Samsung AM140KN4DEH/EU Installation guide

Type
Installation guide
DVM S
AM∗∗∗JXV∗∗∗ Series
AM∗∗∗KXV∗∗∗ Series
AM∗∗∗MXV∗∗∗ Series
AM∗∗∗NXV∗∗∗ Series
Air Conditioner
installation manual
imagine the possibilities
Thank you for purchasing this Samsung product.
DVM_실외기 IM 구주향(ET) ErP 규제_EN_DB68-07586A-02.indd 1 2018-02-20 오후 2:08:10
2
Contents
Safety precautions....................................................................................3
Preparing for installation ..............................................................................6
Selecting installation location ........................................................................25
Space requirement for installation ....................................................................27
Accessories .........................................................................................29
Base construction and installation of the outdoor unit ..................................................30
Installing the wind/snow prevention duct ..............................................................34
Refrigerant pipe installation..........................................................................37
Electrical wiring work ................................................................................69
Air tightness test and vacuum drying ..................................................................87
Pipe insulation ......................................................................................89
Charging refrigerant .................................................................................92
Basic segment display ...............................................................................95
Setting outdoor unit option switch and key function ....................................................95
Setting the MCU and Pipe Addresses (for HR Only).....................................................105
Things to check after completing the installation ......................................................110
Inspection and test operation ........................................................................ 111
Automatic refrigerant amount detection function .....................................................118
Product Information ................................................................................120
Correct Disposal of This Product
(Waste Electrical & Electronic Equipment)
(Applicable in countries with separate collection systems)
This marking on the product, accessories or literature indicates that the product and its electronic
accessories (e.g. charger, headset, USB cable) should not be disposed of with other household waste at the
end of their working life. To prevent possible harm to the environment or human health from uncontrolled
waste disposal, please separate these items from other types of waste and recycle them responsibly to
promote the sustainable reuse of material resources.
Household users should contact either the retailer where they purchased this product, or their local

recycling.
Business users should contact their supplier and check the terms and conditions of the purchase contract.
This product and its electronic accessories should not be mixed with other commercial wastes for disposal.

obligations, e.g. REACH, WEEE, Batteries, visit : samsung.com/uk/aboutsamsung/samsungelectronics/
corporatecitizenship/data_corner.html
DVM_실외기 IM 구주향(ET) ErP 규제_EN_DB68-07586A-02.indd 2 2018-02-20 오후 2:08:10
3
ENGLISH
Safety precautions
Please follow the following safety information for safety of the installer and the user.
DVM S air conditioner uses R-410A refrigerant.
When using R-410A, moisture or foreign substances may affect the performance and reliability of the
product. Safety precautions must be obeyed when installing the refrigerant pipe.
The designed maximum pressure of the system is 4.1MPa and therefore select appropriate material
and thickness according to the regulations.

the refrigerant. (If you charge vapor refrigerant, it may change the blend of the refrigerant and cause
product malfunction.)

models names for connectable indoor units. (If you connect the indoor units that are not designed for
R-410A, it cannot operated normally.)
After completing the installation and trial operation, explain to the user how to use and maintain the
product. Also, hand over this installation manual so that it can be stored by the user.
Manufacturer is not responsible for the incidents occurred by improper installation. Installer is responsible
for any installation related claims from the user occurred by neglecting warnings and cautions stated in
this manual. (Installer will be responsible for any service charges that may occur)
Generally, system air conditioners should not be relocated after installation. But when it has to be

WARNING
Hazards or unsafe practices that may result in severe personal injury or death.
CAUTION
Hazards or unsafe practices that may result in minor personal injury (to installer/user)
or property damage.
SEVERE WARNING SIGNS
Consult qualied installer or dealer for installation.

occur.
Installation work must be done properly according to this installation manual.

When installing the unit in a small room, take measure to keep the refrigerant concentration from exceeding
allowable safety limits in case of refrigerant leakage. Consult the dealer for precautionary measure before
the installation.
When refrigerant leaks and exceed dangerous concentration level, it may cause suffocation accidents.
If any gas or impurities, except R-410A refrigerant, come into the refrigerant pipe, serious problem may
occur and it may cause injury.
Use the supplied accessories, specied components and tools for the installation.
Do not use the pipe and the installation product used for the R-22 refrigerant.


Install the outdoor unit on a hard and even place that can support its weight.
If the place cannot support its weight, the outdoor unit may fall down and it may cause injury.
DVM_실외기 IM 구주향(ET) ErP 규제_EN_DB68-07586A-02.indd 3 2018-02-20 오후 2:08:11
4
Safety precautions
Check the following before installation and service work.

Before welding, remove the refrigerant from inside the pipe or the product.
If you perform welding while refrigerant is in the pipe, it may increase the pressure of the refrigerant and
cause the pipe to burst. If the pipe bursts or explodes, it may cause severe injury to the installer.
When welding, use the nitrogen gas to eliminate oxidation inside the pipe.
Do not modify the product on your own.

Fix the outdoor unit securely on foundation to resist strong wind or earthquake.

Electric work must be done by qualied persons, complying the national wiring regulations and installed
according to the instruction stated in the installation manual with leased circuit.

Make sure to perform grounding work.
Do not connect the ground wire to a gas pipe, water pipe, lightning rod or telephone grounding. Improper
grounding could cause electric shock.
Wiring must be connected with the designated wires and it must be xed securely so that it does not apply
any external force to the connection part of the terminals.

Neatly arrange the wires in the electrical parts to make sure that electrical cover is closed securely without any gaps.

Exclusive circuit breaker (MCCB, ELB) must be installed to the power supply.
When overcurrent or current leakage occurs with no circuit breaker installed, power will not be cut-off and


You must cut-off the power before you work on, or adjust any power supply part for product installation,
maintenance, repair or any other services.
There is risk of electric shock.
Even when the power is off, it is dangerous when you come in contact with inverter PCB, fan PCB since high
pressure DC voltage is charged to those parts.
When replacing/repairing the PCB, cut-off the power and wait until the DC voltage is discharged before
replacing/repairing them. (Wait for more than 15 minutes to allow it to discharge naturally.)
If the refrigerant gas leaks during the installation, you should ventilate the room.

Gas leakage must be checked after installation is completed.

You can get a frostbite if you get in contact with the leaked refrigerant gas.
Supply power to the product during winter time since the product will operate in protection mode itself
when the temperature decrease below 0°C.
If you cut-off the power, compressor protection mode cannot be operated and may cause damage to the product.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or
mental capabilities, or lack of experience and knowledge, unless they have been given supervision or
instruction concerning use of the appliance by a person responsible for their safety.Children should be
supervised to ensure that they do not play with the appliance.
DVM_실외기 IM 구주향(ET) ErP 규제_EN_DB68-07586A-02.indd 4 2018-02-20 오후 2:08:11
5
ENGLISH
For use in Europe : This appliance can be used by children aged from 8 years and above and persons with
reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been
given supervision or instruction concerning use of the appliance in a safe way and understand the hazards
involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by
children without supervision.
CAUTION SIGNS
Do not install the drain pipe directly to the bottom part of the outdoor unit and built a proper drainage so
that water drains out smoothly. If not, pipe may freeze or bursts during winter time and cause damage to the
product or water leakage.
When the draining work is not done properly, water leak may occur and cause property damage.
Install the power cable and communication cable of the indoor and outdoor unit at least 1.5m away from the
electric appliances and install it at least 2m away from the lightning conductor.
Noise may be generated from the electronic devices, depending on the status of the electric wave.
Install the outdoor unit within the angle stated in the table, according to the height of the building.
Do not leave the refrigerant container under the hot sunlight. (There is risk of explosion.)
You must use the appropriate pipes according to the standard since the pressure of the refrigerant is very
high.
Make sure that the pipes does not get any weaker by welding it too much.
Make sure to install the product away from children’s’ reach. (Sharp parts of the heat exchanger is may
cause personal injury and when parts of the product gets damage, it may decrease product’s performance.)
Lighting rod
Protective angle:

Height of the building Protection control
20m or less 
40m or less 
60m or less 
Install the indoor unit away from lighting apparatus that uses ballast stabilizer.
If you use the wireless remote control, it may not operate normally due to ballast stabilizer.
Do not install the product in following places.
Place where outdoor unit’s noise and warm air may disturb neighbors. (It may cause property loss.)
Do not leave any obstacles around the inlet and outlet of the product. (It may cause damage or accidents.)
The place where there is mineral oil or arsenic acid.
Those parts may get damaged due to burned resin and cause water leakage or product may fall.
 
The place where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outlet.
The copper pipe or connection pipe may corrode and refrigerant may leak.
The place where there is a machine that generates electromagnetic waves.
The air conditioner may not operate normally due to problems in control system.
The place where there is a danger of combustible gas leakage or place where thinner or gasoline is
handled.
 

The place near seashore or hot spring where there is risk of outdoor unit corrosion.
DVM_실외기 IM 구주향(ET) ErP 규제_EN_DB68-07586A-02.indd 5 2018-02-20 오후 2:08:11
6
Safety precautions
Changes in DVM S (inverter) compare to conventional models that has to noted when installing
For optimal distribution of the refrigerant, you must use Y-joint as branch joint for connecting outdoor
units. (Do not use T-joint)
You cannot operate normally if you do not complete the trial operation through outdoor unit key mode.
You must use KEY MODE to run trial operation.
DVM S air conditioner uses R-410A refrigerant.
Check the compatibility of other products such as indoor unit, EEV kits etc. which will be connected to DVM S.
Make sure to note that outdoor unit combination is different from DVM PLUS III and IV.
The length of maximum piping, level difference, the quantity of connectable indoor units, the installation
at the outdoor joints and the outdoor unit combinations are different from the conventional models.
If the pipe length is over 2 m between outdoor units, make traps to prevent oil stagnation. Oil stagnation
may occur when outdoor unit at the end of module stops while other outdoor units are still in operation.
Preparing for installation
Outdoor unit classication
Classication Small type DVM S Large A type DVM S Large B type
Appearance
Packaging material disposition
Safely store or dispose the packaging materials.
Sharp metals such as nails or wooden material packaging that may break into pieces become a
cause for personal injury.
Make sure to store or dispose the vinyl type packaging material to keep it out of reach of children.
Children may put them over their face, which is very dangerous since it may lead them to
suffocation.
CAUTION
DVM_실외기 IM 구주향(ET) ErP 규제_EN_DB68-07586A-02.indd 6 2018-02-20 오후 2:08:11
7
ENGLISH
Preparing for installation
Outdoor unit combination
Make sure to use an indoor unit that is compatible with DVM S.
Indoor units can be connected within the range indicated in following table.
If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and
heating capacity of the indoor unit may decrease.
Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit

capacity)
You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor
unit is set to 64 since outdoor unit only support up to 64 communication address. Indoor unit address can


connected.
Do not install 1st-generation MCU and 2nd-generation MCU together.
 
 
Use the following table to determine the size and number of outdoor units needed to achieve

CAUTION
Standard type (Heat pump)
Model name for combination
AM080JXVAGH/ET AM100JXVAGH/ET AM120JXVAGH/ET AM140KXVAGH/ET AM160KXVAGH/ET AM180KXVAGH/ET
Number of individual outdoor units
1 1 1 1 1 1
Combined
outdoor unit
AM080JXVAGH/ET 1
AM100JXVAGH/ET 1
AM120JXVAGH/ET 1
AM140KXVAGH/ET 1
AM160KXVAGH/ET 1
AM180KXVAGH/ET 1
AM200KXVAGH/ET
AM220NXVAGH/ET
AM240KXVAGH/ET
AM260KXVAGH/ET
Total capacity
of the
connected
indoor units
(Cooling)
Minimum (kW)
11.2 14.0 16.8 20.0 22.5 25.2
Maximum (kW)
29.1 36.4 43.7 52.0 58.5 65.5
Maximum number of connectable
indoor units
14 18 21 26 29 32
DVM_실외기 IM 구주향(ET) ErP 규제_EN_DB68-07586A-02.indd 7 2018-02-20 오후 2:08:11
8
Preparing for installation
Model name for combination
AM200KXVAGH/ET AM220NXVAGH/ET AM240KXVAGH/ET AM260KXVAGH/ET AM280NXVAGH1ET AM300NXVAGH1ET
Number of individual outdoor units
1 1 1 1 2 2
Combined
outdoor unit
AM080JXVAGH/ET
AM100JXVAGH/ET 1
AM120JXVAGH/ET 1
AM140KXVAGH/ET
AM160KXVAGH/ET
AM180KXVAGH/ET 1 1
AM200KXVAGH/ET 1
AM220NXVAGH/ET 1
AM240KXVAGH/ET 1
AM260KXVAGH/ET 1
Total capacity
of the
connected
indoor units
(Cooling)
Minimum (kW)
28.0 30.8 33.6 36.4 39.2 42.0
Maximum (kW)
72.8 80.1 8 7.4 94.6 101.9 109.2
Maximum number of connectable
indoor units
36 40 43 47 51 54
Model name for combination
AM320NXVAGH1ET AM340NXVAGH1ET AM360NXVAGH1ET AM380NXVAGH1ET AM400NXVAGH1ET AM420NXVAGH1ET
Number of individual outdoor units
2 2 2 2 3 3
Combined
outdoor unit
AM080JXVAGH/ET
AM100JXVAGH/ET 1
AM120JXVAGH/ET 1 2
AM140KXVAGH/ET 1
AM160KXVAGH/ET 1
AM180KXVAGH/ET 1 1 2 1 1 1
AM200KXVAGH/ET 1
AM220NXVAGH/ET
AM240KXVAGH/ET
AM260KXVAGH/ET
Total capacity
of the
connected
indoor units
(Cooling)
Minimum (kW)
45.2 47.7 50.4 53.2 56.0 58.8
Maximum (kW)
117.5 124.0 131.0 138.3 145.6 152.9
Maximum number of connectable
indoor units
58 61 64 64 64 64
DVM_실외기 IM 구주향(ET) ErP 규제_EN_DB68-07586A-02.indd 8 2018-02-20 오후 2:08:11
9
ENGLISH
Model name for combination
AM440NXVAGH1ET AM460NXVAGH1ET AM480NXVAGH1ET AM500NXVAGH1ET AM520NXVAGH1ET AM540NXVAGH1ET
Number of individual outdoor units
3 3 3 3 3 3
Combined
outdoor unit
AM080JXVAGH/ET 1
AM100JXVAGH/ET 1
AM120JXVAGH/ET 1
AM140KXVAGH/ET 1
AM160KXVAGH/ET 1
AM180KXVAGH/ET 2 2 2 2 2 3
AM200KXVAGH/ET
AM220NXVAGH/ET
AM240KXVAGH/ET
AM260KXVAGH/ET
Total capacity
of the
connected
indoor units
(Cooling)
Minimum (kW)
61.6 64.4 6 7. 2 70.4 72.9 75.6
Maximum (kW)
160.2 167.4 174.7 183.0 189.5 196.6
Maximum number of connectable
indoor units
64 64 64 64 64 64
Model name for combination
AM560NXVAGH1ET AM580NXVAGH1ET AM600NXVAGH1ET AM620NXVAGH1ET AM640NXVAGH1ET AM660NXVAGH1ET
Number of individual outdoor units
3 3 3 4 4 4
Combined
outdoor unit
AM080JXVAGH/ET 1
AM100JXVAGH/ET 1
AM120JXVAGH/ET 1
AM140KXVAGH/ET
AM160KXVAGH/ET
AM180KXVAGH/ET 2 1 3 3 3
AM200KXVAGH/ET 1 2 3
AM220NXVAGH/ET
AM240KXVAGH/ET
AM260KXVAGH/ET
Total capacity
of the
connected
indoor units
(Cooling)
Minimum (kW)
78.4 81.2 84.0 86.8 89.6 92.4
Maximum (kW)
203.8 211.1 218.4 225.7 233.0 240.2
Maximum number of connectable
indoor units
64 64 64 64 64 64
DVM_실외기 IM 구주향(ET) ErP 규제_EN_DB68-07586A-02.indd 9 2018-02-20 오후 2:08:12
10
Preparing for installation
Model name for combination
AM680NXVAGH1ET AM700NXVAGH1ET AM720NXVAGH1ET AM740NXVAGH1ET AM760NXVAGH1ET AM780NXVAGH1ET
AM800NXVAGH1ET
Number of individual outdoor units
4 4 4 4 4 4 4
Combined
outdoor unit
AM080JXVAGH/ET
AM100JXVAGH/ET
AM120JXVAGH/ET
AM140KXVAGH/ET 1
AM160KXVAGH/ET 1
AM180KXVAGH/ET 3 3 4 3 2 1
AM200KXVAGH/ET 1 2 3 4
AM220NXVAGH/ET
AM240KXVAGH/ET
AM260KXVAGH/ET
Total capacity
of the
connected
indoor units
(Cooling)
Minimum (kW)
95.6 98.1 100.8 103.6 106.4 109.2 112.0
Maximum (kW)
248.6 255.1 262.1 269.4 276.6 283.9 291.2
Maximum number of connectable
indoor units
64 64 64 64 64 64 64
Premium compact type (Heat pump)
Model name for combination
AM080JXVHGH/ET AM100JXVHGH/ET AM120JXVHGH/ET AM140NXVHGH/ET AM160NXVHGH/ET AM180NXVHGH/ET
Number of individual outdoor units
1 1 1 1 1 1
Combined
outdoor unit
AM080JXVHGH/ET
1
AM100JXVHGH/ET
1
AM120JXVHGH/ET
1
AM140NXVHGH/ET
1
AM160NXVHGH/ET
1
AM180NXVHGH/ET
1
AM200NXVHGH/ET
AM220NXVHGH/ET
AM240KXVGGH/ET
AM260KXVGGH/ET
Total capacity
of the
connected
indoor units
Minimum (kW) 11.2 14.0 16.8 20.0 22.5 25.2
Maximum (kW) 29.1 36.4 43.7 52.0 58.5 65.5
Maximum number of connectable
indoor units
14 18 21 26 29 32
DVM_실외기 IM 구주향(ET) ErP 규제_EN_DB68-07586A-02.indd 10 2018-02-20 오후 2:08:12
11
ENGLISH
Model name for combination
AM200NXVHGH/ET AM220NXVHGH/ET AM240KXVGGH/ET AM260KXVGGH/ET AM280NXVGGH3ET AM300NXVGGH3ET
Number of individual outdoor units
1 1 1 1 2 2
Combined
outdoor unit
AM080JXVHGH/ET
AM100JXVHGH/ET
AM120JXVHGH/ET
1 1
AM140NXVHGH/ET
AM160NXVHGH/ET
1
AM180NXVHGH/ET
1
AM200NXVHGH/ET
1
AM220NXVHGH/ET
1
AM240KXVGGH/ET
1
AM260KXVGGH/ET
1
Total capacity
of the
connected
indoor units
Minimum (kW) 28.0 30.8 33.6 36.4 39.3 42.0
Maximum (kW) 72.8 80.1 8 7. 4 94.6 102.2 109.2
Maximum number of connectable
indoor units
36 40 43 47 51 54
Model name for combination
AM320NXVGGH3ET AM340NXVGGH3ET AM360NXVGGH3ET AM380NXVGGH3ET AM400NXVGGH3ET AM420NXVGGH3ET
Number of individual outdoor units
2 2 2 2 2 2
Combined
outdoor unit
AM080JXVHGH/ET
AM100JXVHGH/ET
AM120JXVHGH/ET
1 1 1 1
AM140NXVHGH/ET
AM160NXVHGH/ET
AM180NXVHGH/ET
AM200NXVHGH/ET
1 2 1
AM220NXVHGH/ET
1 1
AM240KXVGGH/ET
1
AM260KXVGGH/ET
1
Total capacity
of the
connected
indoor units
Minimum (kW) 44.8 4 7. 6 50.4 53.2 56.0 58.8
Maximum (kW) 116.5 123.8 131.0 138.3 145.6 152.9
Maximum number of connectable
indoor units
58 61 64 64 64 64
DVM_실외기 IM 구주향(ET) ErP 규제_EN_DB68-07586A-02.indd 11 2018-02-20 오후 2:08:12
12
Preparing for installation
Model name for combination
AM440NXVGGH3ET AM460NXVGGH3ET AM480NXVGGH3ET AM500NXVGGH3ET AM520NXVGGH3ET AM540NXVGGH3ET
Number of individual outdoor units
2 2 2 2 2 3
Combined
outdoor unit
AM080JXVHGH/ET
AM100JXVHGH/ET
AM120JXVHGH/ET
1
AM140NXVHGH/ET
AM160NXVHGH/ET
1
AM180NXVHGH/ET
AM200NXVHGH/ET
1 1
AM220NXVHGH/ET
1
AM240KXVGGH/ET
1 1
AM260KXVGGH/ET
1 1 1 2 1
Total capacity
of the
connected
indoor units
Minimum (kW) 61.6 64.4 6 7. 2 70.0 72.8 75.7
Maximum (kW) 160.2 167.4 174.7 182.0 189.3 196.8
Maximum number of connectable
indoor units
64 64 64 64 64 64
Model name for combination
AM560NXVGGH3ET AM580NXVGGH3ET AM600NXVGGH3ET AM620NXVGGH3ET AM640NXVGGH3ET AM660NXVGGH3ET
Number of individual outdoor units
3 3 3 3 3 3
Combined
outdoor unit
AM080JXVHGH/ET
AM100JXVHGH/ET
AM120JXVHGH/ET
1 1 1 1 1
AM140NXVHGH/ET
1
AM160NXVHGH/ET
AM180NXVHGH/ET
1
AM200NXVHGH/ET
1
AM220NXVHGH/ET
1
AM240KXVGGH/ET
1
AM260KXVGGH/ET
1 1 1 1 2 2
Total capacity
of the
connected
indoor units
Minimum (kW) 78.4 81.2 84.0 86.8 89.6 92.8
Maximum (kW) 203.8 211.1 218.4 225.7 233.0 241.3
Maximum number of connectable
indoor units
64 64 64 64 64 64
DVM_실외기 IM 구주향(ET) ErP 규제_EN_DB68-07586A-02.indd 12 2018-02-20 오후 2:08:12
13
ENGLISH
Model name for combination
AM680NXVGGH3ET AM700NXVGGH3ET AM720NXVGGH3ET AM740NXVGGH3ET AM760NXVGGH3ET AM780NXVGGH3ET AM800NXVGGH3ET
Number of individual outdoor units
3 3 3 3 3 3 4
Combined
outdoor unit
AM080JXVHGH/ET
AM100JXVHGH/ET
AM120JXVHGH/ET
1
AM140NXVHGH/ET
AM160NXVHGH/ET
1 1
AM180NXVHGH/ET
1
AM200NXVHGH/ET
1
AM220NXVHGH/ET
1
AM240KXVGGH/ET
1
AM260KXVGGH/ET
2 2 2 2 2 3 2
Total capacity
of the
connected
indoor units
Minimum (kW) 95.3 98.0 100.8 103.6 106.4 109.2 112.1
Maximum (kW) 247.8 254.8 262.1 269.4 276.6 283.9 291.5
Maximum number of connectable
indoor units
64 64 64 64 64 64 64
Premium energy efciency type (Heat pump)
Model name for combination
AM080JXVHGH/ET AM100JXVHGH/ET AM120JXVHGH/ET AM140NXVHGH/ET AM160NXVHGH/ET AM180NXVHGH/ET
Number of individual outdoor units
1 1 1 1 1 1
Combined
outdoor unit
AM080JXVHGH/ET
1
AM100JXVHGH/ET
1
AM120JXVHGH/ET
1
AM140NXVHGH/ET
1
AM160NXVHGH/ET
1
AM180NXVHGH/ET
1
AM200NXVHGH/ET
AM220NXVHGH/ET
AM240KXVGGH/ET
AM260KXVGGH/ET
Total capacity
of the
connected
indoor units
Minimum (kW) 11.2 14.0 16.8 20.0 22.5 25.2
Maximum (kW) 29.1 36.4 43.7 52.0 58.5 65.5
Maximum number of connectable
indoor units
14 18 21 26 29 32
DVM_실외기 IM 구주향(ET) ErP 규제_EN_DB68-07586A-02.indd 13 2018-02-20 오후 2:08:12
14
Preparing for installation
Model name for combination
AM200NXVHGH/ET AM220NXVGGH4ET AM240NXVGGH4ET AM260NXVGGH4ET AM280NXVGGH4ET AM300NXVGGH4ET
Number of individual outdoor units
1 2 2 2 2 2
Combined
outdoor unit
AM080JXVHGH/ET
1 1
AM100JXVHGH/ET
1
AM120JXVHGH/ET
AM140NXVHGH/ET
1 1 2 1
AM160NXVHGH/ET
1
AM180NXVHGH/ET
1
AM200NXVHGH/ET
1
AM220NXVHGH/ET
AM240KXVGGH/ET
AM260KXVGGH/ET
Total capacity
of the
connected
indoor units
Minimum (kW) 28.0 31.2 34.0 36.4 40.0 42.5
Maximum (kW) 72.8 81.1 88.4 94.6 104.0 110.5
Maximum number of connectable
indoor units
36 40 43 47 51 54
Model name for combination
AM320NXVGGH4ET AM340NXVGGH4ET AM360NXVGGH4ET AM380NXVGGH4ET AM400NXVGGH4ET AM420NXVGGH4ET
Number of individual outdoor units
2 2 2 2 2 3
Combined
outdoor unit
AM080JXVHGH/ET
1
AM100JXVHGH/ET
AM120JXVHGH/ET
AM140NXVHGH/ET
1 1 1
AM160NXVHGH/ET
AM180NXVHGH/ET
1 2 1
AM200NXVHGH/ET
1 1 2 1
AM220NXVHGH/ET
AM240KXVGGH/ET
AM260KXVGGH/ET
Total capacity
of the
connected
indoor units
Minimum (kW) 45.2 48.0 50.4 53.2 56.0 59.2
Maximum (kW) 117.5 124.8 131.0 138.3 145.6 153.9
Maximum number of connectable
indoor units
58 61 64 64 64 64
DVM_실외기 IM 구주향(ET) ErP 규제_EN_DB68-07586A-02.indd 14 2018-02-20 오후 2:08:12
15
ENGLISH
Model name for combination
AM440NXVGGH4ET AM460NXVGGH4ET AM480NXVGGH4ET AM500NXVGGH4ET AM520NXVGGH4ET AM540NXVGGH4ET
Number of individual outdoor units
3 3 3 3 3 3
Combined
outdoor unit
AM080JXVHGH/ET
1
AM100JXVHGH/ET
AM120JXVHGH/ET
AM140NXVHGH/ET
2 2 1 1
AM160NXVHGH/ET
AM180NXVHGH/ET
2 1 2 1 3
AM200NXVHGH/ET
1 1
AM220NXVHGH/ET
AM240KXVGGH/ET
AM260KXVGGH/ET
Total capacity
of the
connected
indoor units
Minimum (kW) 61.6 65.2 68.0 70.4 73.2 75.6
Maximum (kW) 160.2 169.5 176.8 183.0 190.3 196.6
Maximum number of connectable
indoor units
64 64 64 64 64 64
Model name for combination
AM560NXVGGH4ET AM580NXVGGH4ET AM600NXVGGH4ET AM620NXVGGH4ET AM640NXVGGH4ET AM660NXVGGH4ET
Number of individual outdoor units
3 3 3 4 4 4
Combined
outdoor unit
AM080JXVHGH/ET
1 1
AM100JXVHGH/ET
AM120JXVHGH/ET
1
AM140NXVHGH/ET
AM160NXVHGH/ET
AM180NXVHGH/ET
2 1 3 2 3
AM200NXVHGH/ET
1 2 3 1
AM220NXVHGH/ET
AM240KXVGGH/ET
AM260KXVGGH/ET
Total capacity
of the
connected
indoor units
Minimum (kW) 78.4 81.2 84.0 86.8 89.6 92.4
Maximum (kW) 203.8 211.1 218.4 225.7 233.0 240.2
Maximum number of connectable
indoor units
64 64 64 64 64 64
DVM_실외기 IM 구주향(ET) ErP 규제_EN_DB68-07586A-02.indd 15 2018-02-20 오후 2:08:12
16
Preparing for installation
Model name for combination
AM680NXVGGH4ET AM700NXVGGH4ET AM720NXVGGH4ET AM740NXVGGH4ET AM760NXVGGH4ET AM780NXVGGH4ET AM800NXVGGH4ET
Number of individual outdoor units
4 4 4 4 4 4 4
Combined
outdoor unit
AM080JXVHGH/ET
AM100JXVHGH/ET
AM120JXVHGH/ET
AM140NXVHGH/ET
1 1
AM160NXVHGH/ET
AM180NXVHGH/ET
3 2 4 3 2 1
AM200NXVHGH/ET
1 1 2 3 4
AM220NXVHGH/ET
AM240KXVGGH/ET
AM260KXVGGH/ET
Total capacity
of the
connected
indoor units
Minimum (kW) 95.6 98.4 100.8 103.6 106.4 109.2 112.0
Maximum (kW) 248.6 255.8 262.1 269.4 276.6 283.9 291.2
Maximum number of connectable
indoor units
64 64 64 64 64 64 64
Essential type (Heat pump)
Model name for combination
AM100MXVDGH/ET AM120MXVDGH/ET AM140MXVDGH/ET AM160MXVDGH/ET AM180MXVDGH/ET AM200MXVDGH1ET
Number of individual outdoor units
1 1 1 1 1 2
Combined
outdoor unit
AM100MXVDGH/ET
1 2
AM120MXVDGH/ET
1
AM140MXVDGH/ET
1
AM160MXVDGH/ET
1
AM180MXVDGH/ET
1
Totalcapacityof
the connected
indoor units
(Cooling)
Minimum (kW)
14.0 16.8 20.0 22.5 25.2 28.0
Maximum (kW)
36.4 43.7 52.0 58.5 65.5 72.8
Maximum numberofconnectable
indoor units
18 21 26 29 32 36
DVM_실외기 IM 구주향(ET) ErP 규제_EN_DB68-07586A-02.indd 16 2018-02-20 오후 2:08:13
17
ENGLISH
Model name for combination
AM220MXVDGH1ET AM240MXVDGH1ET AM260MXVDGH1ET AM280MXVDGH1ET AM300MXVDGH1ET AM320MXVDGH1ET
Number of individual outdoor units
2 2 2 2 2 2
Combined
outdoor unit
AM100MXVDGH/ET
1
AM120MXVDGH/ET
1 2 1 1
AM140MXVDGH/ET
1 2 1
AM160MXVDGH/ET
AM180MXVDGH/ET
1 1
Totalcapacityof
the connected
indoor units
(Cooling)
Minimum (kW)
30.8 33.6 36.8 40.0 42.0 45.2
Maximum (kW)
80.1 8 7.4 95.7 104.0 109.2 117.5
Maximum numberofconnectable
indoor units
40 43 47 51 54 58
Model name for combination
AM340MXVDGH1ET AM360MXVDGH1ET AM380MXVDGH1ET AM400MXVDGH1ET
Number of individual outdoor units
2 2 3 3
Combined
outdoor unit
AM100MXVDGH/ET
AM120MXVDGH/ET
2 1
AM140MXVDGH/ET
1 2
AM160MXVDGH/ET
1
AM180MXVDGH/ET
1 2
Totalcapacityof
the connected
indoor units
(Cooling)
Minimum (kW)
47.7 50.4 53.6 56.8
Maximum (kW)
124.0 131.0 139.4 147.7
Maximum numberofconnectable
indoor units
61 64 64 64
DVM_실외기 IM 구주향(ET) ErP 규제_EN_DB68-07586A-02.indd 17 2018-02-20 오후 2:08:13
18
Preparing for installation
Premium compact type (Heat recovery)
Model name for combination
AM080JXVHGR/ET AM100JXVHGR/ET AM120JXVHGR/ET AM140NXVHGR/ET AM160NXVHGR/ET AM180NXVHGR/ET
Number of individual outdoor units
1 1 1 1 1 1
Combined
outdoor unit
AM080JXVHGR/ET
1
AM100JXVHGR/ET
1
AM120JXVHGR/ET
1
AM140NXVHGR/ET
1
AM160NXVHGR/ET
1
AM180NXVHGR/ET
1
AM200NXVHGR/ET
AM220NXVHGR/ET
AM240MXVGNR/ET
AM260MXVGNR/ET
Totalcapacityof
the connected
indoor units
(Cooling)
Minimum (kW)
11.2 14.0 16.8 20.0 22.5 25.2
Maximum (kW)
29.1 36.4 43.7 52.0 58.5 65.5
Maximum numberofconnectable
indoor units
14 18 21 26 29 32
Model name for combination
AM200NXVHGR/ET AM220NXVHGR/ET AM240MXVGNR/ET AM260MXVGNR/ET AM280NXVGNR3ET AM300NXVGNR3ET
Number of individual outdoor units
1 1 1 1 2 2
Combined
outdoor unit
AM080JXVHGR/ET
AM100JXVHGR/ET
AM120JXVHGR/ET
1 1
AM140NXVHGR/ET
AM160NXVHGR/ET
1
AM180NXVHGR/ET
1
AM200NXVHGR/ET
1
AM220NXVHGR/ET
1
AM240MXVGNR/ET
1
AM260MXVGNR/ET
1
Totalcapacityof
the connected
indoor units
(Cooling)
Minimum (kW)
28.0 30.8 33.6 36.4 39.3 42.0
Maximum (kW)
72.8 80.1 8 7. 4 94.6 102.2 109.2
Maximum numberofconnectable
indoor units
36 40 43 47 51 54
DVM_실외기 IM 구주향(ET) ErP 규제_EN_DB68-07586A-02.indd 18 2018-02-20 오후 2:08:13
19
ENGLISH
Model name for combination
AM320NXVGNR3ET AM340NXVGNR3ET AM360NXVGNR3ET AM380NXVGNR3ET AM400NXVGNR3ET AM420NXVGNR3ET
Number of individual outdoor units
2 2 2 2 2 2
Combined
outdoor unit
AM080JXVHGR/ET
AM100JXVHGR/ET
AM120JXVHGR/ET
1 1 1 1
AM140NXVHGR/ET
AM160NXVHGR/ET
AM180NXVHGR/ET
AM200NXVHGR/ET
1 2 1
AM220NXVHGR/ET
1 1
AM240MXVGNR/ET
1
AM260MXVGNR/ET
1
Totalcapacityof
the connected
indoor units
(Cooling)
Minimum (kW)
44.8 4 7.6 50.4 53.2 56.0 58.8
Maximum (kW)
116.5 123.8 131.0 138.3 145.6 152.9
Maximum numberofconnectable
indoor units
58 61 64 64 64 64
Model name for combination
AM440NXVGNR3ET AM460NXVGNR3ET AM480NXVGNR3ET AM500NXVGNR3ET AM520NXVGNR3ET AM540NXVGNR3ET
Number of individual outdoor units
2 2 2 2 2 3
Combined
outdoor unit
AM080JXVHGR/ET
AM100JXVHGR/ET
AM120JXVHGR/ET
1
AM140NXVHGR/ET
AM160NXVHGR/ET
1
AM180NXVHGR/ET
AM200NXVHGR/ET
1 1
AM220NXVHGR/ET
1
AM240MXVGNR/ET
1 1
AM260MXVGNR/ET
1 1 1 2 1
Totalcapacityof
the connected
indoor units
(Cooling)
Minimum (kW)
61.6 64.4 67. 2 70.0 72.8 75.7
Maximum (kW)
160.2 167.4 174.7 182.0 189.3 196.8
Maximum numberofconnectable
indoor units
64 64 64 64 64 64
DVM_실외기 IM 구주향(ET) ErP 규제_EN_DB68-07586A-02.indd 19 2018-02-20 오후 2:08:13
20
Preparing for installation
Model name for combination
AM560NXVGNR3ET AM580NXVGNR3ET AM600NXVGNR3ET AM620NXVGNR3ET AM640NXVGNR3ET AM660NXVGNR3ET
Number of individual outdoor units
3 3 3 3 3 3
Combined
outdoor unit
AM080JXVHGR/ET
AM100JXVHGR/ET
AM120JXVHGR/ET
1 1 1 1 1
AM140NXVHGR/ET
1
AM160NXVHGR/ET
AM180NXVHGR/ET
1
AM200NXVHGR/ET
1
AM220NXVHGR/ET
1
AM240MXVGNR/ET
1
AM260MXVGNR/ET
1 1 1 1 2 2
Totalcapacityof
the connected
indoor units
(Cooling)
Minimum (kW)
78.4 81.2 84.0 86.8 89.6 92.8
Maximum (kW)
203.8 211.1 218.4 225.7 233.0 241.3
Maximum numberofconnectable
indoor units
64 64 64 64 64 64
Model name for combination
AM680NXVGNR3ET AM700NXVGNR3ET AM720NXVGNR3ET AM740NXVGNR3ET AM760NXVGNR3ET AM780NXVGNR3ET AM800NXVGNR3ET
Number of individual outdoor units
3 3 3 3 3 3 4
Combined
outdoor unit
AM080JXVHGR/ET
AM100JXVHGR/ET
AM120JXVHGR/ET
1
AM140NXVHGR/ET
AM160NXVHGR/ET
1 1
AM180NXVHGR/ET
1
AM200NXVHGR/ET
1
AM220NXVHGR/ET
1
AM240MXVGNR/ET
1
AM260MXVGNR/ET
2 2 2 2 2 3 2
Totalcapacityof
the connected
indoor units
(Cooling)
Minimum (kW)
95.3 98.0 100.8 103.6 106.4 109.2 112.1
Maximum (kW)
247.8 254.8 262.1 269.4 276.6 283.9 291.5
Maximum numberofconnectable
indoor units
64 64 64 64 64 64 64
DVM_실외기 IM 구주향(ET) ErP 규제_EN_DB68-07586A-02.indd 20 2018-02-20 오후 2:08:13
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124

Samsung AM140KN4DEH/EU Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI