Installation Instructions for 116DEXSTC-FJ AdaptaBeacon
®
Fire Alarm Strobe Lights for Use in Hazardous Locations
DescriptionDescription
DescriptionDescription
Description
The 116DEXSTC-FJ AdaptaBeacon is an in-rush current lim-
ited strobe light. When pendant, wall or ceiling mounted,
it is UL1971 Listed Signaling Appliance for the Hearing
Impaired. Stanchion mount models are UL 1638 Listed
for Private Mode Emergency Signaling. All models are
CSFM Listed.
The strobe is intended for indoor use in UL listed
compatiable fire alarm systems and other applications re-
quiring electrical supervision of signaling circuit field wir-
ing. This strobe flashes a 360-degree beam of light ap-
proximately 65 times per minute with a UL 1971 60 cd
wall and ceiling light output per Figure 7.
When assembled in accordance with these instructions,
the 116DEXSTC-FJ visual strobe signal is UL Listed for use
in Class I, Division 1, Groups C and D, Class I, Division 2,
Groups A, B, C and D, Class II Division 1, Group E, F and G,
Class II, Division 2, Group F and G, and Class III Division 1
and 2 hazardous locations with Operating Temperature
Codes per the following chart. See Table 1 for Electrical
Specifications.
This strobe is UL and cUL Listed as a Type 3R and 4X enclo-
sure. See Figure 1.
InstallationInstallation
InstallationInstallation
Installation
Install this unit in accordance with the applicable require-
ments in the latest edition of the National Fire Alarm Code
(NFPA 72), National Electrical Code (NFPA 70), and Cana-
dian Electrical Code.
a. Pendant Mount Models (Figure 2): Install the
catalog number 116EX-P, pendant mounting
module, to the main housing. Install explosion-
proof hanger box (not supplied). Secure 3/4" (19
mm) NPT threaded conduit (not supplied) to the
box. Install the unit on the conduit. Proceed to
step 2.
b. Ceiling Mount Models (Figure 3): Mount the
catalog number 116EX-C, ceiling/wall mounting
module, using appropriate hardware (not supplied)
suitable for the mounting surface. Proceed to step
2.
c. Bracket Mount Models (Figure 4): Install the
catalog number 116EX-C ceiling/wall mouting
module using appropriate hardware (not supplied)
for the mounting surface. Install the catalog
number 116EX-B wall mounting elbow to the wall
box. Run the unit's wiring through the elbow to
the wall box. Proceed to step 2.
d. Stanchion Mount Models (Figure 5): Install the
catalog number 116EX-S, stanchion mounting
module, to the main housing. Run the unit's wires
through the 1 1/4" conduit to the appropriate
junction box. Install the unit on the conduit.
Proceed to step 2.
2. Connect field earth ground wire to ground screw or
earth ground via conduit system.
3. Wire the unit in accordance with Figure 6. See Table
3 for required supply wire temperature ratings.
4. As appropriate, install the fixture on the mounting
module.
WARNING
To reduce the risks of ignition of hazardous atmo-
spheres and shock, do not apply power to the unit
until installation has been completed and unit is
tightly assembled and secured.
1. Mount using the following applicable method.
5. Apply power to the unit and ensure proper function.
WARNING
To reduce the risk of ignition of hazardous atmo-
spheres and shock, keep assembly tightly closed
when circuits are energized.
P/N 3100759 ISSUE 1 © 2004
Cheshire, CT 06410 203-699-3300 (Ph)
203-699-3365 (Cust. Serv. Fax)
203-699-3078 (Tech. Serv. Fax)
STANCHION
116EX-S 1 1/4" HUB
CEILING
116EX-C 3/4" HUB
PENDANT
116EX-P 3/4" HUB
116EX-C
116 SERIES HOUSING AND GLOBE
ASSEMBLY WITH GUARD
WALL
116EX-B 3/4" HUB
Figure 1. Mounting Options
P/N 3100759 ISSUE 1
Figure 2. Detail of Pendant Mounting Figure 3. Detail of Ceiling Mounting
Figure 4. Detail of Wall Bracket Mounting Figure 5. Detail of Stanchion Mounting
12"
12 3/4"
7 1/4"
1"
13"
13 3/4"
7 1/4"
5/16"
4"
4"
6 3/4"
1/4"
1 1/4"
Conduit
13 1/4"
12 3/4"
13 1/2"
Figure 6. Wiring Diagram
NOTE: For non-fire alarm use, i.e. without field wire supervision, installer can tie the two white leads
together and tie the two black leads together.
5/16"
4"
4"
6 3/4"
1"
12 9/16"
9 7/16"
16 1/16"
16 13/16"
NOTE: DC polarity of circuit shown in supervisory state (signal inactive). Circuit polarity to reverse to activate signal.
Electrical supervision requires wire run to be broken at each device.
Device for constant input voltage. Do not connect to “coded” or pulsating voltage.
From Power Source
or
Previous Signaling Device
End-of-Line Resistor,
when required with
supervised system
KEY:
Light symbol -
Wire nut symbol -
(+)
White
(+)
White
(+)
White
(+)
White
Black
(-)
Black
(-)
Black
(-)
Black
(-)
Series
116DEX
Series
116DEX
(+)
(-)
NOTE: Not for use as a Public Mode Fire Alarm
Signal
P/N 3100759 ISSUE 1
MaintenanceMaintenance
MaintenanceMaintenance
Maintenance
Disassemble the unit as follows (Figure 8):
2. Loosen the globe and ring assembly set screw. Insert
a suitable tool into the notches in the globe and ring
assembly and loosen the assembly by prying in a
counterclockwise direction. Remove the ring and
globe assembly.
3. Refer to Table 2 for the correct replacement catalog
number and replace the necessary part.
4. To replace, simply screw the unit on until it seats firmly
onto its gasket. Tighten the unit another 1/8 to 1/4
turn. Tighten the setscrew.
5. Reinstall the guard, where applicable, and secure using
the three supplied screws.
6. After the unit is assembled, apply power and make
sure the unit functions properly.
1. Loosen the (3) guard screws and remove the guard.
WARNING
To reduce the risk of ignition of hazardous atmo-
spheres and shock, keep assembly tightly closed
when circuits are energized.
To reduce the risk of ignition of hazardous atmo-
spheres and shock, disconnect from the supply and
circuit and allow five (5) minutes for stored energy to
dissipate before disassembling the unit.
Table 1. 116DEXSTC-FJ AdaptaBeacon Strobe Light
Electrical Specifications
Max RMS Operating
Voltage Designation* Current (A)**
Regulated 24V DC 0.802
Regulated 24V FWR 1.140
CAUTION: To prevent damage to the signal circuit and to
otherwise assure continued proper functioning, DO NOT
operate the unit outside of the Regulated 24V DC/FWR
voltage range of 16 - 33V DC/V FWR.
*The designation Regulated 24 refers to the voltage range of 16
- 33 volts.
**The Max RMS Operating Current is defined as the current
rating over the entire voltage range.
Table 2. 116DEXSTC-FJ
Catalog Electrical Conduit Flash Strobe Tube
Description Number Ratings Size Rate Replacement
Housing Less 116DEXSTC-FJ 16 - 33V DC N/A Approx. 92-ST
Mounting Module 0.802/1.104A 65 fpm
Ceiling/Wall 116EX-C N/A 3/4" NPT N/A N/A
Mounting Module
Pendant 116EX-P N/A 3/4" NPT N/A N/A
Mounting Module
Stanchion 116EX-S N/A 1 1/4" NPT N/A N/A
Mounting Module
Wall Bracket 116EX-W N/A N/A N/A N/A
Mounting Elbow
Table 3. Ratings
Operating Temperature
Ambient Supply Wire Class I, Div. 2 Class I, Div. 1 & 2 Class II & III, Div. 1 Class II & III, Div. 2
Temp. Temp. Marking Groups A, B Groups C, D Groups E, F, G Group F, G
40°C 75°C T2D (215°C) T6 (85°C) T4A (120°C) T4A (120°C)
55°C 90°C T2C (230°C) T6 (85°C) T4 (135°C) T4 (135°C)
P/N 3100759 ISSUE 1
WALL
BRACKET
MOUNTING
ANGLE
(DEGREES)
VERTICAL
PLANE
HORIZONTAL
PLANE
zero 100% 100%
590%90%
10 90% 90%
15 90% 90%
20 90% 90%
25 90% 90%
30 90% 75%
35 65% 75%
40 46% 75%
45 34% 75%
50 27% 55%
55 22% 45%
60 18% 40%
65 16% 35%
70 15% 35%
75 13% 30%
80 12% 30%
85 12% 25%
90 12% 25%
Compound
45
24%
UL1971 REQUIRED
DISPERSION AS % OF CD
RATING
CEILING
MOUNTING
ANGLE
(DEGREES)
0 100%
590%
10 90%
15 90%
20 90%
25 90%
30 75%
35 75%
40 75%
45 75%
50 55%
55 45%
60 40%
65 35%
70 35%
75 30%
80 30%
85 25%
90 25%
Compound 45 24%
UL1971
REQUIRED
X & Y PLANE
DISPERSION
AS % OF CD
RATING
Figure 7. Light Output Patterns for 116DEXSTC-FJ
Effective Candela Light Output for Wall Bracket Mount
Vertical Plane
(Zero degree angle at side of globe)
Effective Candela Light Output for Ceiling Mount
X & Y Planes
(Zero degree angle at bottom of of globe)
UL 1971 Hearing Impaired: 60 cd wall
UL 1971 Hearing Impaired: 60 cd ceiling
0
10
20
30
40
50
60
70
80
90
100
110
120
130
-90
-85
-80
-75
-70
-65
-60
-55
-50
-45
-40
-35
-30
-25
-20
-15
-10
-5
0 degrees
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
TYPICAL CD
UL REQUIRED CD
FOR 35 RATING
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
180
175
170
165
160
155
150
145
140
135
130
125
120
115
110
105
100
95
90
85
80
75
70
65
60
55
50
45
40
35
30
25
20
15
10
5
degrees 0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
135
140
145
150
155
160
165
170
TYPICAL CD
UL REQUIRED CD
FOR 55 RATING
P/N 3100759 ISSUE 1
Figure 8. Disassembly of the 116DEXSTC-FJ AdaptaBeacon
Strobe Tube
Globe & Ring
Assembly
Guard
CAUTION: Wait 5 minutes for strobe energy to dissipate
prior to disassembly.
Contacting Edwards:
Phone: (203) 699-3300
Website: http://www.edwards-signals.com