Watlow Series PD User manual

Category
Measuring, testing & control
Type
User manual
0600-0043-0010 Rev. B Made in the U.S.A.
November 2006 $15.00
User’s Manual
Registered Company
Winona, Minnesota USA
Series PD
Ethernet-Enabled
Temperature/Process Controller
1241 Bundy Boulevard., Winona, Minnesota USA 55987
Phone: +1 (507) 454-5300, Fax: +1 (507) 452-4507 http://www.watlow.com
Safety Information
We use note, caution and warning symbols throughout this book to draw your attention to
important operational and safety information.
A “NOTE” marks a short message to alert you to an important detail.
A “CAUTION” safety alert appears with information that is important for protecting your
equipment and performance. Be especially careful to read and follow all cautions that apply
to your application.
A “WARNING” safety alert appears with information that is important for protecting you,
others and equipment from damage. Pay very close attention to all warnings that apply to
your application.
The safety alert symbol, ç (an exclamation point in a triangle) precedes a general CAUTION
or WARNING statement.
The electrical hazard symbol, Ó (a lightning bolt in a triangle) precedes an electric shock
hazard CAUTION or WARNING safety statement.
Technical Assistance
If you encounter a problem with your Watlow controller, review your configuration informa-
tion to verify that your selections are consistent with your application: inputs, outputs,
alarms, limits, etc. If the problem persists, you can get technical assistance from your local
Watlow representative (see back cover), by e-mailing your questions to wintechsupport@wat
-
low.com or by dialing +1 (507) 494-5656 between 7 a.m. and 5 p.m., Central Standard Time
(CST). Ask for for an Applications Engineer. Please have the following information available
when calling:
• Complete model number • All Series PD configuration information
• Quick Start Guide or User’s Manual • Computer Hardware / Software Configuration
Warranty
The Series PD is manufactured by ISO 9001-registered processes and is backed by a three-
year warranty.
Return Material Authorization (RMA)
1. Call Watlow Customer Service, (507) 454-5300, for a Return Material Authorization
(RMA) number before returning any item for repair. We need this information:
Ship to address Bill to address
Contact name Phone number
Method of return shipment Your P.O. number
Detailed description of the problem Any special instructions
Name and phone number of person returning the product.
2. Prior approval and an RMA number, from the Customer Service Department, is needed
when returning any unused product for credit. Make sure the RMA number is on the outside
of the carton, and on all paperwork returned. Ship on a Freight Prepaid basis.
3. After we receive your return, we will examine the unit and try to verify the reason for
the return.
4. In cases of manufacturing defect, we will enter a repair order, replacement order or issue
credit for material returned.
5. To return products that are not defective, goods must be be in new condition, in the orig-
inal boxes and they must be returned within 120 days of receipt. A 20 percent restocking
charge is applied for all returned stock controls and accessories.
6. If the unit is unrepairable, it will be returned to you with a letter of explanation.
7. Watlow reserves the right to charge for no trouble found (NTF) returns.
The Series PD User’s Manual is copyrighted by Watlow Winona, Inc., © November 2003 with all
rights reserved. (2413)
ç
CAUTION or
WARNING
Ó
Electrical
Shock Hazard
CAUTION or WARNING
Watlow Series PD 1 Table of Contents
Chapter 1 - Overview . . . . . . . . . . . . . . . . . . . . . . . . . .2
Chapter 2 - Install and Wire . . . . . . . . . . . . . . . . . . . .3
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Mounting/Removal . . . . . . . . . . . . . . . . . . . . . . . . . .4
Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Chapter 3 - Indicator Lights . . . . . . . . . . . . . . . . . . .19
Chapter 4 - Ethernet Communications . . . . . . . . . .20
Chapter 5 - Monitor Device Page . . . . . . . . . . . . . . .22
Navigation Frame . . . . . . . . . . . . . . . . . . . . . . . . .23
Chapter 6 - Device Information Page . . . . . . . . . . . .25
Chapter 7 - Device Configuration Page . . . . . . . . . .28
Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Control Loops . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Datalogging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
File System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Chapter 8 - Calibration Page . . . . . . . . . . . . . . . . . . .59
Chapter 9 - Parameter Table . . . . . . . . . . . . . . . . . . .62
Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
Control Loops . . . . . . . . . . . . . . . . . . . . . . . . . . . .76
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100
Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .116
Datalogging . . . . . . . . . . . . . . . . . . . . . . . . . . . . .118
Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .122
Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .127
Chapter 10 - Features . . . . . . . . . . . . . . . . . . . . . . .129
Chapter 11 - Troubleshooting . . . . . . . . . . . . . . . . .144
Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .146
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . .146
Ordering Information . . . . . . . . . . . . . . . . . . . . . .148
Declaration of Conformity . . . . . . .inside back cover
TC
Table of Contents
Watlow Series PD 2 Chapter 1 Overview
The Series PD controller is a DIN rail mounted, general purpose industrial PID temperature/
process controller. The Series PD is available in single and dual channel versions and features an
embedded web server to provide an easy to use interface for configuration and monitoring of
processes. The controller also features several popular communications protocols to facilitate easy
integration into most existing process management systems.
The Series PD accepts thermocouple, RTD and process signal control inputs and also features
auxiliary digital inputs or optional current transformer (CT) inputs. Up to four control or event
(alarm) outputs can be selected on either the single or dual channel versions.
Advanced features of the Series PD controllers include internal datalogging of key control pa-
rameters, INFOSENSE-P™ sensor technology, heater burn out detection and an enhanced control
algorithm.
The SERIES PD controller is backed by a three-year warranty from Watlow Winona and is
UL
®
508, C-UL
®
, CSA and CE approved.
Figure 2 — Series PD inputs and outputs.
1
Overview
PD
PID Controller
Power
Ethernet Link
Ethernet Activity
1
2
3
4
1
2
Input Error
Input Error
Output
Output
Output
Output
Address
1 or 2 Universal
Analog Inputs
(Single or dual channel)
Event or Current
Transformer (CT) Inputs
4 outputs can be configured
as control or event (alarm)
outputs. Any output can be
assigned to either channel 1 or 2.
Ethernet Communications
Watlow Series PD 3 Chapter 2 Install and Wire
DIN
rail
bracket for
panel mounting
(M3.5 or #6
screw required)
Side View
Front View
8.1 mm
(0.32 in)
95.3 mm
(3.75 in)
72.9 mm
(2.87 in)
128.5 mm
(5.06 in)
Attachment Angle
10˚
DIN
rail
107.7 mm
(4.24 in)
118.4 mm
(4.66 in)
Min. Clearance 51 mm
(2 in)
Min. Clearance
between rail
centerlines
146.1 mm
(5.75 in)
41.7 mm
(1.64 in)
41.9 mm
(1.65 in)
Top/bottom
mount
hole offset
PD
PID Controller
Power
Ethernet Link
Ethernet Activity
1
2
3
4
1
2
Input Error
Input Error
Output
Output
Output
Output
Address
PD
PID Controller
Power
Ethernet Link
Ethernet Activity
1
2
3
4
1
2
Input Error
Input Error
Output
Output
Output
Output
Address
PD
PID Controller
Power
Ethernet Link
Ethernet Activity
1
2
3
4
1
2
Input Error
Input Error
Output
Output
Output
Output
Address
Use DIN EN 50022 35 X 7.5 mm rail
ç
Caution: Maintain the correct spacing be-
tween rows of controllers to allow suffi-
cient air circulation and installation clear-
ance. Failure to do so could result in
damage to equipment.
Figure 3 — Series PD dimensions
2
Install and Wire
Series PD Dimensions
Watlow Series PD 4 Chapter 2 Install and Wire
Mounting the Series PD
Figure 4a — Mounting
1. Push unit in and down to catch rail hook on top of rail.
2. Rotate bottom of unit toward rail.
3. Rail clasp will audibly “snap” into place. If the Series PD does not snap into place, check to
see if the rail is bent.
Removing the Series PD
Figure 4b — Removal
1. Press down on back of the Series PD until the bottom hook clears the rail.
2. Rotate bottom up and away from rail.
Watlow Series PD 5 Chapter 2 Install and Wire
Series PD Connector Locations
Two connectors on the bottom of the unit provide connection points for the input power, inputs
and outputs. These connectors are removable and each terminal position is numbered.
The RJ-45 connector is located on the top of the Series PD to allow connection to an Ethernet
network.
Input and Output Connectors
Figure 5a — Input and Output Connectors
Ethernet RJ-45 Connector
Figure 5b — RJ-45 Connector
Ethernet RJ-45
Connector
Jumper to default
IP address on
power up
Input Connector
Controller Power and
Output Connector
Bottom View
Watlow Series PD 6 Chapter 2 Install and Wire
Ó
Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may re-
sult in damage to equipment and
property, and/or injury or loss of
life.
Ó
WARNING: If high voltage is ap-
plied to the controller, irre-
versible damage will occur.
Note: 24 V
ÅÅ
input power re-
quired to use single cycle,vari-
able time base output function.
Wiring the Series PD
The model number for each output option appears with its wiring diagram.
Check the label on the controller and compare your model number to those
shown here and to the model number breakdown in the Appendix of this
manual.
All outputs are referenced to a de-energized state.
All wiring and fusing must conform to the National Electric Code and to
any locally applicable codes as well.
Figure 6a — Power Wiring
(all model numbers)
• Nominal voltage: 24V (ac/dc)
25 26
25
26
-
+
24V(ac/dc)
L2
L1
Isolation Blocks
There are no electrical connections between these blocks
Relay outputs (mechanical and solid-state) provide isolation through their
relay contacts. Each relay output is isolated from the blocks above and is
isolated from other relay outputs.
Analog Input 1
Digital Inputs
Current Transformer Inputs
Analog Input 2
Control Outputs
Alarm Outputs
Retransmit Outputs
Communications
Watlow Series PD 7 Chapter 2 Install and Wire
Ó
Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may re-
sult in damage to equipment and
property, and/or injury or loss of
life.
Figure 7a — Thermocouple Input 1
(all model numbers)
Thermocouples are polarity sensitive. The negative lead (usually red) must be
connected to terminal 9.
• Input impedance: >20 M
Figure 7b — Thermocouple Input 2
PDD _-_ _ _ _-_ _ _ _
Thermocouples are polarity sensitive. The negative lead (usually red) must be
connected to terminal 5.
• Input impedance: >20 M
• Input 2 isolated from Input 1
Figure 7c — 2-Wire RTD Input 1 (100 DIN curve 0.00385
//°C)
(all model numbers)
Terminals 9 and 11 must be shorted for a two-wire RTD.
• Nominal excitation current: 250 µA
Figure 7d — 3-Wire RTD Input 1 (100 DIN curve 0.00385
//°C)
(all model numbers)
The S1 lead (usually white) must be connected to terminal 10.
• Nominal excitation current: 250 µA
9 10 11 12
10 S1
11 S2
9 S3
12 INFOSENSE-P™ DATA
INFOSENSE-P™ GND
9 10 11 12
10 S1
11 S2
9 S3
9 10 11 12
10 S1
11 S2
9
5 6 7 8
6 +
5 -
8 INFOSENSE-P™ DATA
INFOSENSE-P™ GND
5 6 7 8
6 +
5 -
9 10 11 12
10 +
9 -
12 INFOSENSE-P™ DATA
INFOSENSE-P™ GND
9 10 11 12
10 +
9 -
Watlow Series PD 8 Chapter 2 Install and Wire
ç
Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may re-
sult in damage to equipment and
property, and/or injury or loss of
life.
ç
WARNING: Process input may
not have sensor break protec-
tion. Outputs can remain full on.
Figure 8a — 2-Wire RTD Input 2 (100 DIN curve 0.00385
//°C)
PDD _-_ _ _ _-_ _ _ _
Terminals 5 and 7 must be shorted for a two-wire RTD.
• Nominal excitation current: 250 µA
Figure 8b — 3-Wire RTD Input 2 (100 DIN curve 0.00385
//°C)
PDD _-_ _ _ _-_ _ _ _
The S1 lead (usually white) must be connected to terminal 6.
• Nominal excitation current: 250 µA
Figure 8c — Input 1, 0 to 10V
ÎÎ
(dc) Process Input
(all model numbers)
• Input impedance 20 k, dc only
Figure 8d — Input 2, 0 to 10V
ÎÎ
(dc) Process Input
PDD _-_ _ _ _-_ _ _
• Input impedance 20 k, dc only
• Input 2 isolated from Input 1
5 6 7 8
8
5
+
-
9 10 11 12
12
9
+
-
5 6 7 8
6 S1
7 S2
5 S3
8 INFOSENSE™ DATA
INFOSENSE™ GND
5 6 7 8
6 S1
7 S2
5 S3
5 6 7 8
6 S1
7 S2
5
Watlow Series PD 9 Chapter 2 Install and Wire
Ó
Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may re-
sult in damage to equipment and
property, and/or injury or loss of
life.
ç
WARNING: Process input may
not have sensor break protec-
tion. Outputs can remain full on.
Note: Install a 1k pull-down
resistor for each digital in-
put using voltage inputs.
Note: Install a 10k pull-up re-
sistor for each digital input
using contact closure in-
puts.
Figure 9a — Input 1, 0 to 20 mA Process Input
(all model numbers)
• Input impedance 100 , dc only
• Controller does not supply power for the current loop
Figure 9b — Input 2, 0 to 20 mA Process Input
PDD _-_ _ _ _-_ _ _
• Input impedance 100 , dc only
• Controller does not supply power for the current loop
• Input 2 isolated from Input 1
Dual Digital Inputs
PD_ 1-_ _ _ _-_ _ _
• Input impedance 10k, dc only
• Input 2 isolated from Input 1
Figure 9c — Voltage input
0-1VÎ (dc) Event Input Low State
2-36VÎ (dc) Event Input High State
Figure 9d — Contact closure
0-2kEvent Input Low State
> 7kEvent Input High State
1 2 3 4
4
1
+5V(dc)
2
3
Digital Common
Digital Input 1
Digital Input 2
10k 10k
Add a 10k pull
up resistor for each
active input
1 2 3 4
1
2
3
Digital Common
Digital Input 1 +
Digital Input 2 +
-
1k
1k
Add a 1k pull
down resistor for
each active input
5 6 7 8
7
5
+
-
9 10 11 12
11
9
+
-
Watlow Series PD 10 Chapter 2 Install and Wire
ç
Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may re-
sult in damage to equipment and
property, and/or injury or loss of
life.
Note: Current transformer (CT)
must be purchased separately.
Note: A current transformer input
cannot be associated with a
process output on Output 1 or 3.
Figure 10a — Digital input internal circuit
Dual Current Transformer (CT) Inputs
PD_ 3-_ _ _ _-_ _ _
• Input impedance 100, Vac only.
The current transformer (CT) must be purchased separately. Watlow CT
part number is 16-0246 (up to 50 amps).
Systems that are more than 50 amps need an interstage transformer. For
example, if you use a 300 amp CT, part number 16-0073, and an interstage
transformer, part number 16-0176, the 300 amp CT provides a 5 amp signal
to the interstage transformer. In turn, the interstage transformer provides a
20 mA maximum signal to the controller.
Figure 10b — Single Phase
1 2 3 4
1
2
3
CT Common
CT Input 1
CT Input 2
L2
L1
CT
Load wire
Center leg not used
To CT Input 1 or 2
To CT Common
AC Load
CT Input 1 or 2
CT Common
0 to 5A
AC
0 to
20mA
A
Single phase current sensing up to 300 amp
16-0176
Transformer
Digital Input 2 (3)
Digital Input Common (1)
Internal Circuitry
Digital Input 1 (2)
Watlow Series PD 11 Chapter 2 Install and Wire
ç
Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may re-
sult in damage to equipment and
property, and/or injury or loss of
life.
Note: Current transformer (CT)
must be purchased separately.
Note: A current transformer input
cannot be associated with a
process output on Output 1 or 3.
Note: Install a 1k pull-down
resistor for each digital in-
put using voltage inputs.
Note: Install a 10k pull-up re-
sistor for each digital input
using contact closure in-
puts.
Figure 11a — Three Phase using Two Current Transformers
One Digital Input and One Current Transformer Input
PD_ 2-_ _ _ _-_ _ _
Digital Input 1
• Input impedance 10k, dc only
Figure 11b — Voltage input
0-1VÎ (dc) Event Input Low State
2-36VÎ (dc) Event Input High State
Figure 11c — Contact closure
0-2kEvent Input Low State
> 7kEvent Input High State
1 2 3 4
4
1
+5V(dc)
2
3
Digital Common
Digital Input 1
10k
Contact Closure
(add a 10k pull
up resistor for each
active input)
1 2 3 4
1
2
Digital Common
Digital Input 1 +
-
1k
Add a 1k pull
down resistor for
each active input
1 2 3 4
Bk
Red
Red
WhBk
BkWh
Bk
16-0176
Transformer
CT
CT
L1
L3
L2
5A
20mA
3-phase current sensing up to 300 amp
To CT Input 1 or 2
To CT Common
1
2
3
CT Common
CT Input 1
CT Input 2
L3
L1
L2
Phase
dot
To CT Input 1 or 2
To CT Common
Watlow Series PD 12 Chapter 2 Install and Wire
ç
Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may re-
sult in damage to equipment and
property, and/or injury or loss of
life.
Note: Current transformer (CT)
must be purchased separately.
Note: A process output cannot be
installed on Output 1 or 3 when
using current transformer input.
Figure 12a — Current Transformer Input 2, Single Phase
• Input impedance 100, Vac only
The current transformer must be purchased separately. Watlow current
transformer part number is 16-0246 (up to 50 amps).
Systems that are more than 50 amps need an interstage transformer. For
example, if you use a 300 amp current transformer, part number 16-0073,
and an interstage transformer, part number 16-0176, the 300 amp current
transformer provides a 5 amp signal to the interstage transformer. In turn,
the interstage transformer provides a 20 mA maximum signal to the con-
troller.
Figure 12b — Current Transformer Input 2, Three Phase
1 2 3 4
Bk
Red
Red
WhBk
BkWh
Bk
16-0176
Transformer
CT
CT
L1
L3
L2
5A
20mA
3-phase current sensing up to 300 amp
To CT Input 2
To CT Common
1
3
CT Common
CT Input 2
L3
L1
L2
Phase
dot
1 2 3 4
1
3
CT Common
CT Input 2
L2
L1
CT
Load wire
Center leg not used
AC Load
CT Input 2
CT Common
0 to 5A
AC
0 to
20mA
A
Single phase current sensing up to 300 amp
16-0176
Transformer
Watlow Series PD 13 Chapter 2 Install and Wire
ç
Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may re-
sult in damage to equipment and
property, and/or injury or loss of
life.
Quencharc Note:
Switching pilot duty loads (relay
coils, solenoids, etc.) with the
mechanical relay or solid-state
relay output options requires use
of an R.C. suppressor.
Watlow carries the R.C. suppres-
sor Quencharc brand name,
which is a trademark of ITW
Paktron. Watlow Part No. 0804-
0147-0000.
Note: 24 V
ÅÅ
input power re-
quired to use single cycle,vari-
able time base output function.
Figure 13a — Output 1 Mechanical Relay
PD_ _ - J _ _ _ - _ _ _ _
• Form A contact
• 2 A, resistive
• 125 VA pilot duty, 120/240VÅ (ac), inductive
• 240VÅ (ac) maximum
• 30VÎ (dc) maximum
• See Quencharc note
• For use with ac or dc
• Minimum load current 10 mA
• Output does not supply power
Figure 13b — Output 1 Solid-state Relay
PD_ _ - K _ _ _ - _ _ _ _
• Form A contact
• 0.5 A, resistive
• 20 VA pilot duty, 120/240VÅ (ac), inductive
• 24 to 240VÅ (ac)
• See Quencharc note
• Minimum load current 10 mA
• Maximum leakage current 100 µA
• Not for use with direct current (dc)
• Output does not supply power
Figure 13c — Output 1 Switched DC
PD_ _ - C_ _ _ - _ _ _ _
• Supply current 30 mAÎ (dc) maximum
• Supply voltage 24VÎ (dc)
• Not recommended for switching mechanical relays
• Output supplies power
Internal Circuitry
dc-
dc+
24VÎ (dc)
Load
Switched DC
-
+
13
15
13 14 15
15 dc -
13 dc +
14 com
Internal Circuitry
COM.
N.O.
Solid-state Relay
14
15
Solid-state Switch
13 14 15
15 normally open
14 com
Internal Circuitry
COM.
N.O.
Mechanical Relay
14
15
13 14 15
15 normally open
14 com
Watlow Series PD 14 Chapter 2 Install and Wire
ç
Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may re-
sult in damage to equipment and
property, and/or injury or loss of
life.
Quencharc Note:
Switching pilot duty loads (relay
coils, solenoids, etc.) with the
mechanical relay or solid-state
relay output options requires use
of an R.C. suppressor.
Watlow carries the R.C. suppres-
sor Quencharc brand name,
which is a trademark of ITW
Paktron. Watlow Part No. 0804-
0147-0000.
Note: A current transformer input
is not available for Output 1 or 3
if a process output.
Note: 24 V
ÅÅ
input power re-
quired to use single cycle,vari-
able time base output function.
Figure 14a — Output 1 Open Collector
PD_ _ - C_ _ _ - _ _ _ _
• Maximum current sink 200 mAÎ (dc)
• Maximum supply voltage 42VÎ (dc)
• Output does not supply power
Figure 14b — Output 1 Process
PD_ _ - F_ _ _ - _ _ _ _
• Analog output is scalable between 0 to 10VÎ (dc) or 0 to 20 mAÎ (dc)
• Load capability: voltage 1 kminimum; current 800 maximum
• Output supplies power
• Cannot use voltage and current output at the same time
Figure 14c — Output 2 Mechanical Relay
PD_ _ - _ E _ _ - _ _ _ _
• Form C contacts
• 2 A, resistive
• 125 VA pilot duty, 120/240VÅ (ac), inductive
• 240VÅ (ac) maximum
• 30VÎ (dc) maximum
• See Quencharc note
• For use with ac or dc
• Minimum load current: 10 mA
• Output does not supply power
Internal Circuitry
COM.
N.O.
Mechanical Relay
17
18
N.C.
16
16 17 18
18 normally open
17 com
16 normally closed
13 14 15
15 amps +
13 volts +
14 com -
Internal Circuitry
dc-
COM.
dc+
42VÎ (dc) maximum
Open Collector
13
15
14
Load
-
+
Power
Supply
-
+
Class 2 power source
required for agency
compliance.
13 14 15
15 dc -
13 dc +
14 com
Watlow Series PD 15 Chapter 2 Install and Wire
ç
Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may re-
sult in damage to equipment and
property, and/or injury or loss of
life.
Quencharc Note:
Switching pilot duty loads (relay
coils, solenoids, etc.) with the
mechanical relay or solid-state
relay output options requires use
of an R.C. suppressor.
Watlow carries the R.C. suppres-
sor Quencharc brand name,
which is a trademark of ITW
Paktron. Watlow Part No. 0804-
0147-0000.
Note: 24 V
ÅÅ
input power re-
quired to use single cycle,vari-
able time base output function.
Figure 15a — Output 2 Solid-state Relay
PD_ _ - _ K _ _ - _ _ _ _
• Form A contact
• 0.5 A, resistive
• 20 VA pilot duty, 120/240VÅ (ac), inductive
• 24 to 240VÅ (ac)
• See Quencharc note
• Minimum load current 10mA
• Maximum leakage current 100µA
• Not for use with direct current (dc)
• Output does not supply power
Figure 15b — Output 2 Switched DC
PD_ _ - _ C _ _ - _ _ _ _
• Maximum supply current 30 mAÎ (dc)
• Supply voltage 24VÎ (dc)
• Not recommended for switching mechanical relays
• Output supplies power
Figure 15c — Output 2 Open Collector
PD_ _ - _ C _ _ - _ _ _ _
• Maximum current sink 200 mAÎ (dc)
• Maximum supply voltage 42VÎ (dc)
• Output does not supply power
Internal Circuitry
dc-
COM.
dc+
42VÎ (dc) maximum
Open Collector
16
18
17
Load
-
+
Power
Supply
-
+
Class 2 power source
required for agency
compliance.
16 17 18
18 dc -
16 dc +
17 com
Internal Circuitry
dc-
dc+
24VÎ (dc)
Load
Switched DC
-
+
16
18
16 17 18
18 dc -
16 dc +
17 com
Internal Circuitry
COM.
N.O.
Solid-state Relay
17
18
Solid-state Switch
16 17 18
18 normally open
17 com
Watlow Series PD 16 Chapter 2 Install and Wire
ç
Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may re-
sult in damage to equipment and
property, and/or injury or loss of
life.
Quencharc Note:
Switching pilot duty loads (relay
coils, solenoids, etc.) with the
mechanical relay or solid-state
relay output options requires use
of an R.C. suppressor.
Watlow carries the R.C. suppres-
sor Quencharc brand name,
which is a trademark of ITW
Paktron. Watlow Part No. 0804-
0147-0000.
Note: 24 V
ÅÅ
input power re-
quired to use single cycle,vari-
able time base output function.
Figure 16a — Output 3 Mechanical Relay
PD_ _ - _ _ J _ - _ _ _ _
• Form A contact
• 2 A, resistive
• 125 VA pilot duty, 120/240VÅ (ac), inductive
• 240VÅ (ac) maximum
• 30VÎ (dc) maximum
• See Quencharc note
• For use with ac or dc
• Minimum load current: 10 mA
• Output does not supply power
Figure 16b — Output 3 Solid-state Relay
PD_ _ - _ _ K _ - _ _ _ _
• Form A.contact
• 0.5 A, resistive
• 20 VA pilot duty, 120/240VÅ (ac), inductive
• 24 to 240VÅ (ac)
• See Quencharc note
• Minimum load current 10 mA
• Maximum leakage current 100 µA
• Not for use with direct current (dc)
• Output does not supply power
Figure 16c — Output 3 Switched DC
PD_ _ - _ _ C _ - _ _ _ _
• Maximum supply current 30 mAÎ (dc)
• Supply voltage 24VÎ (dc)
• Not for switching mechanical relays
• Output supplies power
Internal Circuitry
dc-
dc+
24VÎ (dc)
Load
Switched DC
-
+
19
21
19 20 21
21 DC -
19 DC +
20 com
Internal Circuitry
COM.
N.O.
Solid-state Relay
20
21
Solid-state Switch
19 20 21
21 normally open
20 com
Internal Circuitry
COM.
N.O.
Mechanical Relay
20
21
19 20 21
21 normally open
20 com
Watlow Series PD 17 Chapter 2 Install and Wire
ç
Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may re-
sult in damage to equipment and
property, and/or injury or loss of
life.
Quencharc Note:
Switching pilot duty loads (relay
coils, solenoids, etc.) with the
mechanical relay or solid-state
relay output options requires use
of an R.C. suppressor.
Watlow carries the R.C. suppres-
sor Quencharc brand name,
which is a trademark of ITW
Paktron. Watlow Part No. 0804-
0147-0000.
Note: A current transformer input
is not available for Output 1 or 3
if a process output.
Note: 24 V
ÅÅ
input power re-
quired to use single cycle,vari-
able time base output function.
Figure 17a — Output 3 Open Collector
PD_ _ - _ _ C _ - _ _ _ _
• Maximum current sink 200 mAÎ (dc)
• Maximum supply voltage 42VÎ (dc)
• Output does not supply power
Figure 17b — Output 3 Process
PD_ _ - _ _ F _ - _ _ _ _
• Analog output scalable from 0 to 10VÎ (dc) or 0 to 20 mAÎ (dc)
• Load capability: voltage, 1 kminimum; current, 800 maximum
• Output supplies power
• Cannot use voltage and current output at the same time
Figure 17c — Output 4 Mechanical Relay
PD_ _ - _ _ _ E - _ _ _ _
• Form C.contacts
• 2 A, resistive
• 125 VA pilot duty, 120/240VÅ (ac), inductive
• 240VÅ (ac) maximum
• 30VÎ (dc) maximum.
• See Quencharc note
• For use with ac or dc
• Minimum load current: 10 mA
• Output does not supply power
Internal Circuitry
COM.
N.O.
Mechanical Relay
23
24
N.C.
22
22 23 24
24 normally open
23 com
22 normally closed
19 20 21
21 amps +
19 volts +
20 com -
Internal Circuitry
dc-
COM.
dc+
42VÎ (dc) maximum
Open Collector
19
21
20
Load
-
+
Power
Supply
-
+
Class 2 power source
required for agency
compliance.
19 20 21
21 DC -
19 DC +
20 com
Watlow Series PD 18 Chapter 2 Install and Wire
ç
Warning:
Use National Electric (NEC) or
other country-specific standard
wiring and safety practices when
wiring and connecting this con-
troller to a power source and to
electrical sensors or peripheral
devices. Failure to do so may re-
sult in damage to equipment and
property, and/or injury or loss of
life.
Quencharc Note:
Switching pilot duty loads (relay
coils, solenoids, etc.) with the
mechanical relay or solid-state
relay output options requires use
of an R.C. suppressor.
Watlow carries the R.C. suppres-
sor Quencharc brand name,
which is a trademark of ITW
Paktron. Watlow Part No. 0804-
0147-0000.
Note: 24 V
ÅÅ
input power re-
quired to use single cycle,vari-
able time base output function.
Figure 18a — Output 4 Solid-state Relay
PD_ _ - _ _ _ K - _ _ _ _
• Form A.contact
• 0.5 A, resistive
• 20 VA pilot duty, 120/240VÅ (ac), inductive
• 24 to 240VÅ (ac)
• See Quencharc note
• Minimum load current 10mA
• Maximum leakage current 100µA
• Not for use with direct current (dc)
• Output does not supply power
Figure 18b — Output 4 Switched DC
PD_ _ - _ _ _ C - _ _ _ _
• Maximum supply current 30 mAÎ (dc)
• Supply voltage 24VÎ (dc)
• Not recommended for switching mechanical relays
• Output supplies power
Figure 18c — Output 4 Open Collector
PD_ _ - _ _ _ C - _ _ _ _
• Maximum current sink 200 mAÎ (dc)
• Maximum supply voltage 42VÎ (dc)
• Output does not supply power
Internal Circuitry
dc-
COM.
dc+
42VÎ (dc) maximum
Open Collector
22
24
23
Load
-
+
Power
Supply
-
+
Class 2 power source
required for agency
compliance.
22 23 24
24 dc -
22 dc +
23 com
Internal Circuitry
dc-
dc+
24VÎ (dc)
Load
Switched DC
-
+
22
24
22 23 24
24 dc -
22 dc +
23 com
Internal Circuitry
COM.
N.O.
Solid-state Relay
23
24
Solid-state Switch
22 23 24
24 normally open
23 com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188

Watlow Series PD User manual

Category
Measuring, testing & control
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI