18 GMC-I Gossen-Metrawatt GmbH
Current Measurement Tips:
• The measuring circuit must be mechanically stable and
protected against unintentional interruption. Conductor
cross sections and connection points must be substan-
tial enough to avoid excessive overheating.
• In the 300 mA and 10 A measuring ranges an intermit-
tent acoustic signal warns you, if the measurement value
has exceeded the measuring range upper limit value.
• Current ranges up to 300 mA are protected with a
FF (UR) 1.6 A/1000 V AC/DC fuse in combination with
power diodes up to a short-circuit current of 25 A. The
breaking capacity of the fuse is equal to 10 kA at a nom-
inal voltage of 1000 V AC/DC with resistive load.
• Measuring ranges up to 10 A are protected with a
FF (UR) 16 A/1000 V AC/DC fuse. The breaking capacity
of the fuse is equal to 30 kA at a nominal voltage of
1000 V AC/DC with resistive load.
• If the fuse for the active current measuring range is
defective, “FUSE” appears at the digital display and an
acoustic signal sounds simultaneously.
• If a fuse blows, eliminate the cause of the overload
before placing the instrument back into operation!
• Fuse replacement is described in
chapter 25.2, page 56.
9.1 AC Measurement with Current Transformers
9.1.1 mA or A Transformer Output
(METRA HIT 23/24/25/26)
If a (clip-on) current transformer is connected to the multi-
meter (mA or A input), all current indicators are displayed in
accordance with the selected transformation ratio. How-
ever, the current transformer must have a transformation
ratio of either 1000:1 or 10000:1, and the transformation
ratio must be selected in the following menu.
Current Clip Setup Menu:
SEt ↵ CLIP ↵ oFF 1000 10000 ↵.
If you have selected 1000 or 10000 in the menu, you can
switch back and forth between two different current dis-
plays with the help of the ESC|FUNC key:
The selected transformation ratio is only taken into consid-
eration if a preceding c: is entered (c for clip).
Attention!
!
If current transformers are used at the secondary
side in an open condition, e.g. due to defective or
non-connected power cables, a blown device fuse
or incorrect connection, dangerously high voltages
can occur at the terminals. For this reason, check to
see if the measuring instrument’s current path and
transformer’s secondary winding, which is con-