ABB PQFA User manual

Type
User manual
Instructions Manual PQFA
Power Quality Filter
ABB Jumet
PQFA Instructions Manual
__________________________________________________________________________
Asea Brown Boveri Jumet S.A.
2
Table of contents
1. SAFETY INSTRUCTIONS...................................................................................................................5
2. UPON RECEPTION ............................................................................................................................6
2.1. DELIVERY INSPECTION........................................................................................................................6
2.2. IDENTIFICATION TAG...........................................................................................................................6
2.3. STORAGE..........................................................................................................................................6
2.4. LONG STORAGE PERIOD AND REFORMING .............................................................................................6
3. PQFA PRINCIPLE AND CHARACTERISTICS....................................................................................7
3.1. REASONS FOR LIMITING HARMONICS .................................................................................................... 7
3.2. GENERAL PRINCIPLE OF ACTIVE FILTERING............................................................................................8
3.3. THE ABB ACTIVE FILTER: THE PQFA. .................................................................................................9
3.4. THE PQFA: PERFORMANCES............................................................................................................11
3.4.1. Filtering.................................................................................................................................11
3.4.2. Reactive power......................................................................................................................12
3.4.3. EMC......................................................................................................................................12
4. COMPONENTS DESCRIPTION AND IDENTIFICATION...................................................................13
4.1. COMPONENTS DESCRIPTION .............................................................................................................13
4.1.1. PQF current generator...........................................................................................................13
4.1.2. The control............................................................................................................................14
4.2. COMPONENTS IDENTIFICATION ..........................................................................................................15
5. MECHANICAL INSTALLATION........................................................................................................26
6. ELECTRICAL INSTALLATION .........................................................................................................29
6.1. OVERVOLTAGE ................................................................................................................................29
6.2. POWER CABLES AND EXTERNAL PROTECTION......................................................................................29
6.3. CURRENT TRANSFORMERS/CONTROL CABLES SELECTION.....................................................................32
6.4. CURRENT TRANSFORMERS INSTALLATION...........................................................................................34
6.4.1. CT’s connection to the PQFA.................................................................................................34
6.4.2. CT’s connection topology: cases............................................................................................36
6.4.2.1. Case 1: Global compensation – one feeding transformer........................................................................36
6.4.2.2. Case 2: Individual compensation – one feeding transformer...................................................................37
6.4.2.3. Case 3: global compensation – transformer busbar not accessible........................................................38
6.4.2.4. Case 4: two independent feeding transformers........................................................................................40
6.4.2.5. Case 5: back up generator.........................................................................................................................42
6.5. PRECAUTIONS WITH CAPACITORS ......................................................................................................43
7. CUBICLES INTERCONNECTIONS...................................................................................................44
7.1. INTRODUCTION ................................................................................................................................44
7.2. MECHANICAL INSTALLATION ..............................................................................................................44
7.3. ELECTRICAL CONNECTIONS...............................................................................................................45
7.3.1. Connections between cubicles...............................................................................................45
7.3.1.1. Power connection........................................................................................................................................45
7.3.1.2. Control connection......................................................................................................................................46
7.3.1.3. Domino boards connection.........................................................................................................................47
7.3.1.4. Earth connection.........................................................................................................................................48
7.3.2. Connections to the supply......................................................................................................48
7.3.2.1. Power connection........................................................................................................................................48
7.3.2.2. Protective earth...........................................................................................................................................48
8. PQF-PROG INSTALLATION AND PC CONNECTION ......................................................................50
8.1. SYSTEM REQUIREMENTS...................................................................................................................50
8.2. INSTALLING PQF-PROG ON YOUR PC................................................................................................50
PQFA Instructions Manual
__________________________________________________________________________
Asea Brown Boveri Jumet S.A.
3
HARDWARE CONNECTION..............................................................................................................................50
9. COMMISSIONING.............................................................................................................................51
9.1. STEP 1...........................................................................................................................................51
9.2. STEP 2...........................................................................................................................................51
9.3. STEP 3...........................................................................................................................................52
9.3.1. PQF connection diagram.......................................................................................................52
9.3.2. Material needed & hypotheses for correct measurements......................................................53
9.3.3. Checking the correct connection of the CTs with a two channel scopemeter...........................53
9.3.3.1. Measurement of CT in phase L1................................................................................................................53
9.3.3.2. Measurement of CT in phase L2 and L3...................................................................................................55
9.3.4. Checking the correct connection of the CTs with two current probes......................................56
9.3.5. Checking the correct connection of the CTs with a Fluke 41B.................................................56
9.4. STEP 4...........................................................................................................................................57
9.4.1. With PQF-Prog......................................................................................................................57
9.4.2. With the PQF-Manager..........................................................................................................58
9.5. STEP 5...........................................................................................................................................59
9.6. STEP 6...........................................................................................................................................59
9.7. STEP 7...........................................................................................................................................59
9.8. STEP 8...........................................................................................................................................59
10. OPERATION.....................................................................................................................................61
10.1. NORMAL WORKING SEQUENCE ..........................................................................................................61
10.2. OPERATION WITH CAPACITORS..........................................................................................................66
10.3. BEHAVIOR IN CASE OF POWER OUTAGE ..............................................................................................66
10.4. BUTTONS, LIGHTS AND LED’S SIGNIFICATION......................................................................................67
10.4.1. Master cubicle.......................................................................................................................67
10.4.2. Slave cubicle.........................................................................................................................67
10.4.3. PQF-Manager........................................................................................................................68
10.4.4. Control rack...........................................................................................................................69
10.5. PROGRAMMING WITH PQF-PROG......................................................................................................70
10.5.1. Filter operation principle.........................................................................................................70
10.5.2. Starting..................................................................................................................................71
10.5.3. Programming the filter............................................................................................................73
10.6. PROGRAMMING WITH PQF-MANAGER................................................................................................75
10.6.1. Filter operation principle.........................................................................................................75
Keys identification..............................................................................................................................76
10.6.3. Programming the filter............................................................................................................77
10.7. PQFA AND NETWORK MONITORING WITH THE PQF-MANAGER..............................................................81
10.7.1. Filter status............................................................................................................................81
10.7.2. Network status.......................................................................................................................82
10.7.3. Waveform..............................................................................................................................83
10.7.4. Spectrum...............................................................................................................................84
10.8. REMOTE CONTROL AND ALARM CONTACT............................................................................................85
10.8.1. Remote control......................................................................................................................85
10.8.2. Alarm contact.........................................................................................................................86
10.9. PROTECTIONS .................................................................................................................................86
11. FAULT HANDLING AND TROUBLESHOOTING ..............................................................................88
11.1. FAULT HANDLING .............................................................................................................................88
11.1.1. Type of faults.........................................................................................................................88
11.1.2. Fault handling and fault clearance procedure.........................................................................88
11.2. TROUBLESHOOTING .........................................................................................................................91
11.2.1. Frequent problems occurring at commissioning stage............................................................91
11.2.2. Error codes meaning..............................................................................................................91
11.2.3. Faults not related to error codes.............................................................................................95
11.2.4. Restarting the filter after fault correction.................................................................................95
PQFA Instructions Manual
__________________________________________________________________________
Asea Brown Boveri Jumet S.A.
4
12. MAINTENANCE................................................................................................................................96
12.1. MAINTENANCE FREQUENCY...............................................................................................................96
12.2. MAINTENANCE PROCEDURE ..............................................................................................................96
12.3. FAN................................................................................................................................................97
12.4. CAPACITORS REFORMING .................................................................................................................97
PQFA Instructions Manual
Asea Brown Boveri Jumet S.A.
5
1. Safety instructions
These safety instructions are intended for all work on the PQFA.
Neglecting these instructions can cause physical injury and death.
All electrical installation and maintenance work on the PQFA should be
carried out by qualified electricians.
Do not attempt to work on a powered PQFA.
After switching off the mains, always wait at least 5 minutes before
working on the unit in order to allow the discharge of DC capacitors
through the discharge resistors.
DC capacitors might be charged to more than 1000V.
Before manipulating current transformers, make sure that the secondary
is short-circuited. Never open the secondary of a loaded current
transformer.
You must always wear isolating gloves and eye-protection when
working on electrical installation. Also make sure that all local safety
regulations are fulfilled.
PQFA Instructions Manual
Asea Brown Boveri Jumet S.A.
6
2. Upon reception
2.1. Delivery inspection
Each PQFA is delivered in a sealed package designed to protect adequately
the equipment during shipment.
Upon receipt of the equipment, make sure that the packing is in good
condition.
After removal of the packing, check visually the exterior and interior of your
filter. Any loss or damage should be notified immediately.
Care should be taken to ensure that correct handling facilities are used.
2.2. Identification tag
Each PQFA is fitted with a nameplate for identification purposes. The
nameplate includes the type of filter, nominal frequency, voltage and current
as well as a serial number and an ABB internal article code.
This information should always remain readable to ensure proper identification
during the whole life of the filter.
2.3. Storage
PQFA packing is made for a storage period of maximum six months (transport
time included from delivery date EXW ABB Jumet factory). Packing for longer
storage period can be done on request.
If your PQFA is not installed once unpacked, it should be stored in a clean
indoor, dry, dust free and non-corrosive environment. The storage
temperature must be between –15°C and 70°C with a maximum relative
humidity of 95%, non-condensing.
Before installing and operating your PQFA, you should read very carefully this
instructions manual and you should make sure that the information given on
the nameplate corresponds to your network.
2.4. Long storage period and reforming
If your PQFA is non-operational or stored for more than one year, the DC
capacitors need to be reformed (re-aged). Without reforming, capacitors may
be damaged when the filter starts to operate.
The reforming methods are described in chapter 12 (maintenance).
PQFA Instructions Manual
Asea Brown Boveri Jumet S.A.
7
3. PQFA principle and characteristics
3.1. Reasons for limiting harmonics
Power electronics based equipment is the main source of the harmonic
pollution in electric networks. Examples of such equipment include drives (AC
or DC), UPS’s, welders, PCs, printers etc.
In general, the semiconductor switches in this equipment conduct only during
a fraction of the fundamental period. This is how such equipment can obtain
their main properties regarding energy saving, dynamic performance and
flexibility of control. However, as a result a discontinuous current containing a
considerable amount of distortion is drawn from the supply.
Harmonic pollution causes a number of problems. A first effect is the increase
of the RMS-value and the peak-value of the distorted waveform. This is
illustrated in figure 3.1. that shows the increase of these values as more
harmonic components are added to an initially undistorted waveform. The
RMS-value and the peak-value of the undistorted waveform are defined as
100 %. The peaks of the fundamental component and the distortion
components are assumed to be aligned. It may be seen that the distorted
waveform, which contains harmonics up to the 25th harmonic, has a peak
value that is twice the value of the undistorted waveform and a RMS-value
that is 10 % higher.
Peak: 100 % 133 % 168 % 204 %
RMS: 100 % 105 % 108 % 110 %
Figure 3.1. Evolution of the increase in peak-value and the RMS-value of
a waveform as more harmonic components are added
The increase in RMS-value leads to increased heating of the electrical
equipment. Furthermore, circuit breakers may trip due to higher thermal or
instantaneous levels. Also, fuses may blow and capacitors may be damaged.
kWh meters may give faulty readings. The winding and iron losses of motors
increase and they may experience perturbing torques on the shaft. Sensitive
electronic equipment may be damaged. Equipment, which uses the supply
voltage as a reference may not be able to synchronise properly and either
applies wrong firing, pulses to switching elements or switch off. Interference
with electronic communications equipment may occur.
100 % H1
+ 33 % H3
+ 20 % H5
… + 4 %
PQFA Instructions Manual
Asea Brown Boveri Jumet S.A.
8
Distorted networks may also cause generators malfunctions.
Overall it may be concluded that an excessive amount of harmonics leads to a
premature ageing of the electrical installation. This is an important motivation
for taking action against harmonics.
3.2. General principle of active filtering
The active filter measures the harmonic currents and generates actively a
harmonic current spectrum in opposite phase to the measured distorting
harmonic current. The original harmonics are thereby cancelled. The principle
is shown in figure 3.2.
Figure 3.2. Principle of active filtering
The control of the active filter in combination with the active generation of the
compensating current allows for a concept that may not be overloaded.
Harmonic currents exceeding the capacity of the active filter will remain on the
network, but the filter will operate and eliminate all harmonic currents up to its
capacity.
The principle of active filter showing currents and spectra is clarified in Figure
3.3.
PQFA
Supply
Load
Fundamental only
-1.3
1.3
0 360
-1.3
1.3
0 360
-1.3
1.3
0 360
i
distortion
i
compensation
PQFA Instructions Manual
Asea Brown Boveri Jumet S.A.
9
Figure 3.3. Active filter principle illustrated in time and frequency
domains
3.3. The ABB Active filter: the PQFA.
As we have just seen, the active filter is basically a compensating current
generator. The most important parts are then the current generator and the
control system.
The compensating current is in a first step created by a three-phase Insulated
Gate Bipolar Transistors (IGBT) inverter bridge that is able to generate any
given voltage waveform with PWM (Pulse Width Modulation) technology. The
IGBT bridge uses a DC voltage source realised in the form of a DC capacitor.
The inverter bridge is in fact the same technology than in AC drives.
The generated voltage is coupled to the network via reactors and a small filter
circuit. The desired current generator is thereby achieved.
The DC capacitors are loaded actively through the inverter bridge and there is
no need of external power source. Obviously, the DC voltage level must
always be higher than the peak value of the network voltage in order to be
able to inject currents to the network.
To control the active filter the choice stands between open loop and closed
loop current control. Under open loop current control, the harmonics currents
are measured on the load side of the active filter that computes the required
compensating current and injects it into the network.
Closed loop current control as performed by the PQFA is shown in Figure 3.4.
In this topology the resulting current to the network is measured and the
active filter operates by injecting a compensating current minimising this
resulting current. In this configuration, the filter directly controls its effect on
the filtration.
+=
Load
current
1 5 7 11 13 17 19
-20
0
20
40
1 5 7 11 13 17 19
Active Filter
current
1 5 7 11 13 17 19
-20
0
20
40
1 5 7 11 13 17 19
Clean
feeder
current
1 5 7 11 13 17 19
-20
0
20
40
1 5 7 11 13 17 19
WaveformsHarmonics
-1.3
1.3
0 360
-1.3
1.3
0 360
-1.3
1.3
0 360
PQFA Instructions Manual
Asea Brown Boveri Jumet S.A.
10
Figure 3.4. Closed loop control
In addition to being more precise, the closed loop control system also allows
for a direct control of the degree of filtering. Furthermore, the closed loop
control system ensures that measurement errors do not result in a higher
distortion.
To fully exploit the potential of an active filter we need a digital measurement
and control system that is fast enough to operate in true real time. We need to
be able to track the individual harmonics and control the compensating
current according to the requirements of the plant and this with full control at
every instant in time. To achieve this, we need advanced Digital Signal
Processors, DSP’s.
Among the physical signals needed by the PQFA, the three line currents have
obviously to be measured. Standard CTs with 5A secondary are usually
sufficient. Those analogue signals must first be acquired, levelled and
antialias-filtered before digitalisation. Fast and high precision analogue-to-
digital converters are used to create a digital representation of the analogue
signals. The digitised signals are then sent to the powerful DSP that controls
all measurements and calculations in real time, and builds the PWM
references for the inverter. It is another processor, a microcontroller, which
handles all digital input/output (including the command of the PWM inverter).
More dedicated to control than to calculations, this microcontroller ensures for
instance the closing of the relays and contactors.
One control is needed per PQFA system and can handle more than one
power module simultaneously.
Control
AF
Target
Measurement Feedback
Output
PQFA Instructions Manual
Asea Brown Boveri Jumet S.A.
11
3.4. The PQFA: performances
3.4.1. Filtering
The main requirement for an active filter installed in an industrial installation is
to attenuate the harmonics produced by the non-linear loads of the
installation.
The ideal active filter should allow the user to choose freely which harmonic
components to filter and should offer an adjustable degree of filtering.
It is also worth noting that the total harmonic voltage distortion at the point of
common coupling (PCC) is often calculated up to the 40
th
[1] or the 50
th
[2]
harmonic. Furthermore, the total number of harmonics that can be filtered
determines directly the quality of the resulting current. This is illustrated in
figure 3.5., which shows the filtered waveforms obtained by filtering up to
different harmonic levels.
(a) Filtering up to the 13
th
harmonic.
(b) Filtering up to the 25
th
harmonic.
(c) Filtering up to the 50
th
harmonic.
Figure 3.5. Waveforms obtained by eliminating the harmonic
components of a rectangular periodic signal up to the (a) 13
th
harmonic,
(b) the 25
th
harmonic and (c) the 50
th
harmonic
This figure highlights the need for an active filter that can operate up to
sufficiently high harmonic frequencies.
The PQFA can filter simultaneously 20 (15) independent harmonics up to the
50
th
for 50Hz (60Hz) based networks. The number of harmonics to be filtered
as well as their frequencies is completely programmable by the user.
PQFA Instructions Manual
Asea Brown Boveri Jumet S.A.
12
Besides the harmonic selection functionality, the user has also the possibility
to specify a filtration level for each selected harmonic. The PQFA will filter the
selected harmonics until
by the user and may be different for each selected harmonic. This
functionality is especially useful when the objective is to fulfil the requirements
of a standard and results in a better use of the available compensation power.
It also allows the installation of active filters on networks already fitted with a
fixed passive filter.
We can see that we are very close to the ideal filter: the choice of which
harmonic components to filter is free and the degree of filtering is adjustable
according to the wishes of the user.
Moreover, all typical harmonics generated by three-phase non-linear loads
may be filtered simultaneously.
3.4.2. Reactive power
Besides the filtering functionality, reactive power compensation is also
possible with the active filter. Compared to traditional capacitor banks, the
reactive compensation of the PQFA is continuous (‘stepless’), fast and
smooth (no transients at switching). The compensation can be either
capacitive or inductive.
Two types of compensation are available: automatic compensation where a
target power factor has to be set, and fixed compensation based on a
predefined amount of kvar.
3.4.3. EMC
The PQFA has been verified for compliance with EU (European Union)
directives for EMC (electromagnetic compatibility) for operation at 50 Hz and
bears the CE-mark to this effect.
When an apparatus is used in a system, EU directives may require that the
system is verified for EMC compliance.
PQFA Instructions Manual
Asea Brown Boveri Jumet S.A.
13
4. Components description and identification
4.1. Components description
As already explained, the active filter is basically composed of two parts: the
current generator and the control system.
4.1.1. PQF current generator.
The power circuit of the ABB active filter PQF is represented hereafter.
Output
Filter
PWM inverter
Main Breaker
Power
Lines
+
-
PWM Reactors
Preload
The main components are:
- PWM inverter
- PWM reactors
- Output filer
- Preloading circuit
The current generator is physically organised in power modules, each
including a PWM inverter, three PWM reactors and the output filter.
Each PQFA cubicle may contain one or two power modules. There is one
breaker and one preloading circuit per cubicle.
Non-linear load(s)
(three-
phase or
single-phase)
PQF Digital
Control
Compensation
current
Current
measurement
PQF current
generator
PQFA Instructions Manual
Asea Brown Boveri Jumet S.A.
14
The PWM inverter is composed of DC capacitors and an IGBT inverter bridge.
This system is able to generate any voltage waveform with PWM technology.
The physical layout of a PWM inverter module is shown hereafter. Each PWM
inverter is fitted with a local electronic control called the domino board. The
domino board is controlled by the central DSP. The domino board is fitted with
jumpers noted JP100, JP101, JP102, JP103, JP104, JP105, JP106, JP109
and JP110 (JP107 and JP108 are off). In case of several power modules, only
the domino board of the last slave is fitted with jumpers.
The PWM reactors convert the voltage created by the PWM inverter into
currents that will be injected in the network.
The output filter consists in line reactors and an RC shunt circuit.
The function of the preloading circuit is to avoid at start-up high inrush
currents that could damage the power electronics or create transients in the
network.
4.1.2. The control
For best performances, the control of the PQFA is Digital Signal Processor
(DSP) based.
The three lines currents are measured by external CT. Those analogue
signals must first be acquired, levelled and antialias-filtered before
digitalisation. Fast and high precision anlogue-to-digital converters are used to
create a digital representation of the analogue signals. The digitised signals
are then sent to the powerful DSP that controls all measurements and
DC capacitors
Low inductance
DC bus bar
Inverter
Heatsink
PQFA Instructions Manual
Asea Brown Boveri Jumet S.A.
15
calculation in real time, and builds the PWM references for the inverter. It is
another processor, a microcontroller, which handles all digital input/output
(including the command of the PWM inverter). More dedicated to control than
to calculations, this microcontroller ensures for instance the closing of relays
and contactors.
One control unit may command up to 8 power modules.
4.2. Components identification
Control
PWM
inverter
module 2
PWM
inverter
module 1
Domino
board
Circuit
breaker
Fan
Output
filter
capacitor
Auxiliary
voltage
transformer
PQF
Manager
PQFA Instructions Manual
Asea Brown Boveri Jumet S.A.
16
A more detailed identification is given in the following pages.
The identification hereafter is related to the drawings of the following pages.
Internal views indicate the position of identified components but fixation
details are not included. Although visible on the drawings, some components
may actually be hidden in the real structure.
Mains power breaker
Q11: power breaker
L1, L2, L3: power cables connection
K102: contactor closing MCB
K103: contactor opening MCB
X8: terminal Sace wiring
Fan
M101: fan motor
K101: fan contactor
X9: terminal block motor connection wiring
F101: motor overload protection
Auxiliaries
Q101: breaker for auxiliaries
T101: auxiliary voltage transformer
PWM inverter
U11: module 1
U21: module 2
A117: module 1 domino board
A118: module 2 domino board
Output filter
C11_12_13A/B Module 1 output filter capacitor
C21_22_23A/B Module 2 output filter capacitor
X14 Terminal block capacitors module 1 wiring
X15 Terminal block capacitors module 2 wiring
R11/12/13 Module 1 output filter resistor
R21/22/23 Module 2 output filter resistor
L11/12/13 Module 1 line reactors
L21/22/23 Module 2 line reactors
PWM reactors
L14/15/16 Module 1 PWM reactors
L24/25/26 Module 2 PWM reactors
PQFA Instructions Manual
Asea Brown Boveri Jumet S.A.
17
Preloading circuit
K11 Preload contactor
R14/15 Preload resistor
U1 Preload bridge
Control rack
A111 Digital I/O board
A112 Interface board – IGBT’s and DSP
A113 Digital Signal Processor
A119 Interface PQF Manager board
A114 Current input board
A115 Analog input board
A116 +24V power supply board
U100 Power supply ? 15V
U109 Power supply + 5V
X1 Terminal block digital I/O wiring
X4 Terminal block current input wiring
X2 Terminal block analog input wiring
X10 Terminal power supply wiring
X6 Terminal current input wiring
A67 AC voltage board
Door components
S102 RESET push button
S101 RUN push button
S104 Remote local switch
H101 White lamp: controller connected to supply (auxiliary
breaker closed)
H102 Red lamp: MCB closed
H103 Green lamp: MCB open
A120 PQF-Manager
Other components
B101/102/103 Internal current sensors
K104 Alarm contactor
K12 Remote contactor
X5 Terminal block backplane wiring (external CT connection)
PQFA Instructions Manual
Asea Brown Boveri Jumet S.A.
18
X10 Terminal power supply wiring
X11 Terminal DC bus wiring
X12 Terminal signaling wiring
X13 Terminal inter cubicles wiring
A104 DC voltage convertor
PQFA Instructions Manual
Asea Brown Boveri Jumet S.A.
19
Master cubicle view
Zoom on next page
PQFA Instructions Manual
Asea Brown Boveri Jumet S.A.
20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98

ABB PQFA User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI