Eaton 93E Operating instructions

Type
Operating instructions

This manual is also suitable for

Eaton 93E Battery Upgrade

The Eaton 93E Battery Upgrade is a cost-effective and easy-to-install solution for extending the runtime of your Eaton 93E UPS. With this upgrade, you can add up to 9 additional batteries to your UPS, providing up to 20 minutes of additional runtime at full load. The upgrade kit includes everything you need to install the additional batteries, including the batteries themselves, the wiring harness, and the mounting hardware.

Here are some of the benefits of the Eaton 93E Battery Upgrade:

  • Extended runtime: Provides up to 20 minutes of additional runtime at full load, giving you more time to save your work and shut down your system safely in the event of a power outage.

Eaton 93E Battery Upgrade

The Eaton 93E Battery Upgrade is a cost-effective and easy-to-install solution for extending the runtime of your Eaton 93E UPS. With this upgrade, you can add up to 9 additional batteries to your UPS, providing up to 20 minutes of additional runtime at full load. The upgrade kit includes everything you need to install the additional batteries, including the batteries themselves, the wiring harness, and the mounting hardware.

Here are some of the benefits of the Eaton 93E Battery Upgrade:

  • Extended runtime: Provides up to 20 minutes of additional runtime at full load, giving you more time to save your work and shut down your system safely in the event of a power outage.
p/n: P-164000967
Revision 01
Battery Upgrade Instructions
For use with the Eaton
®
93E (20–60 kVA)
Eaton Series
Eaton reserves the right to change specifications without prior notice. Eaton is a registered trademark of Eaton. All other trademarks are
property of their respective companies.
©Copyright 2020 Eaton, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the
express written approval of Eaton.
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during installation and maintenance
of the UPS and batteries. Please read all instructions before operating the equipment and save this
manual for future reference.
CONSIGNES DE SÉCURITÉ IMPORTANTES CONSERVER CES INSTRUCTIONS
Ce manuel comporte des instructions importantes que vous êtes invité à suivre lors de toute
procédure d'installation et de maintenance de la UPS. Veuillez consulter entièrement ces instructions
avant de faire fonctionner l'équipement et conserver ce manuel afin de pouvoir vous y reporter
ultérieurement.
Battery Upgrade Instructions for 93E (20–60 kVA) P-164000967—Rev 01 1
CChhaapptteerr 11 IInnttrroodduuccttiioonn
11..11 IInnttrroodduuccttiioonn
Upgrade kit P-106000220 facilitates replacing one existing two-row battery tray assembly with two single-row
battery assemblies.
The replacement trays contain nine batteries each, such that it takes two single-row trays to complete one
string. Each single-row battery tray has one circuit.
Each kit (P-106000220) includes two single-row battery trays and two harness adapters. Only one harness
adapter is needed for the installation; the second harness adapter is a spare.
Figure 1. Upgrade Kit P-106000220 (Two Cartons) Includes Two Single-Row Battery Trays and Two
Wiring Harness Adapters
Figure 2. Wiring Harness Adapter P-152001881
2 Battery Upgrade Instructions for 93E (20–60 kVA) P-164000967—Rev 01
Introduction
Battery Upgrade Instructions for 93E (20–60 kVA) P-164000967—Rev 01 3
CChhaapptteerr 22 UUppggrraaddee IInnssttrruuccttiioonnss
22..11 BBaatttteerryy UUppggrraaddee IInnssttrruuccttiioonnss
READ THIS ENTIRE PROCEDURE BEFORE PERFORMING ANY WORK
WARNING
This procedure involves interacting with components that may be energized.
Any and all work can involve hazards when working on electrical equipment. The work must be done in
accordance with all applicable local, federal, or other safety requirements and must be performed by qualified
personnel.
1. Review and inspect the parts within the battery upgrade kit (Part Number: P-106000220)
!
IMPORTANT
In the event of input power failure while performing this procedure, battery backup will not be available.
2. Follow the instructions in the Eaton 93E UPS Installation and Operation Manual to place the 93E UPS in
bypass and in maintenance bypass. However, if the UPS cannot be placed in maintenance bypass, this
procedure can still be performed.
3. Remove the UPS front panel door
4. Open breakers:
!
IMPORTANT
Ensure the UPS is in Maintenance Bypass before opening the Input and Bypass Breakers; otherwise a Load
Loss will occur.
Input Breaker
Bypass Breaker
Battery Breaker - Extended Battery Cabinet (EBC)
Battery Breaker - UPS (if EBC capable)
Module Output Breaker (if parallel configuration)
4 Battery Upgrade Instructions for 93E (20–60 kVA) P-164000967—Rev 01
Figure 3. Eaton 93E 30 kVA and 60 kVA UPS Breaker Locations
Input Breaker
Battery Breaker
(EBC capable
option only.)
93E 30 kVA UPS 93E 60 kVA UPS
5. Follow appropriate Lock Out /Tag Out (LOTO) and electrical safety procedures
6. Remove dead front panels:
30 kVA, upper and lower panels
60 kVA lower two panels
7. Disconnect all internal battery trays (note battery wiring configurations)
Battery Upgrade Instructions
Battery Upgrade Instructions for 93E (20–60 kVA) P-164000967—Rev 01 5
Figure 4. Eaton 93E 30 kVA and 60 kVA Battery Tray and Cabinet Wiring
WARNING
All battery trays must be disconnected before proceeding.
Battery Upgrade Instructions
6 Battery Upgrade Instructions for 93E (20–60 kVA) P-164000967—Rev 01
8. Follow appropriate protocols to verify the UPS is electrically isolated / de-energized by using a certified
Digital Multi-Meter to verify the absence of AC voltages within the UPS
9. Remove the internal battery trays and label them as “old”
10. Install all the new battery trays
!
IMPORTANT
Before connecting ANY battery trays, verify and orient yourself with ALL battery harnesses
11. Attach the Wiring Adaptor Harness to the existing UPS cabinet wiring harness for each battery shelf (one
shelf at a time) (red–to–red and black–to–black).
WARNING
The 2-circuit connectors should ALWAYS mate with a battery tray connector, NEVER with a 2-circuit connector
in another UPS harness. Arc-flash incident may occur when incorrectly mated.
a. Install the adapter on each UPS cabinet battery harness. Connect the adapter to the UPS cabinet
wiring harness (red–to–red and black–to–black).
Figure 5. Wiring Harness Adapter
Battery Upgrade Instructions
Battery Upgrade Instructions for 93E (20–60 kVA) P-164000967—Rev 01 7
Figure 6. Wiring Harness Connection Detail
Wiring Adapter
Harness
Black Black
White
Wire
Red Red
Black Black
Cabinet
Wiring
Harness
Battery Tray
Wiring
Battery Tray
Wiring
Red Red
Black Black
Red Red
Connector
Sleeving
*Battery Tray
Connection
Only
*Cabinet Harness
Connection Only
Battery Tray Shelf
Battery Tray Battery Tray Battery Tray Battery Tray
b. Verify the absence of DC voltage on the harness (use precautions when verifying the voltage readings)
Battery Upgrade Instructions
8 Battery Upgrade Instructions for 93E (20–60 kVA) P-164000967—Rev 01
Figure 7. Wiring Harness Adapter DC Voltage Testing
c. Slowly push the black sleeving over the cabinet harness Anderson connectors until centered
Tie wrap each end of the sleeving
Figure 8. Battery Wiring Adapter Harness Sleeving Detail
Tie Wraps
Cabinet
Wiring
Harness
Wiring Adapter
Harness
Connector
Sleeving
Battery Upgrade Instructions
Battery Upgrade Instructions for 93E (20–60 kVA) P-164000967—Rev 01 9
Figure 9. Connector Sleeving Installed
12. Repeat step 11 until all UPS cabinet battery harnesses are connected to a Wiring Harness Adapter
13. Once all of the UPS cabinet battery harnesses are connected to the Wiring Harness Adapter, proceed to
2.1.1 Internal Battery Voltage Polarity Verification Procedure
22..11..11 IInntteerrnnaall BBaatttteerryy VVoollttaaggee PPoollaarriittyy VVeerriiffiiccaattiioonn PPrroocceedduurree
!
IMPORTANT
Checking string polarity must be conducted separately for each battery string (pair of battery trays). These
checks also assure that all battery-to-battery jumpers in the battery tray assemblies are connected. Be sure to
disconnect the current battery tray pair before moving to the next pair. Strings should not be connected in
parallel until after each and every string polarity has been verified. Failure to do this could result in a serious arc-
flash injury
1. Utilizing one shelf at a time, attach the Wiring Harness Adapter to the left most battery string cables
Battery Upgrade Instructions
10 Battery Upgrade Instructions for 93E (20–60 kVA) P-164000967—Rev 01
Figure 10. Battery Wiring Adapter Connection to Battery Tray Cabling
Verify battery voltage polarity at the battery fuses (Gen 1 & 2) and the UPS battery breaker (Gen 3, top side
on the breaker). The measured voltage is around “+230vdc”
Battery Upgrade Instructions
Battery Upgrade Instructions for 93E (20–60 kVA) P-164000967—Rev 01 11
Figure 11. Eaton 93E 30 kVA UPS Fuse Location Detail
Battery Upgrade Instructions
12 Battery Upgrade Instructions for 93E (20–60 kVA) P-164000967—Rev 01
Figure 12. Eaton 93E 60 kVA UPS Fuse Location Detail
2. Disconnect the new harness from the right most battery string cables and connect the second new
harness to the left most battery string cables
Verify battery voltage polarity at the battery fuses (Gen 1 & 2) and the UPS battery breaker (Gen 3)
3. Disconnect the new harness from the left most battery string cables
4. Repeat these steps for the remaining battery shelves, once all battery strings have been successfully
tested, proceed to
22..11..22 BBaatttteerryy TTrraayy CCoonnnneeccttiioonn aanndd WWrraapp UUpp
1. Connect the new harnesses to the batteries for each shelf
2. Verify the battery voltage at the battery fuses (Gen 1 & 2) and battery breaker (Gen 3)
3. Before the battery dead front panel is reinstalled, the battery harnesses for each battery shelf must be
formed by hand
30 kVA
a. Push most of the battery harness between the right most battery and the frame
Battery Upgrade Instructions
Battery Upgrade Instructions for 93E (20–60 kVA) P-164000967—Rev 01 13
Figure 13. Eaton 93E 30 kVA UPS Battery Shelf Cabling Clean Up
b. Leave some stress relief for installing the battery dead front panel
c. Use tie wraps to help secure the battery harness
d. Press the battery harness as close to the batteries and next to the battery shelf (the red mark on
the battery is an example for the CSE to use as an example noting the shipping bracket lower
edge on the dead front panel)
e. Form the battery cables as close to the batteries and the shelf as possible
Use tie wraps as needed
60 kVA
a. Shelf 1 wire forming is different. Push most of the harness between the battery and the UPS
frame. Use tie wraps and tie wrap mounting pads as needed to anchor the battery harness to
ensure it is not touching the battery fuse nor the side frame of the UPS. (Gen 3 UPS are shipped
with tie wrap mounting pads)
Battery Upgrade Instructions
14 Battery Upgrade Instructions for 93E (20–60 kVA) P-164000967—Rev 01
Figure 14. Eaton 93E 60 kVA UPS Battery Shelf Cabling Clean Up
Leave some stress relief for installing the battery dead front panel
b. Repeat step “a” for the remaining battery shelves
c. Press the battery harness as close to the batteries and next to the battery shelf (the red mark on
the battery is an example [30 kVA] picture for the CSE to use as an example noting the shipping
bracket lower edge on the dead front panel)
d. Form the battery cables as close to the batteries and the shelf as possible
Use tie wraps as needed
Battery Upgrade Instructions
Battery Upgrade Instructions for 93E (20–60 kVA) P-164000967—Rev 01 15
4. Install the appropriate new wiring labels
30kVA, label P/N - P-138000552
60kVA, label P/N - P-138000553
5. Reinstall the battery dead front panel
As you install the panel, you may feel some slight resistance. The shipping bracket on the dead front panel
is pressing on the battery harness
Reinstall slowly to ensure you are not pinching any battery cables. If you feel as though it is too much
resistance, reform the wires and reinstall the dead front panel
6. Reinstall remaining dead front panels
7. Refer to the Eaton 93E UPS Installation and Operations Manual instructions to return the UPS to normal
and supporting the load
Battery Upgrade Instructions
P-16400096701
P-164000967 01
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18

Eaton 93E Operating instructions

Type
Operating instructions
This manual is also suitable for

Eaton 93E Battery Upgrade

The Eaton 93E Battery Upgrade is a cost-effective and easy-to-install solution for extending the runtime of your Eaton 93E UPS. With this upgrade, you can add up to 9 additional batteries to your UPS, providing up to 20 minutes of additional runtime at full load. The upgrade kit includes everything you need to install the additional batteries, including the batteries themselves, the wiring harness, and the mounting hardware.

Here are some of the benefits of the Eaton 93E Battery Upgrade:

  • Extended runtime: Provides up to 20 minutes of additional runtime at full load, giving you more time to save your work and shut down your system safely in the event of a power outage.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI