | E33-10 FPI Direct Vent Gas Insert
|
20 installation
DIRECT VENT FIREPLACE
E33
918-416a 11.05.14
Page 2 of 3
7) Align the bottom grooves of log 03-21 onto the
right side of the grate and gently slide the log back
until it touches the locating tab (refer to Diagram 4
& 5).
Diagram 4
Locating
Tab
03-23
03-17 03-21
Diagram 5
8) Align and position the pin hole of log 03-20 down
into the left locating pin of log 03-21. Slide into
the groove and gently place into position until it
touches the locating tab. (see Diagram 6 & 7)
Locating
Tab
03-20
Locating
Pin
Diagram 6
Diagram 7
03-23
03-20
03-17
03-21
9) Place log 03-22 over log 03-23 and log 03-20.
Ensure the pin hole of log 03-22 lines up with the
left pin of log 03-23 as well as the left pin of log
03-20 (refer to Diagram 8).
03-22
Locating
Pins
03-23
03-20
Diagram 8
10) Place log 03-18 over log 03-23 and log 03-20.
Ensure the pin hole of log 03-18 lines up with the
middle pin of log 03-23 and the right pin of log
03-20 (refer to Diagram 9 & 10).
03-20
03-18
03-23
Locating
Pins
Diagram 9
03-21
03-21
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48

Regency Energy E33-LP10 Owners & Installation Manual

Category
Fireplaces
Type
Owners & Installation Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI