EDWARDS 116DEGEX()-FJ Installation guide

  • Hello! I've reviewed the Edwards Signaling 116DEGEX(*)-FJ Series Mass Notification Strobe Installation Sheet. This document provides instructions for installing, wiring, and maintaining these strobes in hazardous locations. It also covers key features like the strobe's 360-degree beam, flash rate, and compliance with UL standards. I'm ready to assist with any questions you have.
  • What is the intended use for 116DEGEX(*)-FJ Series Mass Notification Strobes?
    What standards do these strobes meet or exceed?
    What is the flash rate of the strobe?
    What type of enclosure are these strobes listed as?
    What mounting options are available?
© 2018 United Technologies Corporation 1 / 5 P/N 3101633-EN • REV 004 • ISS 22OCT18
116DEGEX(*)-FJ Series Mass Notification Strobe for Hazardous
Locations Installation Sheet
Description
The 116DEGEX(*)-FJ Series Mass Notification Strobes are heavy
duty, diode polarized, in-rush current-limited strobes intended for use
in Mass Notification signaling (non-fire alarm) applications requiring
electrical supervision of signaling circuit wiring. When pendant, wall, or
ceiling mounted, the strobe meets or exceeds the requirements of UL
1638 Visual Signaling Appliances - Private Mode Emergency and
General Utility Signaling.
The strobe is intended for indoor or outdoor use in applications
requiring electrical supervision of signaling circuit field wiring. The
strobe flashes a 360-degree beam of light approximately 65 times per
minute. The strobe has been evaluated to UL 1971 polar plot
requirements with “on axis” light output values (Figure 6 and Figure 7).
The strobe features an enhanced synchronization circuit to comply with
the latest requirements of UL 1971 Signaling Devices for the Hearing
Impaired and the latest Canadian standard CAN/ULC-S526.
Synchronized operation requires a separately installed synchronization
control module. See Table 1 for a list of compatible synchronization
modules.
When assembled with an available mounting subassembly (116EX-P,
116EX-C, or 116EX-C with 116EX-B) and in accordance with these
instructions, the 116DEGEX(*)-FJ visual strobe signal is UL Listed as a
Mass Notification Signaling Appliance for use in Class I, Division 1,
Groups C and D, Class I, Division 2, Groups A, B, C, and D
(hazardous or nonhazardous locations), Class II Division 1, Groups E,
F, and G, Class II, Division 2, Group F and G, and Class III Division 1
and 2 hazardous locations with Operating Temperature Codes per
Table 3. Refer to “Specifications” on page 4 for more information.
This strobe is UL and cUL Listed as a Type 3R and 4X enclosure.
Refer to Figure 5.
Note: This equipment is suitable for use in Class, Division and Group
as defined in Product Covered or non-hazardous locations (Table 3).
Installation
WARNINGS
Explosion hazard. To reduce the risks of ignition of hazardous
atmospheres and shock, do not apply power to the unit until
installation has been completed and unit is tightly assembled and
secured.
Explosion hazard. Do not remove or replace lamps, fuses, or
adjustment switch/potentiometer unless the power has been
disconnected or the area is known to be free of ignitable
concentrations of flammable gases or vapors.
Explosion hazard. To reduce the risk of ignition of hazardous
atmospheres and shock, keep the assembly tightly closed when
circuits are energized.
Explosion hazard. Do not disconnect equipment while the circuit
is live or unless the area is known to be free of ignitable
concentrations.
Install this unit in accordance with the applicable requirements in the
latest edition of NFPA 70 National Electrical Code.
Note: This equipment is suitable for use in Class, Division, and Group
as defined in Product Covered or non-hazardous locations (Table 2).
1. Mount the signal using one of the following applicable methods.
a. Pendant mount models (Figure 1): Install the pendant
mount module, Cat. No. 116EX-P, to the main housing.
Tighten the setscrew. Install an explosion-proof hanger box
(not supplied). Secure the 3/4 in. NPT threaded conduit (not
supplied) to the box. Install the unit on the conduit. Ensure
the conduit engages at least five full threads and then tighten
the setscrew to secure the pendant mount module to the
conduit. Connect the field earth ground wire to the ground
screw or earth ground via the conduit system. Wire in
accordance with Figure 4. See Table 3 for required supply
wire temperature ratings.
b. Ceiling mount models (Figure 2): Mount the ceiling mount
module, Cat. No. 116EX-C, using hardware (not supplied)
that is suitable for the mounting surface. Connect field earth
ground wire to the ground screw or earth ground via conduit
system. Wire the unit in accordance with Figure 4. See
Table 3 for required supply wire temperature ratings. Install
the main housing to the ceiling mount module. Tighten the
setscrew to secure the main housing to the ceiling mount
module.
c. Wall/bracket mount models (Figure 3): Install the ceiling
mount module, Cat. No. 116EX-C, using hardware (not
supplied) that is suitable for the mounting surface. Install the
wall mount module, Cat. No. 116EX-B, to the main housing.
Tighten the setscrew to secure the wall mounting module to
the main housing. Run the unit's wiring through the elbow to
the wall box. Connect the field earth ground wire to the
ground screw or earth ground via the conduit system. Wire
the unit in accordance with Figure 4. See Table 3 for
required supply wire temperature ratings. Install the main
2 / 5 P/N 3101633-EN • REV 004 • ISS 22OCT18
housing and 116EX-B wall mount module to the ceiling
mount module. Tighten the setscrew to secure the 116EX-B
wall mount module to the ceiling mount module.
2. Apply power to the unit and ensure proper operation.
Maintenance
WARNINGS
Explosion hazard. To reduce the risk of ignition of hazardous
atmospheres and shock, keep the assembly tightly closed when
circuits are energized.
Explosion hazard. To reduce the risk of ignition of hazardous
atmospheres and shock, disconnect from the supply and circuit
and allow 5 minutes for stored energy to dissipate before
disassembling the unit.
Explosion hazard. To reduce the risk of ignition of hazardous
atmospheres and shock, disconnect from the supply and circuit
and allow 5 minutes for stored energy to dissipate before
disassembling the unit.
Caution: Equipment damage hazard. To prevent damage to the signal
circuit and to otherwise assure continued proper functioning, do not
operate the unit outside of the Regulated 24 DC or 24 FWR voltage
range of 16 to 33 VDC or VFWR.
To disassemble the unit (Figure 8):
1. Loosen the three guard screws and remove the guard.
2. Loosen the globe and ring assembly setscrew. Insert a suitable
tool into the notches in the globe and ring assembly and loosen the
assembly by prying in a counterclockwise direction. Remove the
ring and globe assembly.
3. Refer to Table 2 for the replacement catalog number. Replace the
lens.
4. To replace the globe, simply screw the unit on until it seats firmly
onto its gasket. Tighten the unit another 1/8 to 1/4 turn. Tighten the
setscrew.
5. Reinstall the guard, where applicable, and secure using the three
supplied screws.
6. After the unit is assembled, apply power and make sure the unit
functions properly.
Figure 1: Detail of pendant mounting
(1) Setscrews
Figure 2: Detail of ceiling mounting
(1) Setscrew
Figure 3: Detail of wall/bracket mounting
(1) Setscrews
1 in.
13 in.
13-3/4 in.
7-1/4 in.
5/16 in.
4 in.
4 in.
6-3/4 in.
(1)
(171.45 mm)
(101.6 mm)
(101.6 mm)
(7.93 mm)
(25.4 mm)
(330.2 mm)
(184.15 mm)
1 in.
12-9/16 in.
9-7/16 in.
16-1/16 in.
16-13/16 in.
5/16 in.
4 in.
4 in.
6-3/4 in.
(1)
(319 mm)
(239.7 mm)
(408 mm)
(427 mm)
(25.4 mm)
(171.45 mm)
(101.6 mm)
(8 mm)
P/N 3101633-EN • REV 004 • ISS 22OCT18 3 / 5
Figure 4: Wiring
(1) White
(2) Black
(3) 116DEGEX Series
(4) From power source or previous signaling device
(5) End-of-line resistor, when required with supervised system
Legend
Strobe symbol
Wire nut symbol
Notes
The DC polarity of the circuit shown in supervisory state (signal inactive). Circuit polarity to reverse to activate signal.
Electrical supervision requires wire run to be broken at each device.
Device requires constant input voltage. Do not connect to “coded” or pulsating voltage.
For non-supervised circuit wiring installations, the installer can tie the two white leads together and tie the two black leads together.
Figure 5: Mounting options
(1) Ceiling 116EX-C 3/4 in. conduit entries
(2) Pendant 116EX-P 3/4 in. conduit entry
(3) 116EX-C (wall mounted) 3/4 in. conduit entries
(4) Wall/bracket 116EX-B 3 in. hub
(5) 116 Series housing and globe assembly with guard
(1)
(2)
(3)
(4)
(5)
4 / 5 P/N 3101633-EN • REV 004 • ISS 22OCT18
Figure 6: Effective candela light output for wall bracket mount,
vertical plane (zero degree angle at side of globe)
Mass notification output rating
Red
Amber
Green
Blue
Magenta
6 cd
36 cd
19 cd
10 cd
9 cd
Figure 7: Effective candela light output for ceiling mount, X & Y
planes (zero degree angle at bottom of globe)
Mass notification output rating
Red
Amber
Green
Blue
Magenta
6 cd
33 cd
19 cd
8 cd
9 cd
Figure 8: Disassembly
(1) Strobe tube
(2) Lens
(3) Globe and ring assembly
(4) Guard
Specifications
Voltage
** 16 to 33 VDC / VFWR
Max. RMS operating current*
UL/cUL
UL only
cUL only
0.540 A at 24 VDC Regulated
0.520 A at 24 VFWR Regulated
0.683 A at 24 VFWR Regulated
*The Max. RMS operating current is defined as the
maximum current
rating over the entire voltage range.
**The designation “Regulated 24” refers to the voltage range of
16 to 33 volts.
Table 1: 116DEGEX(*)-FJ compatible synchronization modules
Model names
Model numbers
Auto
-sync output module SIGA-CC1S
SIGA-CC1S-LG
SIGA-MCC1S
SIGA-MCC1S-LG
Genesis signal master
remote mount ADTG1M-RM
EG1M-RM
G1M-RM
G1M-RM-LG
MG1M-RM
XLSG1M-RM
ZG1M-RM
Table 2: Catalog numbers
Description
Catalog number
Housing less mounting module
116DEGEX(*)-FJ
Ceiling mount module
116EX-C
Pendant mount module
116EX-P
Wall mount module (requires use of
ceiling mount module)
116EX-B
* Letter in this position indicates lens color: A = amber, B = blue,
G = green, M= magenta, R = red
(1)
(2)
(3)
(4)
P/N 3101633-EN • REV 004 • ISS 22OCT18 5 / 5
Table 3: Temperature ratings
Ambient temp.
Supply wire temp.
marking
Class I, Div. 2
Groups A, B
Class I, Div. 1 & 2
Groups C, D
Class II & III, Div. 1
Groups E, F, G
Class II & III, Div. 2
Groups F, G
40°C
75°C T2B (260°C) T6 (85°C) T4A (120°C) T4A (120°C)
55
°C 90°C T2B (260°C) T6 (85°C) T4 (135°C) T4 (135°C)
65
°C 105°C T2B (260°C) T6 (85°C) T3C (160°C) T3C (160°C)
Regulatory information
Ratings
UL 1638 Visual Signaling Appliance Private Mode
Emergency and General Utility Signaling
UL 1638A Visual Signal Appliance for General
Signaling Use
UL 1203 Explosion-Proof and Dust-Ignition-Proof
Electrical Equipment for use in Hazardous (Classified)
Locations
UL 121201 Nonincendive Electrical Equipment for use
In Class I and II, Division 2 and Class III, Divisions 1
and 2 Hazardous (Classified) Locations
CSA C22.2 No. 25 Enclosures for use in Class II
Groups E, F, and G Hazardous Locations
CSA C22.2 No. 30 Explosion-
Proof Enclosures for use
in Class I Hazardous Locations
CSA C22.2 No. 213 Nonincendive Electrical
Equipment for use in Class I and II, Division 2 and
Class III, Division 1 and 2 Hazardous (Classified)
Locations
UL and cUL listed Type 3R and 4X enclosure
Contact information
For contact information, see www.edwardsfiresafety.com
/