C
Y
0
W2
R
E
T1
T2
C
Y
0
0
W2
RDFTE
DF1
DF2
Defrost Control Board
RT
LEFT
T1
T2
L2
L1
Single Phase
Field Supply
Grounding
Lug
High Press.
Switch
Compressor
Start Capacitor
Defrost
Thermostat
Reversing Valve
Solenoid
CoreSense
H
C
T1
T2
T3
CCH
ECM
ECM WIRING NOTES:
1) FOR 825 RPM ATTACH WHITE TO RIGHT CONTACTOR. (FOR SKUS 919660,919661,919662,919664)
2) FOR 960 RPM ATTACH YELLOW TO RIGHT CONTACTOR. (FOR SKU 919663)
3) FOR 1100 RPM ATTACH WHITE AND YELLOW TO RIGHT
CONTACTOR.
P
Y
C
R
Start
Relay
1
5
2
YELLOW/BLACK
BLACK
BLACK
YELLOW
RED
RED
RED
BLACK
BLACK
RED
BLACK
BROWN
BLACK
WHITE
YELLOW
SEE ECM WIRING NOTES
BLUE
Route this wire
through CoreSense
YELLOW/BLACK
Grounding
Lug
GRAY
RED
YELLOW
BLACK
BLUE
BLACK
Split System Heat Pump (Outdoor Section)
Single Phase
WIRING DIAGRAM
NOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 volts to ground.
4. For replacement wires use conductors suitable for 105˚C.
Defrost Board Operation:
1. Closing during defrost. Rating: 1 Amp.Max
2. Opens during defronst. Rating: 2HP at 230 Vac Max.
3. Closed when “Y” is on. Open when “Y” is off.
Provides “off” delay time of 5 min. when “Y” opens.
4. With DFT closed and “Y” closed, compressor run
time is accumulated. Opening of DFT during
defrost or interval period resets the interval to 0.
CC - Contactor Coil
CCH - Crankcase Heater
DFT - Defrost Thermostat
HPS - High Pressure Switch
RVS - Reversing Valve Selenoid
* - Hard Start Kit Field Installed
711205
1. Couper le courant avant de faire letretien.
2. Employez uniquement des conducteurs en cuivre.
3. Ne convient pas aux installations de plus de 150 volt a la terre.
FIELD WIRING
LEGEND:
LOW VOLTAGE
HIGH VOLTAGE
Low Voltage
Terminals
E
Defrost Control Board
DFT
Control
Logic
DF1
DF2
DFT
1
2
3
4
1
R
W2
O
Y
C
T2
T1
R
W2
O
Y
C
RVS
HPS
R
P
C
Y
CoreSense
CC
Compressor
R
C
S
HC
CCH
L1
T1
L2
T2
Compressor
Contacts
ECM
208/230V
Instructions for control circuit and optional relay/transformer kit.
Normal Operation, no trip
CoreSense Status LED
Normal Run; Solid Yellow
N/A N/A
N/A N/A
N/A N/A
4 cons, 10x total
4 cons, 10x total
4 cons, 10x total
1 Occurrence
10 consecutive
Red: Flash 2
Red: Flash 3
Red: Flash 4
Red: Flash 5
Red: Flash 9
Code 1; Yellow Flash 1
Code 2; Yellow Flash 2
Code 3; Yellow Flash 3
Code 4; Yellow Flash 4
Long Run Time. Compressor running extremely long run cycle. (disabled in HP mode.)
noitacidnI tuokcoLleveL tuokcoLnoitpircseD DEL sutatS
Comprsesor Pressure Trip. Disch. or suct. pressure out of limits or compressor overloaded.
Short Cycling. Compressor is running only briefly.
Locked Rotor.
Code 5; Yellow Flash 5 Compressor Moderate Run. Compressor runs >15min, then trips >7min.
Code 9; Red Flash 19 Over Current Protection. PROT terminal has >2A input for more than 40ms
Trip; Solid Red Demand but compressor is not running
5. For ampacitities and overcurrent protection, see
unit rating plate.
6. Connect to 24 vac/40va/class 2 circuit. See
Furnace/air handler installation instructions for
control circuit and optional relay/transformer kits.
01/13