Samsung AM260HXVAHH Installation guide

Category
Power heat guns
Type
Installation guide
DVM S
AMFXVAHH Series
AMHXVAHH Series
AMJXVGHH Series
AMKXVGHH Series
Air Conditioner
installation manual
imagine the possibilities
Thank you for purchasing this Samsung
product.
DB68-03938A-08
EN ES PT
DVM S Philip OU_IM_03938A-08_EN.indd 1 2016-09-19 오후 1:48:53
2
Contents
Safety precautions ....................................................................................................... 3
Preparing for installation ................................................................................................. 8
Selecting installation location ........................................................................................... 25
Space requirement for installation ...................................................................................... 27
Accessories ............................................................................................................. 29
Base construction and installation of the outdoor unit ................................................................... 30
Installing the wind/snow prevention duct ............................................................................... 35
Refrigerant pipe installation ............................................................................................. 37
Electrical wiring work ................................................................................................... 61
Air tightness test and vacuum drying ................................................................................... 76
Pipe insulation .......................................................................................................... 78
Charging additional refrigerant ......................................................................................... 82
Basic segment display .................................................................................................. 84
Setting outdoor unit option switch and key function .................................................................... 84
Things to check after completing the installation ........................................................................ 94
Inspection and test operation ........................................................................................... 96
Automatic refrigerant amount detection function ...................................................................... 100
DVM S Philip OU_IM_03938A-08_EN.indd 2 2016-09-19 오후 1:48:53
3
ENGLISH
Safety precautions
Please follow the following safety information for safety of the installer and the user.
DVM S air conditioner uses R-410A refrigerant.
• When using R-410A, moisture or foreign substances may aect the performance and reliability of the product.
Safety precautions must be obeyed when installing the refrigerant pipe.
• The designed maximum pressure of the system is 4.1MPa and therefore select appropriate material and thickness
according to the regulations.
• R-410A is a quasi-azeotrope of two refrigerants and it has to be charged in liquid phase when lling the refrigerant.
(If you charge vapor refrigerant, it may change the blend of the refrigerant and cause product malfunction.)
You must connect the indoor units for R-410A refrigerant. Refer to product catalog to nd out the models names
for connectable indoor units. (If you connect the indoor units that are not designed for R-410A, it cannot operated
normally.)
After completing the installation and trial operation, explain to the user how to use and maintain the product. Also, hand
over this installation manual so that it can be stored by the user.
Manufacturer is not responsible for the incidents occurred by improper installation. Installer is responsible for any
installation related claims from the user occurred by neglecting warnings and cautions stated in this manual. (Installer
will be responsible for any service charges that may occur)
Generally, system air conditioners should not be relocated after installation. But when it has to be relocated for inevitable
reasons, please contact Samsung’s qualied dealers for system air conditioners.
WARNING
• Hazards or unsafe practices that may result in severe personal injury or death.
CAUTION
• Hazards or unsafe practices that may result in minor personal injury (to installer/user) or
property damage.
DVM S Philip OU_IM_03938A-08_EN.indd 3 2016-09-19 오후 1:48:53
4
Safety precautions
SEVERE WARNING SIGNS
Consult qualied installer or dealer for installation.
When installation is done by unqualied person, problems such as water leakage, electric shock or re may occur.
Installation work must be done properly according to this installation manual.
When installation is not done properly, it may cause water leakage, electric shock or re.
When installing the unit in a small room, take measure to keep the refrigerant concentration from exceeding allowable
safety limits in case of refrigerant leakage. Consult the dealer for precautionary measure before the installation.
When refrigerant leaks and exceed dangerous concentration level, it may cause suocation accidents.
If any gas or impurities, except R-410A refrigerant, come into the refrigerant pipe, serious problem may occur and it
may cause injury.
Use the supplied accessories, specied components and tools for the installation.
Do not use the pipe and the installation product used for the R-22 refrigerant.
Failure to use the specied components can cause product fall down, water leakage, electrical shock, and re. (The pipe
and are components used for R-22 refrigerant must not be used)
Install the outdoor unit on a hard and even place that can support its weight.
If the place cannot support its weight, the outdoor unit may fall down and it may cause injury.
Check the following before installation and service work.
Before welding, remove dangerous and inammable things that may cause an explosion and re around the work.
Before welding, remove the refrigerant from inside the pipe or the product.
- If you perform welding while refrigerant is in the pipe, it may increase the pressure of the refrigerant and cause the pipe
to burst. If the pipe bursts or explodes, it may cause severe injury to the installer.
When welding, use the nitrogen gas to eliminate oxidation inside the pipe.
Do not modify the product on your own.
Potential risk of electric shock, re, product failure or injury.
Fix the outdoor unit securely on foundation to resist strong wind or earthquake.
If the outdoor unit is not properly xed, it turns over and accidents may occur.
Electric work must be done by qualied persons, complying the national wiring regulations and installed according to
the instruction stated in the installation manual with leased circuit.
Capacity shortage on the leased circuit and improper installation may cause electric shock or re.
Make sure to perform grounding work.
Do not connect the ground wire to a gas pipe, water pipe, lightning rod or telephone grounding. Improper grounding
could cause electric shock.
DVM S Philip OU_IM_03938A-08_EN.indd 4 2016-09-19 오후 1:48:53
5
ENGLISH
Wiring must be connected with the designated wires and it must be xed securely so that it does not apply any external
force to the connection part of the terminals.
If connection for xation is not properly done, it may cause heat generation or re.
Neatly arrange the wires in the electrical parts to make sure that electrical cover is closed securely without any gaps.
If the cover is not properly closed, heat may generate on the electrical terminal and cause electric shock or re.
Exclusive circuit breaker (MCCB, ELB) must be installed to the power supply.
When overcurrent or current leakage occurs with no circuit breaker installed, power will not be cut-o and it may cause
electric shock or re.
Do not use damaged parts. It may cause re or electric shock.
You must cut-o the power before you work on, or adjust any power supply part for product installation, maintenance,
repair or any other services.
There is risk of electric shock.
Even when the power is o, it is dangerous when you come in contact with inverter PCB, fan PCB since high pressure DC
voltage is charged to those parts.
When replacing/repairing the PCB, cut-o the power and wait until the DC voltage is discharged before replacing/
repairing them. (Wait for more than 15 minutes to allow it to discharge naturally.)
If the refrigerant gas leaks during the installation, you should ventilate the room.
When the refrigerant gas gets in contact with ammable substance, it may generate toxic gas.
Gas leakage must be checked after installation is completed.
When the refrigerant gas gets in contact with ammable substance, it may generate toxic gas.
You can get a frostbite if you get in contact with the leaked refrigerant gas.
Supply power to the product during winter time since the product will operate in protection mode itself when the
temperature decrease below 0°C(32°F).
If you cut-o the power, compressor protection mode cannot be operated and may cause damage to the product.
DVM S Philip OU_IM_03938A-08_EN.indd 5 2016-09-19 오후 1:48:53
6
Safety precautions
CAUTION SIGNS
Do not install the drain pipe directly to the bottom part of the outdoor unit and built a proper drainage so that water
drains out smoothly. If not, pipe may freeze or bursts during winter time and cause damage to the product or water
leakage.
When the draining work is not done properly, water leak may occur and cause property damage.
Install the power cable and communication cable of the indoor and outdoor unit at least 1.5m (4.92ft) away from the
electric appliances and install it at least 2m(6.56ft) away from the lightning conductor.
Noise may be generated from the electronic devices, depending on the status of the electric wave.
Install the outdoor unit within the angle stated in the table, according to the height of the building.
Do not leave the refrigerant container under the hot sunlight. (There is risk of explosion.)
You must use the appropriate pipes according to the standard since the pressure of the refrigerant is very high.
Make sure that the pipes does not get any weaker by welding it too much.
Make sure to install the product away from childrens’ reach. (Sharp parts of the heat exchanger is may cause personal
injury and when parts of the product gets damage, it may decrease product’s performance.)
Lighting rod
Protective angle: 25˚~55˚
Height of the building Protection control
20m(65.62ft) or less 55˚
40m(131.23ft) or less 35˚
60m(196.85ft) or less 25˚
Install the indoor unit away from lighting apparatus that uses ballast stabilizer.
If you use the wireless remote control, it may not operate normally due to ballast stabilizer.
DVM S Philip OU_IM_03938A-08_EN.indd 6 2016-09-19 오후 1:48:53
7
ENGLISH
Do not install the product in following places.
Place where outdoor unit’s noise and warm air may disturb neighbors. (It may cause property loss.)
Do not leave any obstacles around the inlet and outlet of the product. (It may cause damage or accidents.)
The place where there is mineral oil or arsenic acid.
- Those parts may get damaged due to burned resin and cause water leakage or product may fall.
- The eciency of the heat exchanger may reduce or product may break.
The place where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outlet.
- The copper pipe or connection pipe may corrode and refrigerant may leak.
The place where there is a machine that generates electromagnetic waves.
- The air conditioner may not operate normally due to problems in control system.
The place where there is a danger of combustible gas leakage or place where thinner or gasoline is handled.
- (There is risk of re or explosion.)
The place with carbon ber or ammable dust.
The place near seashore or hot spring where there is risk of outdoor unit corrosion.
Changes in DVM S (inverter) compare to conventional models that has to noted when installing
For optimal distribution of the refrigerant, you must use Y-joint as branch joint for connecting outdoor units. (To not use
T-joint)
You cannot operate normally if you do not complete the trial operation through outdoor unit key mode. You must use
KEY MODE to run trial operation.
DVM S air conditioner uses R-410A refrigerant.
Check the compatibility of other products such as indoor unit, EEV kits etc. which will be connected to DVM S.
Make sure to note that outdoor unit combination is dierent from DVM PLUS III and IV.
The length of maximum piping, level dierence, the quantity of connectable indoor units, the installation at the outdoor
joints and the outdoor unit combinations are dierent from the conventional models.
If the pipe length is over 2m(6.56ft) between outdoor units, make traps to prevent oil stagnation. Oil stagnation may
occur when outdoor unit at the end of module stops while other outdoor units are still in operation.
DVM S Philip OU_IM_03938A-08_EN.indd 7 2016-09-19 오후 1:48:53
8
Preparing for installation
Outdoor unit classication
Classication Small type Large type
Appearance
Models AM080/100/120XVH AM140/160/180/200/220/240/260XVH
Packaging material disposition
• Safely store or dispose the packaging materials.
- Sharp metals such as nails or wooden material packaging that may break into pieces become a cause for
personal injury.
- Make sure to store or dispose the vinyl type packaging material to keep it out of reach of children. Children
may put them over their face, which is very dangerous since it may lead them to suocation.
CAUTION
Outdoor unit combination
Make sure to use an indoor unit that is compatible with DVM S.
Indoor units can be connected within the range indicated in following table.
If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating capacity
of the indoor unit may decrease.
Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity. 0.5 ×
Σ(Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ(Outdoor unit capacity)
You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is set to 64
since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned from 0~63. If the
indoor unit address was assigned from 64~79, E201 error will occur.
Maximum 32 Wall-mount type indoor units with EEV (AMNQDCH) can be connected.
• Installation combination must be complied when composing outdoor unit combination.
CAUTION
DVM S Philip OU_IM_03938A-08_EN.indd 8 2016-09-19 오후 1:48:54
9
ENGLISH
Standard type
Model name for combination AM080FXVAHH AM100FXVAHH AM120FXVAHH AM140FXVAHH AM160FXVAHH
Number of individual outdoor units 1 1 1 1 1
Combined outdoor unit
AM080FXVAHH 1
AM100FXVAHH 1
AM120FXVAHH 1
AM140FXVAHH 1
AM160FXVAHH 1
AM180FXVAHH
AM200FXVAHH
AM220FXVAHH
AM240HXVAHH
AM260HXVAHH
Rated capacity
Cooling (kW) 22.4 28.0 33.6 40.0 45.0
Cooling (Btu/h) 76 400 95 500 114 600 136 500 153 500
Heating (kW) 25.2 31.5 37.8 45.0 50.0
Heating (Btu/h) 86 000 107 500 129 000 153 500 170 600
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 11.2 14.0 16.8 20.0 22.5
Minimum (Btu/h) 38 200 47 800 57 300 68 200 76 800
Maximum (kW) 29.1 36.4 43.7 52.0 58.5
Maximum (Btu/h) 99 400 124 200 149 000 177 400 199 600
Maximum number of connectable indoor
units
14 18 21 26 29
Model name for combination AM180FXVAHH AM200FXVAHH AM220FXVAHH AM240HXVAHH AM260HXVAHH
Number of individual outdoor units 1 1 1 1 1
Combined outdoor unit
AM080FXVAHH
AM100FXVAHH
AM120FXVAHH
AM140FXVAHH
AM160FXVAHH
AM180FXVAHH 1
AM200FXVAHH 1
AM220FXVAHH 1
AM240HXVAHH 1
AM260HXVAHH 1
Rated capacity
Cooling (kW) 50.4 56.0 61.6 67.2 72.8
Cooling (Btu/h) 172 000 191 100 210 200 229 300 248 400
Heating (kW) 56.7 63.0 69.3 75.6 81.9
Heating (Btu/h) 193 500 215 000 236 500 258 000 279 500
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 25.2 28.0 30.8 33.6 36.4
Minimum (Btu/h) 86 000 95 500 105 100 114 600 124 200
Maximum (kW) 65.5 72.8 80.1 87.4 94.6
Maximum (Btu/h) 223 600 248 400 273 200 298 100 322 900
Maximum number of connectable indoor
units
32 36 40 43 47
DVM S Philip OU_IM_03938A-08_EN.indd 9 2016-09-19 오후 1:48:54
10
Preparing for installation
Model name for combination AM280HXVAHH1 AM300HXVAHH1 AM320HXVAHH1 AM340HXVAHH1 AM360HXVAHH1
Number of individual outdoor units 2 2 2 2 2
Combined outdoor unit
AM080FXVAHH
AM100FXVAHH
AM120FXVAHH 1 1 1 1
AM140FXVAHH 1
AM160FXVAHH 1
AM180FXVAHH 1
AM200FXVAHH 1
AM220FXVAHH 1 1
AM240HXVAHH
AM260HXVAHH
Rated capacity
Cooling (kW) 78.6 84.0 89.6 95.2 101.6
Cooling (Btu/h) 268 200 286 600 305 700 324 800 346 700
Heating (kW) 87.8 94.5 100.8 107.1 114.3
Heating (Btu/h) 299 600 322 400 343 900 365 400 390 000
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 39.3 42.0 44.8 47.6 50.8
Minimum (Btu/h) 134 100 143 300 152 900 162 400 173 300
Maximum (kW) 102.2 109.2 116.5 123.8 132.1
Maximum (Btu/h) 348 700 372 600 397 400 422 300 450 700
Maximum number of connectable indoor
units
51 54 58 61 64
Model name for combination AM380HXVAHH1 AM400HXVAHH1 AM420HXVAHH1 AM440HXVAHH1 AM460HXVAHH1
Number of individual outdoor units 2 2 2 2 3
Combined outdoor unit
AM080FXVAHH
AM100FXVAHH
AM120FXVAHH 2
AM140FXVAHH 1
AM160FXVAHH 1
AM180FXVAHH
AM200FXVAHH 1
AM220FXVAHH 1 1 2 1
AM240HXVAHH
AM260HXVAHH 1
Rated capacity
Cooling (kW) 106.6 112.8 117.6 123.2 128.8
Cooling (Btu/h) 363 700 384 900 401 300 420 400 439 500
Heating (kW) 119.3 126.9 132.3 138.6 144.9
Heating (Btu/h) 407 100 433 000 451 400 472 900 494 400
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 53.3 56.4 58.8 61.6 64.4
Minimum (Btu/h) 181 900 192 400 200 600 210 200 219 700
Maximum (kW) 138.6 146.6 152.9 160.2 167.4
Maximum (Btu/h) 472 900 500 400 521 600 546 500 571 300
Maximum number of connectable indoor
units
64 64 64 64 64
DVM S Philip OU_IM_03938A-08_EN.indd 10 2016-09-19 오후 1:48:54
11
ENGLISH
Model name for combination AM480HXVAHH1 AM500HXVAHH1 AM520HXVAHH1 AM540HXVAHH1 AM560HXVAHH1
Number of individual outdoor units 3 3 3 3 3
Combined outdoor unit
AM080FXVAHH
AM100FXVAHH
AM120FXVAHH 1 1 1 1 1
AM140FXVAHH 1
AM160FXVAHH 1
AM180FXVAHH 1
AM200FXVAHH 1
AM220FXVAHH 1 1 1 1 2
AM240HXVAHH
AM260HXVAHH
Rated capacity
Cooling (kW) 135.2 140.2 145.6 151.2 156.8
Cooling (Btu/h) 461 300 478 400 496 800 515 900 535 000
Heating (kW) 152.1 157.1 163.8 170.1 176.4
Heating (Btu/h) 519 000 536 000 558 900 580 400 601 900
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 67.6 70.1 72.8 75.6 78.4
Minimum (Btu/h) 230 700 239 200 248 400 258 000 267 500
Maximum (kW) 175.8 182.3 189.3 196.6 203.8
Maximum (Btu/h) 599 700 621 900 645 800 670 700 695 500
Maximum number of connectable indoor
units
64 64 64 64 64
Model name for combination
AM580HXVAHH1 AM600HXVAHH1 AM620HXVAHH1 AM640HXVAHH1 AM660HXVAHH1 AM680HXVAHH1
Number of individual outdoor units 3 3 3 3 3 4
Combined outdoor unit
AM080FXVAHH
AM100FXVAHH
AM120FXVAHH 2
AM140FXVAHH 1
AM160FXVAHH 1
AM180FXVAHH 1
AM200FXVAHH 1
AM220FXVAHH 2 2 2 2 3 2
AM240HXVAHH
AM260HXVAHH
Rated capacity
Cooling (kW) 163.2 168.2 173.6 179.2 184.8 190.4
Cooling (Btu/h) 556 900 573 900 592 300 611 500 630 600 649 700
Heating (kW) 183.6 188.6 195.3 201.6 207.9 214.2
Heating (Btu/h) 626 500 643 500 666 400 687 900 709 400 730 900
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 81.6 84.1 86.8 89.6 92.4 95.2
Minimum (Btu/h) 278 400 287 000 296 200 305 700 315 300 324 800
Maximum (kW) 212.2 218.7 225.7 233.0 240.2 247.5
Maximum (Btu/h) 723 900 746 100 770 100 794 900 819 700 844 600
Maximum number of connectable indoor
units
64 64 64 64 64 64
DVM S Philip OU_IM_03938A-08_EN.indd 11 2016-09-19 오후 1:48:54
12
Model name for combination
AM700HXVAHH1 AM720HXVAHH1 AM740HXVAHH1 AM760HXVAHH1 AM780HXVAHH1 AM800HXVAHH1
Number of individual outdoor units 4 4 4 4 4 4
Combined outdoor unit
AM080FXVAHH
AM100FXVAHH
AM120FXVAHH 1 1 1 1 1
AM140FXVAHH 1 1
AM160FXVAHH 1
AM180FXVAHH 1
AM200FXVAHH 1
AM220FXVAHH 2 2 2 2 3 3
AM240HXVAHH
AM260HXVAHH
Rated capacity
Cooling (kW) 196.8 201.8 207.2 212.8 218.4 224.8
Cooling (Btu/h) 671 500 688 600 707 000 726 100 745 200 767 000
Heating (kW) 221.4 226.4 233.1 239.4 245.7 252.9
Heating (Btu/h) 755 400 772 500 795 400 816 900 838 400 862 900
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 98.4 100.9 103.6 106.4 109.2 112.4
Minimum (Btu/h) 335 800 344 300 353 500 363 100 372 600 383 500
Maximum (kW) 255.8 262.3 269.4 276.6 283.9 292.2
Maximum (Btu/h) 873 000 895 100 919 100 943 900 968 800 997 200
Maximum number of connectable indoor
units
64 64 64 64 64 64
Preparing for installation
DVM S Philip OU_IM_03938A-08_EN.indd 12 2016-09-19 오후 1:48:54
13
ENGLISH
Compact type
Model name for combination AM360HXVAHH2 AM380HXVAHH2 AM460HXVAHH2 AM480HXVAHH2
Number of individual outdoor units 2 2 2 2
Combined outdoor unit
AM120FXVAHH 1 1
AM200FXVAHH 1
AM220FXVAHH 1
AM240HXVAHH 1
AM260HXVAHH 1 1 1
Rated capacity
Cooling (kW) 100.8 106.4 128.8 134.4
Cooling (Btu/h) 343 900 363 100 439 500 458 600
Heating (kW) 113.4 119.7 144.9 151.2
Heating (Btu/h) 386 900 408 400 494 400 515 900
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 50.4 53.2 64.4 67.2
Minimum (Btu/h) 172 000 181 500 219 700 229 300
Maximum (kW) 131.0 138.3 167.4 174.7
Maximum (Btu/h) 447 100 472 000 571 300 596 100
Maximum number of connectable indoor units 64 64 64 64
Model name for combination AM500HXVAHH2 AM520HXVAHH2 AM580HXVAHH2 AM600HXVAHH2
Number of individual outdoor units 2 2 3 3
Combined outdoor unit
AM120FXVAHH 1 1
AM200FXVAHH 1
AM220FXVAHH 1
AM240HXVAHH 1
AM260HXVAHH 1 2 1 1
Rated capacity
Cooling (kW) 140.0 145.6
162.4
168.0
Cooling (Btu/h) 477 700 496 800
554 100
573 200
Heating (kW) 157.5 163.8
182.7
189.0
Heating (Btu/h) 537 400 558 900
623 400
644 900
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW) 70.0 72.8
81.2
84.0
Minimum (Btu/h) 238 800 248 400
277 100
286 600
Maximum (kW) 182.0 189.3 211.1 218.4
Maximum (Btu/h) 621 000 645 800 720 400 745 200
Maximum number of connectable indoor units 64 64 64 64
DVM S Philip OU_IM_03938A-08_EN.indd 13 2016-09-19 오후 1:48:55
14
Model name for combination AM620HXVAHH2 AM640HXVAHH2 AM680HXVAHH2 AM700HXVAHH2
Number of individual outdoor units 3 3 3 3
Combined outdoor unit
AM120FXVAHH
1 1
AM200FXVAHH
AM220FXVAHH 2 2
AM240HXVAHH 1
1
AM260HXVAHH 1 2 1
Rated capacity
Cooling (kW)
173.6 179.2 190.4 196.0
Cooling (Btu/h)
592 300 611 500 649 700 668 800
Heating (kW)
195.3 201.6 214.2 220.5
Heating (Btu/h)
666 400 687 900 730 900 752 400
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW)
86.8 89.6 95.2 98.0
Minimum (Btu/h)
296 200 305 700 324 800 334 400
Maximum (kW)
225.7 233.0 247.5 254.8
Maximum (Btu/h)
770 100 794 900 844 600 869 400
Maximum number of connectable indoor units 64 64 64 64
Model name for combination AM720HXVAHH2 AM740HXVAHH2 AM760HXVAHH2 AM780HXVAHH2
Number of individual outdoor units 3 3 3 3
Combined outdoor unit
AM120FXVAHH
AM200FXVAHH
AM220FXVAHH 1 1
AM240HXVAHH 1
1
AM260HXVAHH 1 2 2 3
Rated capacity
Cooling (kW)
201.6 207.2 212.8 218.4
Cooling (Btu/h)
687 900 707 000 726 100 745 200
Heating (kW)
226.8 233.1 239.4 245.7
Heating (Btu/h)
773 900 795 400 816 900 838 400
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW)
100.8 103.6 106.4 109.2
Minimum (Btu/h)
343 900 353 500 363 100 372 600
Maximum (kW)
262.1 269.4 276.6 283.9
Maximum (Btu/h)
894 300 919 100 943 900 968 800
Maximum number of connectable indoor units 64 64 64 64
Preparing for installation
DVM S Philip OU_IM_03938A-08_EN.indd 14 2016-09-19 오후 1:48:55
15
ENGLISH
High Eciency type (Heat pump)
Model name for combination AM080JXVGHH AM100JXVGHH AM120JXVGHH AM140FXVAHH AM160JXVGHH
Number of individual outdoor units 1 1 1 1 1
Combined outdoor unit
AM080JXVGHH
1
AM100JXVGHH 1
AM120JXVGHH
1
AM140FXVAHH
1
AM160JXVGHH
1
AM180JXVGHH
AM200JXVGHH
Rated capacity
Cooling (kW)
22.4 28.0 33.6 40.0 45.0
Cooling (Btu/h)
76 400 95 500 114 600 136 500 153 500
Heating (kW)
25.2 31.5 37.8 45.0 50.0
Heating (Btu/h)
86 000 107 500 129 000 153 500 170 600
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW)
11.2 14.0 16.8 20.0 22.5
Minimum (Btu/h)
38 200 47 800 57 300 68 200 76 800
Maximum (kW)
29.1 36.4 43.7 52.0 58.5
Maximum (Btu/h)
99 400 124 200 149 000 177 400 199 600
Maximum number of connectable indoor units
14 18 21 26 29
Model name for combination AM180JXVGHH AM200JXVGHH AM220JXVGHH AM240JXVGHH AM260JXVGHH
Number of individual outdoor units 1 1 2 2 2
Combined outdoor unit
AM080JXVGHH
AM100JXVGHH 1
AM120JXVGHH
1
2
1
AM140FXVAHH
1
AM160JXVGHH
AM180JXVGHH
1
AM200JXVGHH 1
Rated capacity
Cooling (kW)
50.4 56.0 61.6 67.2 73.6
Cooling (Btu/h)
172 000 191 100 210 200 229 300 251 100
Heating (kW)
56.7 63.0 69.3 75.6 82.8
Heating (Btu/h)
193 500 215 000 236 500 258 000 282 500
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW)
25.2 28.0 30.8 33.6 36.8
Minimum (Btu/h)
86 000 95 500 105 100 114 600 125 600
Maximum (kW)
65.5 72.8 80.1 87.4 95.7
Maximum (Btu/h)
223 600 248 400 273 200 298 100 326 500
Maximum number of connectable indoor units
32 36 40 43 47
DVM S Philip OU_IM_03938A-08_EN.indd 15 2016-09-19 오후 1:48:55
16
Preparing for installation
Model name for combination AM280JXVGHH AM300JXVGHH AM320JXVGHH AM340JXVGHH AM360JXVGHH
Number of individual outdoor units 2 2 2 2 2
Combined outdoor unit
AM080JXVGHH
AM100JXVGHH
AM120JXVGHH
1 1 1
AM140FXVAHH
1
AM160JXVGHH
1 1
AM180JXVGHH
1
AM200JXVGHH 1 1 1
Rated capacity
Cooling (kW)
78.6 84.0 89.6 96.0 101.0
Cooling (Btu/h)
268 200 286 600 305 700 327 600 344 600
Heating (kW)
87.8 94.5 100.8 108.0 113.0
Heating (Btu/h)
299 600 322 400 343 900 368 500 385 600
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW)
39.3 42.0 44.8 48.0 50.5
Minimum (Btu/h)
134 100 143 300 152 900 163 800 172 300
Maximum (kW)
102.2 109.2 116.5 124.8 131.3
Maximum (Btu/h)
348 700 372 600 397 400 425 800 448 000
Maximum number of connectable indoor units
51 54 58 61 64
Model name for combination AM380JXVGHH AM400JXVGHH AM420JXVGHH AM440JXVGHH AM460JXVGHH
Number of individual outdoor units 2 2 3 3 3
Combined outdoor unit
AM080JXVGHH
AM100JXVGHH
1
AM120JXVGHH
1 2 1
AM140FXVAHH
1
AM160JXVGHH
AM180JXVGHH
1
AM200JXVGHH 1 2 1 1 1
Rated capacity
Cooling (kW)
106.4 112.0 117.6 123.2 129.6
Cooling (Btu/h)
363 100 382 200 401 300 420 400 442 200
Heating (kW)
119.7 126.0 132.3 138.6 145.8
Heating (Btu/h)
408 400 429 900 451 400 472 900 497 500
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW)
53.2 56.0 58.8 61.6 64.8
Minimum (Btu/h)
181 500 191 100 200 600 210 200 221 100
Maximum (kW)
138.3 145.6 152.9 160.2 168.5
Maximum (Btu/h)
472 000 496 800 521 600 546 500 574 900
Maximum number of connectable indoor units
64 64 64 64 64
DVM S Philip OU_IM_03938A-08_EN.indd 16 2016-09-19 오후 1:48:55
17
ENGLISH
Model name for combination AM480JXVGHH AM500JXVGHH AM520JXVGHH AM540JXVGHH AM560JXVGHH
Number of individual outdoor units 3 3 3 3 3
Combined outdoor unit
AM080JXVGHH
AM100JXVGHH
AM120JXVGHH
1 1 1
AM140FXVAHH
1
AM160JXVGHH
1 1
AM180JXVGHH
1
AM200JXVGHH 1 1 2 2 2
Rated capacity
Cooling (kW)
134.6 140.0 145.6 152.0 157.0
Cooling (Btu/h)
459 300 477 700 496 800 518 600 535 700
Heating (kW)
150.8 157.5 163.8 171.0 176.0
Heating (Btu/h)
514 600 537 400 558 900 583 500 600 500
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW)
67.3 70.0 72.8 76.0 78.5
Minimum (Btu/h)
229 600 238 800 248 400 259 300 267 900
Maximum (kW)
175.0 182.0 189.3 197.6 204.1
Maximum (Btu/h)
597 100 621 000 645 800 674 200 696 400
Maximum number of connectable indoor units
64 64 64 64 64
Model name for combination AM580JXVGHH AM600JXVGHH AM620JXVGHH AM640JXVGHH AM660JXVGHH
Number of individual outdoor units 3 3 4 4 4
Combined outdoor unit
AM080JXVGHH
AM100JXVGHH
1
AM120JXVGHH
1 2 1
AM140FXVAHH
1
AM160JXVGHH
AM180JXVGHH
1
AM200JXVGHH 2 3 2 2 2
Rated capacity
Cooling (kW)
162.4 168.0 173.6 179.2 185.6
Cooling (Btu/h)
554 100 573 200 592 300 611 500 633 300
Heating (kW)
182.7 189.0 195.3 201.6 208.8
Heating (Btu/h)
623 400 644 900 666 400 687 900 712 500
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW)
81.2 84.0 86.8 89.6 92.8
Minimum (Btu/h)
277 100 286 600 296 200 305 700 316 600
Maximum (kW)
211.1 218.4 225.7 233.0 241.3
Maximum (Btu/h)
720 400 745 200 770 100 794 900 823 300
Maximum number of connectable indoor units
64 64 64 64 64
DVM S Philip OU_IM_03938A-08_EN.indd 17 2016-09-19 오후 1:48:55
18
Preparing for installation
Model name for combination AM680JXVGHH AM700JXVGHH AM720JXVGHH AM740JXVGHH AM760JXVGHH
Number of individual outdoor units 4 4 4 4 4
Combined outdoor unit
AM080JXVGHH
AM100JXVGHH
AM120JXVGHH
1 1 1
AM140FXVAHH
1
AM160JXVGHH
1 1
AM180JXVGHH
1
AM200JXVGHH 2 2 3 3 3
Rated capacity
Cooling (kW)
190.6 196.0 201.6 208.0 213.0
Cooling (Btu/h)
650 400 668 800 687 900 709 700 726 800
Heating (kW)
213.8 220.5 226.8 234.0 239.0
Heating (Btu/h)
729 500 752 400 773 900 798 400 815 500
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW)
95.3 98.0 100.8 104.0 106.5
Minimum (Btu/h)
325 200 334 400 343 900 354 900 363 400
Maximum (kW)
247.8 254.8 262.1 270.4 276.9
Maximum (Btu/h)
845 500 869 400 894 300 922 600 944 800
Maximum number of connectable indoor units
64 64 64 64 64
Model name for combination AM780JXVGHH AM800JXVGHH
Number of individual outdoor units 4 4
Combined outdoor unit
AM080JXVGHH
AM100JXVGHH
AM120JXVGHH
AM140FXVAHH
AM160JXVGHH
AM180JXVGHH
1
AM200JXVGHH 3 4
Rated capacity
Cooling (kW)
218.4 224.0
Cooling (Btu/h)
745 200 764 300
Heating (kW)
245.7 252.0
Heating (Btu/h)
838 400 859 900
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW)
109.2 112.0
Minimum (Btu/h)
372 600 382 200
Maximum (kW)
283.9 291.2
Maximum (Btu/h)
968 800 993 600
Maximum number of connectable indoor units
64 64
DVM S Philip OU_IM_03938A-08_EN.indd 18 2016-09-19 오후 1:48:55
19
ENGLISH
High Eciency type (Heat pump)
Model name for combination
AM080KXVGHH AM100KXVGHH AM120KXVGHH AM140KXVGHH AM160KXVGHH
Number of individual outdoor units
1 1 1 1 1
Combined
outdoor unit
AM080KXVGHH 1
AM100KXVGHH 1
AM120KXVGHH 1
AM140KXVGHH 1
AM160KXVGHH 1
AM180KXVGHH
AM200KXVGHH
AM220KXVGHH
Rated capacity
Cooling (kW) 22.4 28.0 33.6 40.0 45.0
Cooling (Btu/h) 76 400 95 500 114 600 136 500 153 500
Heating (kW) 25.2 31.5 37.8 45.0 50.0
Heating (Btu/h) 86 000 107 500 129 000 153 500 170 600
Total capacity
of the
connected
indoor units
(Cooling)
Minimum (kW) 11.2 14.0 16.8 20.0 22.5
Minimum (Btu/h) 38 200 47 800 57 300 68 200 76 800
Maximum (kW) 29.1 36.4 43.7 52.0 58.5
Maximum (Btu/h) 99 400 124 200 149 000 177 400 199 600
Maximum number of connectable
indoor units
14 18 21 26 29
Model name for combination
AM180KXVGHH AM200KXVGHH AM220KXVGHH AM240KXVGHH AM260KXVGHH
Number of individual outdoor units
1 1 1 2 2
Combined
outdoor unit
AM080KXVGHH
AM100KXVGHH
AM120KXVGHH 2 1
AM140KXVGHH 1
AM160KXVGHH
AM180KXVGHH 1
AM200KXVGHH 1
AM220KXVGHH 1
Rated capacity
Cooling (kW) 50.4 56.0 61.6 67.2 73.6
Cooling (Btu/h) 172 000 191 100 210 200 229 300 251 100
Heating (kW) 56.7 63.0 69.3 75.6 82.8
Heating (Btu/h) 193 500 215 000 236 500 258 000 282 500
Total capacity
of the
connected
indoor units
(Cooling)
Minimum (kW) 25.2 28.0 30.8 33.6 36.8
Minimum (Btu/h) 86 000 95 500 105 100 114 600 125 600
Maximum (kW) 65.5 72.8 80.1 87.4 95.7
Maximum (Btu/h) 223 600 248 400 273 200 298 100 326 500
Maximum number of connectable
indoor units
32 36 40 43 47
DVM S Philip OU_IM_03938A-08_EN.indd 19 2016-09-19 오후 1:48:55
20
Preparing for installation
Model name for combination
AM280KXVGHH AM300KXVGHH AM320KXVGHH AM340KXVGHH AM360KXVGHH
Number of individual outdoor units
2 2 2 2 2
Combined
outdoor unit
AM080KXVGHH
AM100KXVGHH
AM120KXVGHH 1 1 1 1
AM140KXVGHH 1
AM160KXVGHH 1
AM180KXVGHH 1
AM200KXVGHH 1
AM220KXVGHH 1 1
Rated capacity
Cooling (kW) 78.6 84.0 89.6 95.2 101.6
Cooling (Btu/h) 268 200 286 600 305 700 324 800 346 700
Heating (kW) 87.8 94.5 100.8 107.1 114.3
Heating (Btu/h) 299 600 322 400 343 900 365 400 390 000
Total capacity
of the
connected
indoor units
(Cooling)
Minimum (kW) 39.3 42.0 44.8 47.6 50.8
Minimum (Btu/h) 134 100 143 300 152 900 162 400 173 300
Maximum (kW) 102.2 109.2 116.5 123.8 132.1
Maximum (Btu/h) 348 700 372 600 397 400 422 300 450 700
Maximum number of connectable
indoor units
51 54 58 61 64
Model name for combination
AM380KXVGHH AM400KXVGHH AM420KXVGHH AM440KXVGHH AM460KXVGHH
Number of individual outdoor units
2 2 2 2 3
Combined
outdoor unit
AM080KXVGHH
AM100KXVGHH
AM120KXVGHH 2
AM140KXVGHH
AM160KXVGHH 1
AM180KXVGHH
AM200KXVGHH 2 1
AM220KXVGHH 1 1 2 1
Rated capacity
Cooling (kW) 106.6 112.0 117.6 123.2 128.8
Cooling (Btu/h) 363 700 382 200 401 300 420 400 439 500
Heating (kW) 119.3 126.0 132.3 138.6 144.9
Heating (Btu/h) 407 100 429 900 451 400 472 900 494 400
Total capacity
of the
connected
indoor units
(Cooling)
Minimum (kW) 53.3 56.0 58.8 61.6 64.4
Minimum (Btu/h) 181 900 191 100 200 600 210 200 219 700
Maximum (kW) 138.6 145.6 152.9 160.2 167.4
Maximum (Btu/h) 472 900 496 800 521 600 546 500 571 300
Maximum number of connectable
indoor units
64 64 64 64 64
DVM S Philip OU_IM_03938A-08_EN.indd 20 2016-09-19 오후 1:48:56
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102

Samsung AM260HXVAHH Installation guide

Category
Power heat guns
Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI