ROUND TOp TeRmiNaTiONs
iNsTallaTiON iNsTRUcTiONs
RLT-8DM(HT), RLTT-8DM(HT) AND RLTL-8DM(HT)
Note: For nonchase installation see other side.
1. Construct chase as illustrated in Figure 1 (RLTT-8 Series
only) or Figure 2 (RLT(L)-8 Series only).
Note: The shortest vertical side must be at least 30" high
and the minimum inside dimension must be at least “Y”
(as shown in Figure 7).
2. Addpipesectionstochimneysystemasoutlinedinre-
place installation instructions until the last piece of chimney
is a maximum of 12" below top of chase for RLTT-8 Series
Only (see Figure 1), or a minimum of 6" above chase top
for RLT(L)-8 Series Only (see Figure 2).
3. Fabricateaashinghavinga14"diameterholecentered
over chimney end with a 2" collar around hole (see Figure
3). Attach noncombustible spacers at each corner and
placeashingoverchase.
Figure 1 - Constructing Chase (RLTT-8 Series Only)
Figure 3 - Constructing Chase Top Flashing
As Required
28 Gauge
Galvanized Steel
14"
Diameter
Figure 2 - Constructing Chase (RLT(L)-8 Series Only)
Figure 4 - Installing Termination Cap (RLTT-8 Series Only)
Termination Cap
1" Spacer
Note: Do Not Seal Ventilation Openings.
Storm
Collar
Caulk
Chase
Chase Top
Flashing
1" Space
Double Wall
Chimney
Flashing
2" Collar
6"
Termination Cap
1" Spacer
Note: Do Not Seal Ventilation Openings.
Storm Collar
Caulk
Chase
Chase Top
Flashing
1" Space
Double Wall
Chimney
Flashing
Sheet Metal Screw
Figure 5 - Installing Termination Cap (RLT(L)-8 Series Only)
6"
4. Secureashingthroughsideswith8-pennynailsorsheet
rock screws.
5. Attach storm collar where chimney pierces opening in
ashing.Caulkwherestormcollartouchesouterchim-
neypipe(seeFigure4forRLTT-8SeriesorFigure5for
RLT(L)-8 Series).
6. Place termination cap over opening. Slip 8" stainless
steel inner pipe into stainless steel chimney section.
Lower termination assembly until cap legs clip into outer
chimney pipe. Secure legs of cap with sheet metal screws
(seeFigure4forRLTT-8SeriesorFigure5forRLT(L)-8
Series).