  • Hello! I am an AI chatbot trained to assist you with the Danfoss ECL Comfort 210/296/ 310, A231/A331 Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
OperatingGuide
ECLComfort210/296/310,applicationA231/
A331
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................5
2.1Beforeyoustart.....................................................5
2.2Identifyingthesystemtype......................................13
2.3Mounting...........................................................14
2.4Placingthetemperaturesensors................................18
2.5Electricalconnections.............................................20
2.6InsertingtheECLApplicationKey..............................28
2.7Checklist............................................................34
2.8Navigation,ECLApplicationKeyA231/A331................35
3.0Dailyuse.........................................................41
3.1Howtonavigate...................................................41
3.2Understandingthecontrollerdisplay..........................42
3.3Ageneraloverview:Whatdothesymbolsmean?...........44
3.4Monitoringtemperaturesandsystem
components........................................................45
3.5Influenceoverview................................................46
3.6Manualcontrol.....................................................47
3.7Schedule............................................................48
4.0Settingsoverview............................................49
5.0Settings...........................................................51
5.1IntroductiontoSettings..........................................51
5.2Flowtemperature..................................................52
5.3Returnlimit.........................................................57
5.4Flow/powerlimit.................................................61
5.5Optimization........................................................65
5.6Controlparameters................................................71
5.7Pumpcontrol.......................................................75
5.8Refillwater..........................................................78
5.9Application.........................................................83
5.10Alarm................................................................88
5.11Alarmoverview....................................................91
6.0Commoncontrollersettings..............................92
6.1Introductionto‘Commoncontrollersettings................92
6.2Time&Date.........................................................93
6.3Holiday..............................................................94
6.4Inputoverview.....................................................96
6.5Log...................................................................97
6.6Outputoverride....................................................98
6.7Keyfunctions.......................................................99
6.8System.............................................................101
7.0Miscellaneous................................................108
7.1ECA30/31setupprocedures.................................108
7.2Overridefunction................................................116
7.3Severalcontrollersinthesamesystem......................119
7.4Frequentlyaskedquestions....................................122
7.5Definitions........................................................125
7.6Type(ID6001),overview.......................................128
7.7ParameterIDoverview..........................................129
©Danfoss|2018.01VI.LG.P2.02|1
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisInstallationGuideisassociatedwithECLApplicationKeyA231
(ordercodeno.087H3805).
TheA231Keycontainstwosetsofapplications:oneset(A231.1/
A231.2)andanotherset(A331.1/A331.2).
Thefunctionscanberealizedin:
ECLComfort210(A231)forsimplesolutionsor
ECLComfort310(A231/A331)fore.g.M-busandother
communicationaswellasprimarypressuremeasurement.
TheapplicationsA231/A331complywithECLComfortcontrollers
210/310asofsoftwareversion1.10(visibleatstart-upofthe
controllerandin‘Commoncontrollersettings’in‘System’).
AdditionaldocumentationforECLComfort210and310,modules
andaccessoriesisavailableonhttp://heating.danfoss.com/.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
2|©Danfoss|2018.01
VI.LG.P2.02
ECLComfort210/296/310,applicationA231/A331
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1
Parameterno.
12174
1
2
174
-
Circuit2
Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
VI.LG.P2.02
©Danfoss|2018.01|3
ECLComfort210/296/310,applicationA231/A331
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
4|©Danfoss|2018.01
VI.LG.P2.02
ECLComfort210/296/310,applicationA231/A331
2.0Installation
2.1Beforeyoustart
TheapplicationA231.1isveryflexible.Thesearethebasic
principles:
Heating:
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.TheflowtemperaturesensorS3isthemost
importantsensor.ThedesiredflowtemperatureatS3iscalculated
intheECLcontroller,basedontheoutdoortemperature(S1).
Thelowertheoutdoortemperature,thehigherthedesiredflow
temperature.
Bymeansofaweekschedule,theheatingcircuitcanbein
‘Comfort’or‘Saving’mode(twodifferenttemperaturevaluesfor
desiredroomtemperature).
ThemotorizedcontrolvalvesM1isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
ThereturntemperatureS5tothedistrictheatingsupplyshouldnot
betoohigh.Ifso,thedesiredflowtemperaturecanbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingofthe
motorizedcontrolvalve.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Furthermore,thereturntemperaturelimitationcanbedependent
oftheoutdoortemperature.Typically,thelowertheoutdoor
temperature,thehighertheacceptedreturntemperature.
ThecirculationpumpinquestionisONatheatdemandoratfrost
protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
Thestaticpressureonthesecondaryside(consumerside)can1)
bemeasuredasa0-10Vsignal(fromapressuretransmitter)or
2)beaswitchsignalfromapressureswitch.Incaseofatoolow
pressure,therefillwaterfunctionwillsupplementwithwaterfrom
thesupplyside.
WhentheECLComfortcontrolleroperatesasaslave,onlytherefill
watervalveiscontrolled.Themastercontrolsacommonrefill
waterpumpfortheentiresystem.
TypicalA231.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
S1
Outdoortemperaturesensor
S3
Flowtemperaturesensor
S5
Returntemperaturesensor
S7
Differentialpressureswitch
S8
Pressuretransmitterorpressureswitch
P1
Circulationpump
P2
Circulationpump
P3
Refillwaterpump
M1
Motorizedcontrolvalve
V1
Solenoidvalve,refillwatervalve
R4
Relayoutput,alarm
VI.LG.P2.02
©Danfoss|2018.01|5
ECLComfort210/296/310,applicationA231/A331
ApplicationA231.1ingeneral:
ThecirculationpumpsP1andP2workinshiftaccordingtoa
schedule.Onepumpisusedassparepumpandtheotherpump
isworking.Incaseofmalfunction(missingdifferentialpressure)
ofonepump,theotherpumpwilltakeover.Analarmwillbe
generatedandthedefectivepumpcanbeinspected/repaired.
Alarm(relay4)canbeactivatedif:
Theactualflowtemperaturediffersfromthedesiredflow
temperature.
Theactivatedcirculationpumpdoesnotgenerateapressure
difference.
Therefillwaterfunctiondoesnotgenerateapressurewithin
apresettime.
TypicalA231.1application:
6|©Danfoss|2018.01
VI.LG.P2.02
ECLComfort210/296/310,applicationA231/A331
TheapplicationA231.2isveryflexible.Thesearethebasic
principles:
Heating:
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.TheflowtemperaturesensorS3isthemost
importantsensor.ThedesiredflowtemperatureatS3iscalculated
intheECLcontroller,basedontheoutdoortemperature(S1).
Thelowertheoutdoortemperature,thehigherthedesiredflow
temperature.
Thesupplytemperature(S2)isusedto1)controltheS3
temperatureinrelationtotheS2temperatureor2)maximizethe
limitofthedesiredflowtemperature.
Thefactorysetting,wherethesupplytemperature(S2)determines
thedesiredflowtemperature,doesnotchangethedesiredflow
temperatureaccordingtoComfortor‘Savingmode.
However,ifthesupplytemperature(S2)determinesamax.
limitationofthedesiredflowtemperature,the‘Comfort’and
‘Saving’modewillhavetwodifferenttemperaturevaluesfor
desiredroomtemperature.
ThemotorizedcontrolvalveM1isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
ThereturntemperatureS5tothedistrictheatingsupplyshouldnot
betoohigh.Ifso,thedesiredflowtemperaturecanbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingofthe
motorizedcontrolvalve.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Furthermore,thereturntemperaturelimitationcanbedependent
oftheoutdoortemperature.Typically,thelowertheoutdoor
temperature,thehighertheacceptedreturntemperature.
ThecirculationpumpinquestionisONatheatdemandoratfrost
protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
Thestaticpressureonthesecondaryside(consumerside)can1)
bemeasuredasa0-10Vsignal(fromapressuretransmitter)or
2)beaswitchsignalfromapressureswitch.Incaseofatoolow
pressure,therefillwaterfunctionwillsupplementwithwaterfrom
thesupplyside.
WhentheECLComfortcontrolleroperatesasaslave,onlytherefill
watervalveiscontrolled.Themastercontrolsacommonrefill
waterpumpfortheentiresystem.
TypicalA231.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
S1
Outdoortemperaturesensor
S2
Supplyflowtemperaturesensor
S3
Flowtemperaturesensor
S5
Returntemperaturesensor
S7
Differentialpressureswitch
S8
Pressuretransmitterorpressureswitch
P1
Circulationpump
P2
Circulationpump
P3
Refillwaterpump
M1
Motorizedcontrolvalve
V1
Solenoidvalve,refillwatervalve
R4
Relayoutput,alarm
VI.LG.P2.02
©Danfoss|2018.01|7
ECLComfort210/296/310,applicationA231/A331
ApplicationA231.2ingeneral:
ThecirculationpumpsP1andP2workinshiftaccordingtoa
schedule.Onepumpisusedassparepumpandtheotherpump
isworking.Incaseofmalfunction(missingdifferentialpressure)
ofonepump,theotherpumpwilltakeover.Analarmwillbe
generatedandthedefectivepumpcanbeinspected/repaired.
Alarm(relay4)canbeactivatedif:
Theactualflowtemperaturediffersfromthedesiredflow
temperature.
Theactivatedcirculationpumpdoesnotgenerateapressure
difference.
Therefillwaterfunctiondoesnotgenerateapressurewithin
apresettime.
TypicalA231.2application:
8|©Danfoss|2018.01
VI.LG.P2.02
ECLComfort210/296/310,applicationA231/A331
TheapplicationA331.1isveryflexible.Thesearethebasic
principles:
Heating:
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.TheflowtemperaturesensorS3isthemost
importantsensor.ThedesiredflowtemperatureatS3iscalculated
intheECLcontroller,basedontheoutdoortemperature(S1).
Thelowertheoutdoortemperature,thehigherthedesiredflow
temperature.
Bymeansofaweekschedule,theheatingcircuitcanbein
‘Comfort’or‘Saving’mode(twodifferenttemperaturevaluesfor
desiredroomtemperature).
ThemotorizedcontrolvalvesM1isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
ThereturntemperatureS5tothedistrictheatingsupplyshouldnot
betoohigh.Ifso,thedesiredflowtemperaturecanbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingofthe
motorizedcontrolvalve.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Furthermore,thereturntemperaturelimitationcanbedependent
oftheoutdoortemperature.Typically,thelowertheoutdoor
temperature,thehighertheacceptedreturntemperature.
ThecirculationpumpinquestionisONatheatdemandoratfrost
protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
Thestaticpressureonthesecondaryside(consumerside)can1)be
measuredasa0-10Vsignal(fromapressuretransmitter)or2)bea
switchsignalfromapressureswitch.Incaseofatoolowpressure,
therefillwaterfunctionwillsupplementwithwaterfromthe
supplyside.Thetworefillwaterpumpsareoperatedalternately.
WhentheECLComfortcontrolleroperatesasaslave,onlytherefill
watervalveiscontrolled.Themastercontrolsacommonrefill
waterpumpfortheentiresystem.
TypicalA331.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
S1
Outdoortemperaturesensor
S3
Flowtemperaturesensor
S5
Returntemperaturesensor
S7
Differentialpressureswitch
S8
Pressuretransmitterorpressureswitch
S9
Alarminput
S10
Pressuretransmitter(formonitoringonly)
P1
Circulationpump
P2
Circulationpump
P3
Refillwaterpump
P5
Refillwaterpump
M1
Motorizedcontrolvalve
V1
Solenoidvalve,refillwatervalve
R6
Relayoutput,alarm
VI.LG.P2.02
©Danfoss|2018.01|9
ECLComfort210/296/310,applicationA231/A331
ApplicationA331.1ingeneral:
ThecirculationpumpsP1andP2workinshiftaccordingtoa
schedule.Onepumpisusedassparepumpandtheotherpump
isworking.Incaseofmalfunction(missingdifferentialpressure)
ofonepump,theotherpumpwilltakeover.Analarmwillbe
generatedandthedefectivepumpcanbeinspected/repaired.
Alarm(relay6)canbeactivatedif:
Theactualflowtemperaturediffersfromthedesiredflow
temperature.
Theactivatedcirculationpumpdoesnotgenerateapressure
difference.
Therefillwaterfunctiondoesnotgenerateapressurewithin
apresettime.
TheuniversalalarminputsS9isactivated.
ModbuscommunicationtoaSCADAsystemcanbeestablished.
M-buscommunicationenablesconnectiontofloworenergymeter.
Thecontrollercanlimitthefloworenergytoasetmaximumbut
alsoinrelationtotheoutdoortemperature.
Furthermore,theM-busdatacanbetransferredtotheModbus
communication.
TypicalA331.1application:
10|©Danfoss|2018.01
VI.LG.P2.02
ECLComfort210/296/310,applicationA231/A331
TheapplicationA331.2isveryflexible.Thesearethebasic
principles:
Heating:
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.TheflowtemperaturesensorS3isthemost
importantsensor.ThedesiredflowtemperatureatS3iscalculated
intheECLcontroller,basedontheoutdoortemperature(S1).
Thelowertheoutdoortemperature,thehigherthedesiredflow
temperature.
Thesupplytemperature(S2)isusedto1)controltheS3
temperatureinrelationtotheS2temperatureor2)maximizethe
limitofthedesiredflowtemperature.
Thefactorysetting,wherethesupplytemperature(S2)determines
thedesiredflowtemperature,doesnotchangethedesiredflow
temperatureaccordingtoComfortor‘Savingmode.
However,ifthesupplytemperature(S2)determinesamax.
limitationofthedesiredflowtemperature,the‘Comfort’and
‘Saving’modewillhavetwodifferenttemperaturevaluesfor
desiredroomtemperature.
ThemotorizedcontrolvalvesM1isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
ThereturntemperatureS5tothedistrictheatingsupplyshouldnot
betoohigh.Ifso,thedesiredflowtemperaturecanbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingofthe
motorizedcontrolvalve.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Furthermore,thereturntemperaturelimitationcanbedependent
oftheoutdoortemperature.Typically,thelowertheoutdoor
temperature,thehighertheacceptedreturntemperature.
ThecirculationpumpinquestionisONatheatdemandoratfrost
protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
Thestaticpressureonthesecondaryside(consumerside)can1)be
measuredasa0-10Vsignal(fromapressuretransmitter)or2)bea
switchsignalfromapressureswitch.Incaseofatoolowpressure,
therefillwaterfunctionwillsupplementwithwaterfromthe
supplyside.Thetworefillwaterpumpsareoperatedalternately.
WhentheECLComfortcontrolleroperatesasaslave,onlytherefill
watervalveiscontrolled.Themastercontrolsacommonrefill
waterpumpfortheentiresystem.
TypicalA331.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
S1
Outdoortemperaturesensor
S2
Supplyflowtemperaturesensor
S3
Flowtemperaturesensor
S5
Returntemperaturesensor
S7
Differentialpressureswitch
S8
Pressuretransmitterorpressureswitch
S9
Alarminput
S10
Pressuretransmitter(formonitoringonly)
P1
Circulationpump
P2
Circulationpump
P3
Refillwaterpump
P5
Refillwaterpump
M1
Motorizedcontrolvalve
V1
Solenoidvalve,refillwatervalve
R6
Relayoutput,alarm
VI.LG.P2.02
©Danfoss|2018.01|11
ECLComfort210/296/310,applicationA231/A331
ApplicationA331.2ingeneral:
ThecirculationpumpsP1andP2workinshiftaccordingtoa
schedule.Onepumpisusedassparepumpandtheotherpump
isworking.Incaseofmalfunction(missingdifferentialpressure)
ofonepump,theotherpumpwilltakeover.Analarmwillbe
generatedandthedefectivepumpcanbeinspected/repaired.
Alarm(relay6)canbeactivatedif:
Theactualflowtemperaturediffersfromthedesiredflow
temperature.
Theactivatedcirculationpumpdoesnotgenerateapressure
difference.
Therefillwaterfunctiondoesnotgenerateapressurewithin
apresettime.
TheuniversalalarminputsS9isactivated.
ModbuscommunicationtoaSCADAsystemcanbeestablished.
M-buscommunicationenablesconnectiontofloworenergymeter.
Thecontrollercanlimitthefloworenergytoasetmaximumbut
alsoinrelationtotheoutdoortemperature.
Furthermore,theM-busdatacanbetransferredtotheModbus
communication.
TypicalA331.2application:
Thecontrollerispre-programmedwithfactorysettingsthatareshown
inthe‘ParameterIDoverviewappendix.
12|©Danfoss|2018.01
VI.LG.P2.02
ECLComfort210/296/310,applicationA231/A331
2.2Identifyingthesystemtype
Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange
ofheating,domestichot-water(DHW)andcoolingsystemswith
differentconfigurationsandcapacities.Ifyoursystemdiffers
fromthediagramsshownhere,youmaywanttomakeasketch
ofthesystemabouttobeinstalled.Thismakesiteasiertouse
theOperatingGuide,whichwillguideyoustep-by-stepfrom
installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe
usedforvarioussystems.Basedontheshownstandardsystems,
itispossibletoconfigureadditionalsystems.Inthischapteryou
findthemostfrequentlyusedsystems.Ifyoursystemisnotquite
asshownbelow,findthediagramwhichhasthebestresemblance
withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow
aswellasthereturn.Placethepumpaccordingtothemanufacturer’s
specification.
VI.LG.P2.02
©Danfoss|2018.01|13
ECLComfort210/296/310,applicationA231/A331
2.3Mounting
2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe
ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear
thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart
(forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure
thecontrollerwiththelockingpin.
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto
besecurelylockedintothebase.Forthispurpose,pressthelocking
pinintothebaseuntilaclickisheardandthecontrollernolonger
canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk
thatthecontrollerduringoperationcanunlockfromthebaseandthe
basewithterminals(andalsothe230Va.c.connections)areexposed.
Topreventinjuriestopersons,alwaysmakesurethatthecontroller
issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller
shouldnotbeoperated!
14|©Danfoss|2018.01
VI.LG.P2.02
ECLComfort210/296/310,applicationA231/A331
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe
electricalconnectionsandpositionthecontrollerinthebasepart.
Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical
connectionsandpositionthecontrollerinthebasepart.Secure
thecontrollerwiththelockingpin.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe
lockingpinbymeansofascrewdriver.Thecontrollercannowbe
removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
VI.LG.P2.02
©Danfoss|2018.01|15
ECLComfort210/296/310,applicationA231/A331
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure
thatthesupplyvoltageisdisconnected.
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth
surface.Establishtheelectricalconnections.PlacetheECA30/
31inthebasepart.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode
no.087H3236).Establishtheelectricalconnections.Securethe
framewiththeclamp.PlacetheECA30inthebasepart.TheECA
30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity
functionistobeused.
16|©Danfoss|2018.01
VI.LG.P2.02
ECLComfort210/296/310,applicationA231/A331
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted
intotheECLComfort310/310Bbasepartforadditionalinputand
outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32
isa10-pole(2x5)connector.Theconnectionisautomatically
establishedwhentheECLComfort310/310Bisplacedonthe
basepart.
VI.LG.P2.02
©Danfoss|2018.01|17
ECLComfort210/296/310,applicationA231/A331
2.4Placingthetemperaturesensors
2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition
inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe
ECLComfort210/296/310serieswhichnotallwillbeneeded
foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding
whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot
beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems
withheatexchanger,DanfossrecommendsthattheESMU-typeto
beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere
thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit
measuresarepresentativereturntemperature.
Roomtemperaturesensor
(ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe
controlled.Donotplaceitonoutsidewallsorclosetoradiators,
windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s
specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s
specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto
avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick
measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill,
however,resultinaslowertemperaturemeasurement.
18|©Danfoss|2018.01
VI.LG.P2.02
ECLComfort210/296/310,applicationA231/A331
Pt1000temperaturesensor(IEC751B,1000/0°C)
Relationshipbetweentemperatureandohmicvalue:
VI.LG.P2.02
©Danfoss|2018.01|19
ECLComfort210/296/310,applicationA231/A331
2.5Electricalconnections
2.5.1Electricalconnections230Va.c.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize
andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis
0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thecommongroundterminalisusedforconnectionofrelevant
components(pumps,motorizedcontrolvalves).
ECL210/310
ECL296
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)
forapplicationspecificconnections.
20|©Danfoss|2018.01
VI.LG.P2.02
ECLComfort210/296/310,applicationA231/A331
/