Acuity Brands NaviLite N1L Installation guide

Type
Installation guide
FOR LED EMERGENCY LIGHTING FIXTURE
One Lithonia Way, Conyers GA 30012 Phone: 800-334-8694
©2016 Acuity Brands Lighting, Inc. Printed in the USA Rev 8/2017 P3508 pg 1 of 3
INSTALLATION INSTRUCTIONS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
IMPORTANT SAFEGUARDS:
SAVE THESE INSTRUCTIONS
IMPORTANT: Let the battery charge up for at least 24 hours. Then normal operation of this unit should take
effect. To check, press the “TEST” button. The LED lamps on the unit should turn ON. During an electrical
power failure, the led lamps will automatically come on for a minimum of 90 minutes. In accordance with
NFPA 101, your emergency lighting system must be tested monthly for a minimum of 30 seconds and
annually for 90 minutes. Refer to your local codes for any additional requirements that may apply.
WARNING: FAILURE TO FOLLOW THESE INSTRUCTIONS AND WARNINGS MAY RESULT IN
DEATH, SERIOUS INJURY OR SIGNIFICANT PROPERTY DAMAGE - For your protection, read and follow
these warnings and instructions carefully before installing or maintaining this equipment. These instructions
do not attempt to cover all installation and maintenance situations.
WARNING: RISK OF FIRE - Lamps are hot. Keep combustible material away from hot parts. Observe lamp
manufacture’s warnings, recommendations and restrictions on lamp operation and maintenance. Make sure
lamps are correctly installed.
All service shall be performed by qualified service personnel. This product must be installed and
maintained in accordance with the applicable installation codes by a person familiar with the construction
operation of the product and the hazards involved.
This product must be installed in accordance with the applicable installation codes and ordinances.
Before wiring to power supply, turn off electricity at fuse or circuit breaker.
Disconnect A.C. power and unplug battery before servicing.
Consult your local building code for approved wiring and installation.
May be used outdoors under cover. (0°C-50°C).
Do not let power supply cord touch hot surfaces.
Do not mount near gas or electric heater.
Equipment should be mounted in locations and at heights where it will not readily be subjected to
tampering by unauthorized personnel.
The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
Do not use this equipment for other than intended use.
The AC voltage rating of this equipment is specified on the product label.
Do not connect equipment to any other voltage.
FOR LED EMERGENCY LIGHTING FIXTURE
©2016 Acuity Brands Lighting, Inc. Printed in the USA Rev 8/2017 P3508 pg 2 of 3
INSTALLATION INSTRUCTIONS
IMPORTANT: Let the battery charge up
for at least 24 hours. Then normal
operation of this unit should take effect.
To check, press the “TEST” button. The
LED lamps on the unit should turn ON.
During an electrical power failure, the led
lamps will automatically come on for a
minimum of 90 minutes. In accordance
with NFPA 101, your emergency lighting
system must be tested monthly for a
minimum of 30 seconds and annually for
90 minutes. Refer to your local codes for
any additional requirements that may
apply.
USE FLEXIBLE CONDUIT ONLY.
INSTALLATION
J-BOX MOUNTING
1. Feed fixture leads through the
back plate and connect to AC
power supply (Fig A). For 120V
use black and white wires and for
277V, use red and white wires.
2. Attach back plate to J-Box and
secure with screws.
3. Complete the battery connection.
(Fig. B)
4. Align snaps and push housing
directly onto the back plate (Fig.
C). Apply continuous AC power
and press “TEST” button to check
light.
CONDUIT
1. Secure back plate to wall surface.
Route wires through hole in
conduit flange and make conduit
connection. For 120V, use black
and white wires and for 277V, use
red and white wires.
2. Complete the battery connection
(Fig. B).
3. Align snaps and push housing
directly onto the back plate (Fig.
C). Apply continuous AC power
and press “TEST” button to check
light.
WARNING: Unused wires must be
capped using enclosed wire nuts.
FIG. A FIG. B
FIG. C
One Lithonia Way, Conyers GA 30012 Phone: 800-334-8694
FOR LED EMERGENCY LIGHTING FIXTURE
©2016 Acuity Brands Lighting, Inc. P3508 pg 3 of 3
INSTALLATION INSTRUCTIONS
OPERATION
1. During an electrical power failure, the LED lamps will automatically come on for a minimum of 90 minutes.
2. To test, depress the “TEST” switch. The emergency LED lamps will illuminate. When the switch is released, the
lamps will go off.
NOTE
1. Max mounting height 8 ft to achieve at least 1 ft-candle of illuminance in emergency mode.
Printed in the USA Rev 8/2017
One
Lithonia Way, Conyers GA 30012 Phone: 800-334-8694
STANDARD
HO OPTION (REMOTE CAPABLE)
BLUE(-)
YELLOW(+)
BLUE(-)
BLUE(-)
YELLOW(+)
LAMP
YELLOW(+)
LAMP
READY
TEST
BATTERY
Note:
Unused input lead must
be properly insulated with
wire nut or other approved
method.
RED
BLACK
RED
BLACK
WHITE
277V
120V
0V
CHARGER
BOARD
LAMP
READY
TEST
BATTERY
RED
BLACK
RED
BLACK
WHITE
277V
120V
0V
LAMP
YELLOW(+)
BLUE(-)
YELLOW(+)
BLUE(-)
CHARGER
BOARD
AC INPUT CONNECTOR
(MOUNTING PLATE)
AC INPUT CONNECTOR
(MOUNTING PLATE)
Note:
Use 18-22 AWG stranded
wire to connect remote lamp
heads.
TO REMOTE
WIRING DIAGRAM