7.1 Troubleshooting table
Table 5: Troubleshooting
LED indicator/fault pattern Cause Measures
Green LED does not light up No voltage or voltage below
the limit v
alues
Check the power supply,
check all electrical connec‐
tions (cables and plug connec‐
tions)
Green LED does not light up Voltage interruptions Ensure there is a stable power
supply w
ithout interruptions
Green LED does not light up Sensor is faulty If the power supply is OK,
replace the sensor
Yellow LED flashes Sensor is still ready for opera‐
tion, but the operating condi‐
tions are not ideal
Check the operating condi‐
tions: Fully align the beam of
light (light spot) with the
object / Clean the optical sur‐
faces / Readjust the sensitiv‐
ity (potentiometer)
Yellow LED lights up, no object
in the pa
th of the beam
Remission capability of the
background is excessive
Check changes to the back‐
ground. Reduce the sensitivity
of the sensor or use sensors
with background suppression
Object is in the path of the
beam, yellow LED does not
light up
Sensitivity is set too low or dis‐
tance between the sensor and
the object is too long
Increase the sensing range,
take note of the distance
between the sensor and the
background
Object is in the path of the
beam, yellow LED does not
light up
Remission capability of the
object is insufficient
Increase the sensing range,
take note of the distance
between the sensor and the
background
8 Disassembly and disposal
The sensor must be disposed of according to the applicable country-specific regula‐
tions
. Efforts should be made during the disposal process to recycle the constituent
materials (particularly precious metals).
NOTE
Dispos
al of batteries, electric and electronic devices
•
According to international directives, batteries, accumulators and electrical or
electronic devices must not be disposed of in general waste.
•
The owner is obliged by law to return this devices at the end of their life to the
respective public collection points.
•
WEEE:
This symbol on the product, its package or in this document, indi‐
ca
tes that a product is subject to these regulations.
9 Maintenance
SICK sensors are maintenance-free.
We r
ecommend doing the following regularly: