LG PRLK594A0 Installation guide

Type
Installation guide

The LG PRLK594A0 is a modern EEV kit suitable for use with air conditioners. It helps to precisely control the refrigerant flow, leading to improved energy efficiency and enhanced cooling performance. The kit includes an EEV controller module, thermistors, and other necessary components for hassle-free installation. With the LG PRLK594A0, you can expect better temperature regulation, reduced energy consumption, and a more comfortable indoor environment.

The LG PRLK594A0 is a modern EEV kit suitable for use with air conditioners. It helps to precisely control the refrigerant flow, leading to improved energy efficiency and enhanced cooling performance. The kit includes an EEV controller module, thermistors, and other necessary components for hassle-free installation. With the LG PRLK594A0, you can expect better temperature regulation, reduced energy consumption, and a more comfortable indoor environment.

MFL70524401
Rev.00_053018
INSTALLATION MANUAL
Applied(AHU)
EEV KIT
Original instruction
AIR
CONDITIONER
www.lghvac.com
www.lg.com
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring standards
by authorized personnel only.
Please retain this installation manual for future reference after reading it thoroughly.
Copyright © 2018 LG Electronics Inc. All Rights Reserved.
ENGLISH
FRANÇAIS
ESPAÑOL
1,MFL70524401,영영 2018. 7. 23. 영영 5:04 Page 1
TIPS FOR SAVING ENERGY
2
ENGLISH
• Do not cool excessively indoors. This may be harmful for your health and may consume more
electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air
conditioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the
air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty
purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
Here are some tips that will help you minimize the power consumption when you use the air
conditioner. You can use your air conditioner more efficiently by referring to the instructions
below:
TIPS FOR SAVING ENERGY
1,MFL70524401,영영 2018. 7. 23. 영영 5:04 Page 2
3
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak
performance of your product.
WARNING
It can result in serious injury or death when the directions are ignored.
CAUTION
It can result in minor injury or product damage when the directions are ignored.
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• Installation MUST conform with local building codes or, in the absence of local codes.
• The information contained in the manual is intended for use by a qualified service technician familiar
with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment
malfunction, property damage, personal injury and/or death.
Installation
• Don’t use a power cord, a plug or a loose socket which is damaged.
- Otherwise, it may cause a fire or electrical shock.
• For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
- Do not disassemble or repair the product. There is risk of fire or electric shock.
• Always ground the product.
- There is risk of fire or electric shock.
• Install the panel and the cover of control box securely.
- There is risk of fire or electric shock.
• Always install a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Do not modify or extend the power cable.
- There is risk of fire or electric shock.
• Do not let the air conditioner run for a long time when the humidity is very high and a door or a
window is left open.
- Moisture may condense and wet or damage furniture.
• Be cautious when unpacking and installing the product.
- Sharp edges could cause injury. Be especially careful of the case edges and the fins on the
condenser and evaporator.
• You need to use a safely insulated power supply which follows IEC61558-2-6 and NEC Class2.
- If you do not follow, It may cause fire, electric shock, explosion or injury.
• Securely attach the electrical part cover to EEV Controller Module.
- If the electric part cover of EEV Controller Module is not attached securely, it could result in a fire
or electric shock due to dust, water, etc.
• Do not keep or use flammable gases or combustibles near the equipment.
!
!
!
IMPORTANT SAFETY INSTRUCTIONS
ENGLISH
1,MFL70524401,영영 2018. 7. 23. 영영 5:04 Page 3
- Otherwise, it may cause a fire or the failure of product.
• Do not install, remove or reinstall the unit by yourself.
- Otherwise, it may cause a fire, electrical shock, explosion or injury.
• Do not disassemble or repair the product randomly.
- It will cause a fire or electrical shock.
• Do not install the product in a place where there is the concern of falling down.
- Otherwise, it may result in personal injury.
• Do not install the product on a defective installation stand.
- It may cause injury, accident, or damage to the product.
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the air conditioner could fall with it, causing property damage, product failure,
and personal injury.
• There is a risk of fire and explosion.
- Inert gas (nitrogen) should be used when you check plumbing leaks, cleaning or repairs of pipes
etc. If you are using combustible gases including oxygen, product may have the risk of fires and
explosions.
Operation
• Do not store or use flammable gas or combustibles near the product.
- There is risk of fire or failure of product.
• Do not share the outlet with other appliances.
- It will cause an electric shock or a fire due to heat generation.
• Do not use the damaged power cord.
- Otherwise, it may cause a fire or electrical shock.
• Do not modify or extend the power cord randomly.
- Otherwise, it may cause a fire or electrical shock.
• Take care so that the power cord may not be pulled during operation.
- Otherwise, it may cause a fire or electrical shock.
• Unplug the unit if strange sounds, smell, or smoke comes from it.
- Otherwise, it may cause electrical shock or a fire.
• Keep flames away.
- Otherwise, may occur a fire.
• Take the power plug out if necessary, holding the head of the plug and do not touch it with wet
hands.
- Otherwise, it may cause a fire or electrical shock.
• Do not use the power cord near the heating tools.
- Otherwise, it may cause a fire and electrical shock.
• Do not allow water to run into electrical parts.
- Otherwise, it may cause the failure of machine or electrical shock.
• Hold the plug by the head when taking it out.
- It may cause electric shock and damage.
• Be cautious that water could not enter the product.
- Otherwise, it may cause a fire electrical shock or product damage.
• Do not step on the indoor/outdoor unit and do not put anything on it.
- It may cause an injury through dropping of the unit or falling down.
• Do not place a heavy object on the power cord.
- Otherwise, it may cause a fire or electrical shock.
• When the product is submerged into water, always contact the service center.
- Otherwise, it may cause a fire or electrical shock.
IMPORTANT SAFETY INSTRUCTIONS
4
ENGLISH
1,MFL70524401,영영 2018. 7. 23. 영영 5:04 Page 4
IMPORTANT SAFETY INSTRUCTIONS
5
ENGLISH
CAUTION
Installation
• Always check for gas (refrigerant) leakage after installation or repair of product.
- Low refrigerant levels may cause failure of product.
• Install the drain hose to ensure that water is drained away properly.
- A bad connection may cause water leakage.
• Keep level even when installing the product.
- To avoid vibration or water leakage.
• Do not install the product where the noise or hot air from the outdoor unit could damage the
neighborhoods.
- It may cause a problem for your neighbors.
• Do not install the product where it will be exposed to sea wind (salt spray) directly.
- It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator
fins, could cause product malfunction or inefficient operation.
• Thickness of copper pipes used are as shown “Flaring work” Table.
- Never use copper pipes thinner than that in the table even when it is available on the market
• Do not use copper pipes having a collapsed.
- Otherwise, the expansion valve or capillary tube may become blocked with contaminants.
• For R410A model, use piping, flare nut and tools which is specified for R410A refrigerant.
- Using of (R22) piping, flare nut and tools may cause abnormally high pressure in the refrigerant
cycle (piping), and possibly result in explosion and injury.
• It is desirable that the amount of residual oil less than 40 mg/10m.
!
1,MFL70524401,영영 2018. 7. 23. 영영 5:04 Page 5
6
BEFORE INSTALLATION
ENGLISH
CAUTION
Don't install or operate the unit in rooms mentioned below.
Where mineral oil, like cutting oil is present.
Where the air contains high levels of salt such as air near the ocean.
Where sulphurous gas is present such as that in areas of hot spring.
In vehicles or vessels.
Where voltage fluctuates a lot such as that in factories.
Where high concentration of vapor spray are present.
Where machines generating electromagnetic waves are present.
Where acidic or alkaline vapor is present.
The option boxes must be installed with entrances downward.
!
BEFORE INSTALLATION
1,MFL70524401,영영 2018. 7. 23. 영영 5:04 Page 6
7
2 TIPS FOR SAVING ENERGY
3 IMPORTANT SAFETY INSTRUCTIONS
6 BEFORE INSTALLATION
8 Installation Composition
9 EEV KIT installation
9 Product installation
10 Welding
13 ELECTRICAL CONNECTION
13 Cable connection
15 EEV CONTROLLER MODULE SPECIFICATION
15 Dimension
15 Installation
16 EEV CONTROLLER INSTALLATION
16 Electric wiring work (EEV Controller)
17 DIP switch setting
18 LEAK TEST AND VACUUM
18 Leak test
18 Vacuum
20 Electrical work
21 THERMISTORS INSTALLATION
21 Pipe thermistors Installation
TABLE OF CONTENTS
TABLE OF CONTENTS
ENGLISH
1,MFL70524401,영영 2018. 7. 23. 영영 5:04 Page 7
8
INSTALLATION COMPOSITION
ENGLISH
INSTALLATION COMPOSITION
Liquid pipe
Gas pipe
Refrigerant pipe
Pipe sensor
Communication cable
Refrigerant flow (air conditioning)
Refrigerant flow (heating)
This EEV KIT is a product that connects an AHU with an outdoor unit with the following
composition.
installation components
No. Name Notes
1 AIR HANDLING UNIT -
2 AHU EEV KIT
Connectible outdoor unit capacity
PRLK396A0 22 ~ 40 HP
PRLK594A0 42 ~ 60 HP
3 AHU Comm. KIT -
4 Outdoor unit MULTI V
5 Pipe sensor_IN Sensor: Ø 5, length: 5m, cable color: Black
6 Pipe sensor_OUT Sensor: Ø 7, length: 5m, cable color: Red
7 90˚ elbow
PRLK396A0 Ø19.05 (5/8")
PRLK594A0 Ø19.05 (5/8")
1,MFL70524401,영영 2018. 7. 23. 영영 5:04 Page 8
EEV KIT INSTALLATION
9
ENGLISH
Product installation
1) Remove the two screws
from the EEV KIT's base
plate. Move the screws to
separate the cover plate and
base plate of the EEV KIT.
2) Remove the base plate. 3) Remove the four
screws from the
cover plate
4) Remove the cover
plate.
2
Drill holes in the correct locations and use 4 screws (M5, not provided) to affix the EEV KIT.
1 Remove the screws to separate the cover plate and base plate of the EEV KIT.
Pipe diameter
Ø19.05 mm (5/8")
Hole size
Ø6 mm (1/4")
Pipe diameter
Ø19.05 mm (5/8")
Model name
length
A B
PRLK594A0
273 mm
(10-3/4")
250.3 mm
(9-6/7")
PRLK396A0
273 mm
(10-3/4")
190.3 mm
(7-1/2")
EEV KIT INSTALLATION
1,MFL70524401,영영 2018. 7. 23. 영영 5:04 Page 9
EEV KIT INSTALLATION
10
ENGLISH
Welding
1 Check the inlet/outlet pipe before welding the EEV KIT.
AHU side
Outdoor
unit side
Outlet
A
Inlet
Air-conditioning
standard refrigerant flow
2 Weld the connector pipe (not provided) at the outdoor unit.
3 When connecting the outdoor unit's connector pipe and the EEV KIT pipe, be sure to use a
socket (not provided) that meets the necessary specifications.
4 As the size of the EEV KIT pipe and the outdoor unit's connector pipe could vary, check the
sizes beforehand and use a socket that meets the necessary specifications.
5 When welding, make sure to follow the safety precautions at all times.
6 Be sure to insulate 'A' part after welding with insulation (15T or more).
CAUTION
• Be sure to pass nitrogen through when welding parts together. Failure to do so could lead
to the compressor not working properly or becoming damaged.
• It is essential that the part be wrapped with a wet towel before and after welding. Failure
to do so could result in the part becoming damaged.
• Use a protective panel or be especially cautious not to let welding sparks come in contact
with the AHU panel.
• After welding, be sure to test for any leakage.
• Failure to properly insulate after welding may result in leakage.
!
Outdoor unit connector pipe
(not included)
Connector socket
(not included)
Connector socket(Elbow)
(not included)
[AHU and Outdoor Unit Connection]
AHU Connection Part
1,MFL70524401,영영 2018. 7. 23. 영영 5:04 Page 10
EEV KIT INSTALLATION
11
ENGLISH
When conducting welding, you must pass nitrogen through at about 0.02 MPa (0.2 kg/cm
2
).
Before proceeding to weld, you must remove all the air from inside the pipe using nitrogen.
Failure to use nitrogen results in the occurrence of oxidation inside the pipe, leading to the
malfunction of the compressor and blocking of the strainer.
WARNING
• While welding, always be careful that no refrigerant leaks.
• When refrigerant combusts, it creates a toxic gas that is harmful to the body.
• Do not conduct welding in an enclosed area.
• After welding a pipe, be sure to test for any leakage.
!
Welding area
Taping
Pressure regulator
High-pressure hose
Nitrogen
1,MFL70524401,영영 2018. 7. 23. 영영 5:04 Page 11
12
EEV KIT INSTALLATION
ENGLISH
pipe cutting
1 Be sure to use a copper pipe cutter for the pipe cutting.
2 Remove any burrs.
(When cutting, have the pipe end tilted downward so that any burrs do not get inside of the
pipe.)
Copper
pipe cutter
90°
Incline Roughness
Pipe
Copper
pipe cutter
90°
Incline Roughness
Pipe
CAUTION
• Cut the cutting area in a straight line.
!
CAUTION
• The presence of burrs can result in refrigerant leakage, so be sure to remove any burrs
with a reamer.
• Cutting dust could lead to malfunctioning if it gets inside the pipe.
!
1,MFL70524401,영영 2018. 7. 23. 영영 5:04 Page 12
ELECTRICAL CONNECTION
13
ENGLISH
Cable connection
1 Open the EEV KIT terminal box cover.
2 Check the marked color label and connect the cable using the driver (+).
• Example) Model PRLK594A0
PRLK396A0 is a model with one terminal block.
(Correct wiring)
D
B
C
AHU controller
Detail
AHU EEV controller
WARNING
• Please connect one controller with one terminal block of EEV KIT. Failure to do so may
result in component damage or fire. (Refer to correct wiring.)
• To connect with EEV KIT (PRLK594A0), the AHU EEV controller must be purchased
separately.
!
(Incorrect wiring)
AHU controller
WARNING
• Do not connect to the AHU controller after wiring the terminal blocks inside the EEV KIT.
Failure to do so may result in component damage or fire. (Refer to incorrect wiring.)
!
ELECTRICAL CONNECTION
1,MFL70524401,영영 2018. 7. 23. 영영 5:04 Page 13
14
ELECTRICAL CONNECTION
ENGLISH
3 Use the screwdriver (+) to connect the EEV wires to the terminal block (E) according to the
displayed instructions.
E
Field Wiring Part
Note
BR : Brown
RD : Red
BL : Blue
OR : Orange
YL : Yellow
WH : White
WARNING
• Before installation, check the color on the label and connect it to the terminal block.
• It may result in malfunction.
• Use a ring type terminal (P4) to connect to the terminal block.
!
4 Close the cover of the EEV KIT terminal box (B).
1,MFL70524401,영영 2018. 7. 23. 영영 5:04 Page 14
EEV CONTROLLER MODULE SPECIFICATION
15
ENGLISH
91(3.58)
54(2.13) 61(2.4)
Unit : mm(inch)
<EEV controller module>
1. Open the door using the key.
(PAHCMS000)
2. Install the EEV controller module using screws
in the two holes.
CAUTION
• This model requires DC12 V ~ external power supply. (Select an insulating transformer
that complies with IEC61558-2-6 and NEC Class 2.)
• Please check the product operation range below.
!
Power supply DC 12 V
Product operation range
Ambient temperature -20 ~ 65 °C (-4 ~149 °F) DB
Humidity 0 ~ 98 % (Non-condensing)
Installation
Dimension
EEV CONTROLLER MODULE SPECIFICATION
1,MFL70524401,영영 2018. 7. 23. 영영 5:04 Page 15
16
EEV CONTROLLER INSTALLATION
ENGLISH
<PAHCMS000> <EEV Controller>
EEV(1ch) EEV(2ch)
NTC
Circuit diagram
* Please refer to the circit diagram of PAHCMS000 for further details.
Electric wiring work (EEV Controller)
EEV CONTROLLER INSTALLATION
1,MFL70524401,영영 2018. 7. 23. 영영 5:04 Page 16
EEV CONTROLLER INSTALLATION
17
ENGLISH
>'HIDXOWVHWWLQJ@

21
6:

21
6:
DIP switch setting
• EEV Controller DIP switch 2 (SW02) is for setting modbus addresses, and it is common practice
to follow the table below.(SW01 is ‘reserved’)
No
SW02
1 2 3 4 Address
1 OFF OFF OFF
ON : Software Update
OFF : -
0
2 OFF OFF ON 1
3 OFF ON OFF 2
4 OFF ON ON 3
5 ON OFF OFF 4
6 ON OFF ON 5
7 ON ON OFF 6
8 ON ON ON 7
1,MFL70524401,영영 2018. 7. 23. 영영 5:04 Page 17
18
LEAK TEST AND VACUUM
ENGLISH
Leak tests are carried out to standards identical with the MULTI-V leak test.
Leak tests are carried out by pressurizing nitrogen gas to 3.8MPa (38.7 kgf/cm
2
). Refer to the
following picture for test methods.
(The service valve should be closed when carrying out tests and pressurizing liquid and gas
pipes.)
After nitrogen gas has been pressurized, pressure must not drop during a 24 hour period.
Low
pressure
High
pressure
Nitrogen gas
Direction of indoor unit
Manifold gauge
Low-tension grip
High-tension grip
Service valve
Gas pipe
Liquid pipe
Outdoor unit
Service port
Vacuum testing is conducted to standards identical with the MULTI-V vacuum test.
As shown in the picture below, with the outdoor unit's service valve closed, use the vacuum
pump to perform vacuuming of the AHU and connector pipe from the stop valve's service port.
Vacuuming must always be conducted from the service port of liquid and gas pipes.
After maintaining a vacuum level of 5 Torr for one hour, there should be no change in the
vacuum level for another hour.
(If there is a change in the vacuum level, there could be a leak or moisture inside the pipe)
If there is a possibility of moisture inside the pipe, a vacuum must be maintained for 2 hours,
after which 0.05 Mpa (0.5 kgf/cm2) of nitrogen gas is injected.
After this, a vacuum is should be performed for at least one hour, maintained for an hour once 5
Torr is reached, and then the vacuum gauge is checked for changes.
Refrigerant should never be used for air purging.
Perform vacuuming using a vacuum pump with a vacuum gauge attached.
Vacuum
Leak test
LEAK TEST AND VACUUM
1,MFL70524401,영영 2018. 7. 23. 영영 5:04 Page 18
LEAK TEST AND VACUUM
19
ENGLISH
Low
pressure
High
pressure
Manifold gauge
Low-tension handle
High-tension handle
Service valve
Liquid pipe
Gas pipe
Service port
3-direction joint
Valve
Valve
R410A cylinder
Scale: using a gravimeter
Use one that measures up to 0.1 kg
If a high-density scale is unavailable, a
charging cylinder can be used.
vacuum pump
- Perform a calculation to add a precise amount of refrigerant.
- Adding an imprecise amount of refrigerant could cause problems for the product.
- If the amount of added refrigerant goes beyond of ±10%, burning of the compressor and
poor performance of the indoor unit could occur.
WARNING
• Pipes that must be vacuumed: gas pipe, liquid pipe
• When installing or moving the product to another location, do not fill with any refrigerants
besides the regulated refrigerant (R410A).
• Mixing the original refrigerant with a different refrigerant can cause malfunctioning or
damage to the refrigerant cycle.
• If injecting gaseous R410A, you should change the refrigerant composition you use to a
liquid form.
!
1,MFL70524401,영영 2018. 7. 23. 영영 5:04 Page 19
20
LEAK TEST AND VACUUM
ENGLISH
1 For the wired remote controller wire and outdoor unit communication wire, remove the
coating at the end of the wire to connect and use the pin type (JOBN153) to connect to the
terminal block.
Pin type (JOBN153)
Connection of the wires
Electrical work
CAUTION
• All field supplied parts and materials and electric works must be conform to local codes.
• Use copper wire only.
• All wiring must be performed by an authorized electrician.
• A main switch or other means for disconnection, having a contact separation in all poles,
must be incorporated in the fixed wiring in accordance to relevant local and national
legislation.
• Refer to the installation manual attached to the outdoor unit for the size of power supply
electric wire connected to the outdoor unit, the capacity of the circuit breaker and switch,
wiring and wiring instructions.
!
1,MFL70524401,영영 2018. 7. 23. 영영 5:05 Page 20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23

LG PRLK594A0 Installation guide

Type
Installation guide

The LG PRLK594A0 is a modern EEV kit suitable for use with air conditioners. It helps to precisely control the refrigerant flow, leading to improved energy efficiency and enhanced cooling performance. The kit includes an EEV controller module, thermistors, and other necessary components for hassle-free installation. With the LG PRLK594A0, you can expect better temperature regulation, reduced energy consumption, and a more comfortable indoor environment.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI