  • Hello! I am an AI chatbot trained to assist you with the Emerson SPA-300 Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Edco SPA-300
Medium Duty 120 VAC — 1 Phase
Surge Protection
For Business-Critical Continuity
TM
The Edco SPA-300 is designed to protect sensitive electronic equipment such as traffic
controllers, from high energy surges. The Edco SPA-300 incorporates MOV technology
which clamps these surges before equipment damage occurs.
The Edco SPA-300 is intended for use on bonded neutral to ground applications.
Features
40 kA surge protection
Fast response time
Solid-state design
Epoxy encapsulated
5 year warranty
Part Number Edco SPA-300
Operating Voltage 120 VAC
Clamping Voltage 395 VAC
Operating Current NA
Peak Surge Current 40 kA/Mode/Phase/Total
Operating Frequency 47-63 Hz
EMI Attenuation NA
SPD Technology MOVs
Status Indication NA
Connection Type 1/4 -20 Stainless Steel Stud
Operating Temperature -40°C to +85°C
Dimensions (Inches) 1.875H x 2.875W x 5.25L
Weight 1 lb
General Technical Specifications
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Control
Racks and Integrated Cabinets
Services
Precision Cooling
Surge Protection
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity
TM
.
IO-50132 2/09 Rev. 1 Printed in USA
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power
logo are trademarks and service marks of Emerson Electric Co. ©2009 Emerson Electric Co.
www.emersonnetworkpower.com
Emerson Network Power Contact information
Headquarters
Surge Protection
328 Water Street 650 SW 27th Avenue
Binghamton, NY 13901 Ocala, FL 34471
T: (607) 721-8840 T: (352) 732-3029
T: (800) 288-6169 T: (800) 648-4076
F: (607) 722-8713 F: (352) 867-1237
E: contactsurge@emerson.com
Installation
Mounting
Caution
This product should be installed and
serviced by qualified service technicians
or personnel only.
Remove power before installation or
service.
Hot
Line
Load
120
VAC
SPA-300
Neutral
Ground
2.875"
PLATE
4.875"
5.25"
Hole 3/16"
/