Alpha innotec LWAV Owner's manual

Category
Heat pumps
Type
Owner's manual
UK
83059600jUK – Translation of the original operating manual
Air/Water Heat Pumps
Outdoor installation
Operating Manual
LWAV series
2
Subject to change without notice | 83059600jUK – Translation of the original operating manual | ait-deutschland GmbH
Table of contents
1 About this operating manual ...................... 3
1.1 Validity ....................................................... 3
1.2 Reference documents ............................... 3
1.3 Symbols and markings .............................. 3
1.4 Contact ...................................................... 4
2 Safety ............................................................... 4
2.1 Intended use ............................................. 4
  ............................ 4
2.3 Personal protective equipment ................. 4
2.4 Residual risks ............................................ 4
2.5 Disposal .................................................... 5
2.6 Avoid material damage ............................. 5
3 Description ...................................................... 6
3.1 As-delivered condition .............................. 6
3.2 Design ....................................................... 6
3.3 Accessories............................................... 7
3.4 Function .................................................... 7
4 Operation and care ....................................... 7
4.1 Energy and environmentally aware
operation ................................................... 7
4.2 Care .......................................................... 7
5 Delivery, storage, transport and
installation ....................................................... 8
5.1 Scope of supply ........................................ 8
5.2 Storage ...................................................... 8
5.3 Unpacking and transport ........................... 8
5.4 Installation ................................................. 9
5.5 Attach the side panel, the rear panel,
the cover and the front panel .................. 10
6 Installation of hydraulic system .................11
7 Electrical installation ................................... 12
  ...................... 12
8.1 Heating water quality .............................. 12
 
circuit ....................................................... 13
9 Insulation of hydraulic connections ........ 13
  ......................... 13
11 Commissioning ............................................ 14
12 Maintenance ................................................. 15
12.1 Basic principles ....................................... 15
12.2 Maintenance as required ........................ 15
 ...... 16
12.4 Annual maintenance ............................... 16
13 Malfunctions ................................................. 16
14 Dismantling and disposal .......................... 16
14.1 Dismantling ............................................. 16
14.2 Disposal and recycling ............................ 16
Technical data / scope of supply ............ 17
Performance curves ................................... 18
LWAV 82R1/3 ................................................... 18
LWAV 122R3 .................................................... 20
Dimensional drawings ................................ 22
Installation plans .......................................... 24
Minimum clearances ........................................ 24
Connection set IPWAV vertical ........................ 25
Surface foundation ....................................... 26
Strip foundation ............................................ 27
Connection set WDFAV horizontal ................... 28
Surface foundation ....................................... 29
Strip foundation ............................................ 30
With condensate drain vertical ..................... 31
Condensate line........................................... 32
External condensate line connection ............... 32
Internal condensate line connection ................ 33
Hydraulic integration ................................... 34
LWAV with hydraulic station ............................. 34

hydraulic module ..................................... 35
 .................... 36
Keys hydraulic integration ................................ 37
Circuit diagrams ........................................... 38
LWAV 82R1/3 ................................................... 38
LWAV 122R3 .................................................... 40
EC Declaration of Conformity .................. 43
3
Subject to change without notice | 83059600jUK – Translation of the original operating manual | ait-deutschland GmbH
1 About this operating manual
This operating manual is an integral part of the unit.
Before working on or with the unit, always read
the operating manual carefully and follow it for all
activities at all times, especially the warnings and
safety instructions.
Keep the operating manual at hand at the unit and
hand it over to the new owner if the unit changes
hands.
If you have any questions or if anything is unclear,
ask the local partner of the manufacturer or the
factory’s customer service.
Observe all reference documents.
1.1 Validity
This operating manual refers solely to the unit identi-
 “Nameplate“,
page 7).
1.2 Reference documents
The following documents contain additional informa-
tion to this operating manual:
Heat pump guide, hydraulic integration
Operating manual of the heating and heat pump
controller
Short description of the heat pump controller
Operating manual of the extension board

Log book
1.3 Symbols and markings

Symbol Meaning
Safety-relevant information.
Warning of physical injuries.
DANGER Indicates an imminent danger re-
sulting in severe injuries or death.
WARNING Indicates a potentially dangerous
situation, which can result in se-
vere injuries or death.
CAUTION Indicates a potentially dangerous
situation, which can result in mod-
erate or minor injuries.
IMPORTANT Indicates a potentially dangerous
situation, which can result in ma-
terial damage.
Symbols in the document
Symbol Meaning
Information for specialist
Information for operator
Prerequisite for an action
Single-step instruction for action
1., 2., 3., Numbered step within a multi-step
instruction for action. Adhere to
the given sequence.
Additional information, e.g. a note
for making work easier, informa-
tion on standards
Reference to further information
elsewhere in the operating manual
or in another document
List
4
Subject to change without notice | 83059600jUK – Translation of the original operating manual | ait-deutschland GmbH
1.4 Contact
Addresses for purchasing accessories, for servicing or
for answers to questions about the unit and this oper-
ating manual can be found on the internet and are kept
up-to-date:
Germany: www.alpha-innotec.de
EU: www.alpha-innotec.com
2 Safety
Only use the unit if it is in perfect technical condition
and only use it as intended, safely and aware of the
hazards and under full observance of this operating
manual.
2.1 Intended use
The unit is intended exclusively for the following func-
tions:
Heating
-
cessories)
Cooling, reversible
Intended use includes complying with the operating
 Technical data / scope of supply,
page 17) and the operating manual and ob-
serving the reference documents.
If local regulations apply, observe: laws, stand-
ards and directives.
All other use of the unit is interpreted as not intended.
2.2 
The operating manuals supplied with the product are
intended for all users of the product.
The operation of the product via the heating and he-
at pump control and work on the product which is in-
tended for end customers / operators is suitable for all
age groups of persons who are able to understand the
activities and the resulting consequences and can car-
ry out the necessary activities.
Children and adults who are not experienced in hand-
ling the product and do not understand the necessa-
ry activities and the resulting consequences must be
instructed and, if necessary, supervised by persons
experienced in handling the product and who are re-
sponsible for safety.
Children must not play with the product.

All instructions and information in this operating manu-
-
sonnel.

out the work on the unit safety and correctly. Interfer-
-
ries and material damage.
Ensure that the personnel are familiar with the lo-
cal regulations, especially those relating to work-
ing safely and in awareness of the hazard risks.
Have work on the electrical and electronic compo-

“electrical” training.
Have any other work on the system carried out

Heating installers
Plumbers

work)
During the warranty and guarantee period, servicing
and repair work may only be carried out by personnel
authorised by the manufacturer.
2.3 Personal protective equipment
There is a risk of cutting your hands on sharp edges
of the unit.
Wear cut-resistant protective gloves during trans-
port.
2.4 Residual risks
Injuries caused by electric current
Components in the unit are live with fatal voltage. Be-
fore opening the unit casing:
Disconnect the unit from power supply.
Protect the unit against being switched back on
again.
Residual voltage at the inverter. Wait for 90 sec-
onds before opening the unit.
Existing earthing connections within housings or on
mounting plates must not be altered. If this should ne-
vertheless be necessary in the course of repair or as-
sembly work:
Restore earthing connections to their original con-
dition after completion of the work.
5
Subject to change without notice | 83059600jUK – Translation of the original operating manual | ait-deutschland GmbH
Risk of injury from moving parts
Only switch on the unit with fan protection grilles

Injuries and environmental damage due to
refrigerant
The unit contains harmful and environmentally dan-
gerous refrigerant. If refrigerant leaks out of the unit:
1. 
2. Notify authorised after sales service.
2.5 Disposal
Environmentally hazardous media
Improper disposal of environmentally hazardous me-

Collect media safely.
Dispose of the media in an environmentally sound
manner in accordance with to the local regula-
tions.
2.6 Avoid material damage
The ambient air at the heat pump’s installation site, as
well as the air drawn in as a heat source, must not
contain any corrosive components!
Constituents such as
Ammonia
Sulphur
Chlorine
Salt

can cause damage to the heat pump, which can even
result in the complete failure/total loss of the heat
pump.
Decommissioning/draining the heating
If the system/heat pump is decommissioned or drained
        
the condenser and any heat exchangers have been
drained completely for the event of freezing temper-
atures. Residual water in heat exchangers and con-
densers can result in damage to the components.
Completely drain the system and the condenser,
and open vent valves.
Blow them clear with compressed air, if required.
Improper action
Requirements for minimum scale and corrosion dam-
age in hot water heating systems:
Professional planning and commissioning
Closed system with regard to corrosion
Integration of an adequately dimensioned pres-
sure maintenance

water corresponding to the VDI 2035 norm
Regular servicing and maintenance
If a system is not planned, commissioned and operat-
ed in accordance with the given requirements, there
will be a risk of the following damage and malfunc-
tions:
Malfunctions and failure of components, e.g.
pumps, valves
Internal and external leaks, e.g. at heat exchangers
Reduction in cross-section and blockages in com-
ponents, e.g. heat exchangers, pipes, pumps
Material fatigue
  -
tation)
        -
mation of deposits, and associated noises, e.g.

Observe the information in this operating manual
for all work on and with the unit.

and replenishing the heating circuit

heat generator and the heating components depend
decisively on the quality of the heating water.
-
cium deposits will form as scale. Lime scale deposits
accumulate on the heat transfer surfaces of the heat-
        -
crease. In extreme cases, the heat exchangers will be
damaged.
Fill the system with deionised heating water


6
Subject to change without notice | 83059600jUK – Translation of the original operating manual | ait-deutschland GmbH
3 Description
3.1 As-delivered condition
1 Side panels with design grilles
2 Base frame, sheet metal supports for the fan
module
3 Front panel, cover, rear panel
 

installation site!)
 
3.2 Design
NOTE
This section essentially names the compo-

in this operating manual.
The heat pump module
1 Evaporator module
 
 
4 Cooling circuit module
The cooling circuit module
1 Electrical switch box
2 Plug connection to the fan module
3 Condenser
 
5 Expansion valve
 
7 Filter dryer
8 Inverter unit
7
Subject to change without notice | 83059600jUK – Translation of the original operating manual | ait-deutschland GmbH
Nameplate
The nameplate is attached at the following point on
the unit:
on the back
It contains the following information at the very top:
Model, item number
Serial number
The nameplate also contains an overview of the most
important technical data.
3.3 Accessories
The following accessories are available for the unit via
the manufacturer’s local partner:
Connection set, hydraulic
Connection set, electrical
Domestic hot water tank

Room thermostat for switching the cooling function
Dew point monitor for protecting a system with

Room control panel for controlling the main func-
tions at the living quarters
Extension board
3.4 Function
-
ergy for this process is ambient heat coming from the
outside air. The gaseous refrigerant is compressed

also the temperature. The gaseous refrigerant with

Here, the high temperature is transferred to the heat-
ing water and used in the heating circuit. The liquid re-
frigerant with high pressure and high temperature is
      -
perature drop and the process restarts.
The heated heating water can be used for the domestic
hot water or for heating the building. The temperatures
required and the use are controlled by the heat pump
controller. Any required reheating, support in screed
drying or increase in the domestic hot water temper-
ature can be carried out using an electric heating ele-
ment, which is activated by the heat pump controller
as required.
The integrated vibration decoupling for the hydraulic
system prevents structure-borne sound and vibrations
     
the building.
Cooling
Cooling is integrated in the units. The following op-
       operat-
ing manual of the heating and heat pump controller):
Active cooling
Cooling in combination with hydraulic module or

of 18 °C. In combination with wall-mounted control-

Cooling below 18 °C is only possible in the case

The cooling function is controlled via the heating
and heat pump controller
Switching over between heating and cooling
mode
4 Operation and care
NOTE
The unit is operated via the control panel of
 op-
erating manual of the heating and heat pump
controller).
4.1 Energy and environmentally
aware operation
The generally applicable requirements for energy and
environmentally aware operation of a heating system
also apply to the use of a heat pump. The most impor-
tant measures include:

No unnecessarily high domestic hot water tem-

-
tinuous ventilation), but instead open wide for a

Always ensure that the controller setting is correct
4.2 Care
Wipe down the outside of the unit only using a damp
-
uid, neutral cleaning agent). Do not use any aggres-
sive, abrasive, acid or chlorine-based cleaning agents.
8
Subject to change without notice | 83059600jUK – Translation of the original operating manual | ait-deutschland GmbH
Wear cut resistant protective gloves.
The hydraulic connections are not designed for me-
chanical loads.
Do not lift or transport the unit by the hydraulic con-
nections.
Transport the unit preferably with a lift truck, alterna-
tively with a handcart or by carrying it.
Do not tilt the heat pump module by more than 45°.
The tensioning straps on the heat pump module
may only be used for carrying by hand.
Transport by crane
Transport the unit to the installation site in pack-
aged form and secured on a wooden pallet.
40-50°

Transport with a lift truck
Transport the unit to the place of installation in
packaged for, and secured on a wooden pallet.
Unpacking
1. -
age the unit.
2. Dispose of the transport and packaging materi-
al in an environmentally sound manner and in ac-
cordance with local regulations.
5 Delivery, storage, transport
and installation
IMPORTANT
Damage to the housing and the unit components
due to heavy objects.
Do not place any objects on the unit that are heav-
ier than 30 kg.
5.1 Scope of supply
Check supplied packages immediately on receipt
for visible signs of damage and completeness.
Notify the supplier of any complaints immediately.
The separate package included contains:


1 tube anti-friction agent
1 HT sheet, DN 40 mm 87°
1 protective cover for plug
4 EPP screws

labels)
Type stickers
In panel packages:
Cover, front panel, rear panel, side panels
5.2 Storage
If possible, do not unpack the unit until immediately
before installation.
Store the unit protected against:
Moisture
Frost
Dust and dirt
5.3 Unpacking and transport
Notes on safe transport
 “Technical data / scope of supply,
page 17). There is a risk of injuries or material dam-
age if the unit falls down or overturns.
There is a risk of cutting your hands on sharp edges
of the unit.
9
Subject to change without notice | 83059600jUK – Translation of the original operating manual | ait-deutschland GmbH

If the unit is not transported by a lift truck: Do not lift
          -

The cover, the front panel, the rear panel and the
side panels are in the panel packages, in front of
the unit, behind it and on the unit
Optional separation of the fan module
NOTE
      
can be removed.
1. Disconnect the plug connections of the load and
bus cables at the top left on the switch box of the
cooling circuit for the fan module.
2. Remove the 4 screws from the fan module.
3. Remove the fan module and set it down safely.
4.    
cross-pieces.
1 Tensioning straps with openings for carrying
2 Polystyrene links
3 Screws on the fan module
Carrying the unit, transport using handcart
The housing panels have been set down.
There are two circumferential tensioning straps on the
    
that can be used for lifting and carrying.
Two support crosspieces are clamped into the recess-
es at the sides for the air ducts for stability – do not re-
move them both until after transport.
Transport of the heat pump module with
a handcart
1. Only load the heat pump module on to the hand-
cart with the narrow side, left or right.
2. Secure the heat pump module on the handcart
with a tensioning strap.
3. Transport the heat pump module to the installa-
tion site.
5.4 Installation
CAUTION
In the air outlet area, the air temperature is
approx. 5 K below the ambient temperature.
Under certain climatic conditions an ice lay-
er can therefore develop in the air outlet area.
Install the heat pump so that the air blower
does not discharge into footpath areas
.
NOTE
Always comply with the installation plan for
the respective model. Note the size and mini-
mum clearances.
Installation plan for the respective model, from
Page 24
10
Subject to change without notice | 83059600jUK – Translation of the original operating manual | ait-deutschland GmbH
NOTE
Install the unit so that the switch box side

NOTE
The noise immissions of the heat pumps must
be taken into account in the respective instal-
lation plans for air/water heat pumps. The re-
spective regional regulations must be com-
plied with.
Installation site requirements
Perform installation outdoors only
Clearance dimensions were complied with
Minimum clearances”, page 24
Free air intake and blowing air are possible with-
out any air short-circuit.
The surface is suitable for installation of the unit:
The foundation is level and horizontal
The surface and the foundation have a load-
 units weight
Ground surface in the air outlet area of the heat
pump is permeable to water
Unit installation
1. Align the unit base horizontally using the spirit level
and attach it to a strip foundation or full-area foun-
dation with 4 screws.
2. Unscrew the 4 levelling feet of the heat pumps by
2 turns.
3. Lift the heat pump over the unit base and place it
with the levelling feet in the holes provided in the
unit base. Push the levelling feet under the con-
striction of the holes.
4. Tighten the lock screws on the levelling feet
through the openings in the unit base using the

the unit base.
Heat pump installation instructions
5. Remove the two tensioning straps.
6. Open the tension lock, turn the hook on the base
plate by 90°.
90°
Heat pump installation instructions
7. Remove the two polystyrene crosspieces.
5.5 Attach the side panel, the rear
panel, the cover and the front
panel
Heat pump installation instructions
1. Fasten the rear panel.
2. Fit the cover.
3. Hook in the side panels. Fasten them in the front
at the center using a screw.
4. Attach the front panel.
5.         
front wall.
6.         
front wall.
11
Subject to change without notice | 83059600jUK – Translation of the original operating manual | ait-deutschland GmbH
6 Installation of hydraulic system
1. Install the outside pipes of the heating circuit be-
neath the frost line.
NOTE
If an existing system is being replaced, the
old vibration decoupling may not be reused.
2. Flush the heating circuit thoroughly before con-
necting it to the heating system.
IMPORTANT
Damage to the copper pipes due to impermissible load!
Secure all connections against twisting.
Cross-sections and lengths of the pipes for the
heating circuit are adequately dimensioned.
The free pressing of the circulation pumps pro-
duces at least the minimum throughput required for
  Technical data / scope of supply,
page 17).
The hydraulic system must be equipped with a

on your model.
“Technical data / scope of supply, page 17
The lines for the heating are fastened to the wall or

1 Heating water supply
 
3 Heating water return
3. Insert the vent at the highest point of the heating
circuit.
4.  Tech-
nical data / scope of supply, page 17) are
complied with.
Condensate connection
The heating water drained from the safety valve and
the condensate that accumulates from the air must be
discharged in compliance with the applicable stand-
ards and regulations. Discharge of the condensate
and of the water drained from the safety valve into the
sewage system is permitted only via a funnel waste
trap, which must be accessible at all times.
Condensate line connection
Heat pump installation instructions
Hydraulic connection to the unit
Mount the corresponding connection set.
Installation instructions for connection set
12
Subject to change without notice | 83059600jUK – Translation of the original operating manual | ait-deutschland GmbH
7 Electrical installation
Establishing the electrical connections
IMPORTANT
Irreparable damage to the compressor due to wrong

-
sors load supply.
Basic information relating to the electrical
connection
      
company apply to electrical connections
Equip the power supply for the heat pump with an
all-pole circuit breaker with at least 3 mm contact

 “Technical data /
scope of supply, page 17)
Comply with the electromagnetic compatibility

Install unshielded power supply cables and


Connecting the heat pump module to
the hydraulic module, the hydraulic station
or the wall-mounted controller
The connection is established using the EVS 8 or EVS
accessory.
EVS 8 load and bus connector with 8 m cable.
       -
mum of 2 additional EVS 8)
EVS 8 installation instructions
EVS: Load and bus connector.
Cable on site, maximum cable length of 30 m.
The bus cable must be a shielded cable of at least
4 x 0.5 mm².
As load line:
For the 12 kW unit a 5 x 2.5 mm² cable with
protective conductor
For the 8 kW unit a 3 x 2.5 mm² cable with pro-
tective conductor
EVS installation instructions
1. Route the two plug-in connections of the load and
bus cables to the slots on the heat pump module.
2. Join the connections.
3. Fit the cover for the plug connections.
8 
8.1 Heating water quality
NOTE
For detailed information refer, among
other things, to the VDI Guidelines
2035 “Vermeidung von Schäden in
 
damage in hot water heating systems)
Required pH value: 8.2 …
for aluminium materials:
pH value: 8.2 … 8.5
Fill the system with deionised heating water


Advantages of low-salt operation:
Low corrosion-promoting properties
No formation of mineral scale
Ideal for closed heating circuits

the system
If the required water quality is not achieved, con-
sult a company specialising in the treatment of he-
ating water.
Keep a system log for hot water heating systems
       
2035).
13
Subject to change without notice | 83059600jUK – Translation of the original operating manual | ait-deutschland GmbH
Antifreeze in the heating circuit
For air/water heat pumps installed outdoors, it is not
-
ating circuit.
The heat pumps have safety devices that prevent the
water from freezing, even when the heating is swit-

switched on and is not disconnected from the mains.
Should there be a risk of frost, the circulation pumps
are activated.
The following points must be observed if antifreeze is
added, depending on the concentration of the mixture:
Heat output of the heat pump is reduced
COP value becomes worse
In the case of on-site circulating pumps, the deliv-
  -

The compatibility of the material of the compon-
ents used with the antifreeze mixture must be en-
sured
8.2 
the heating circuit
Outlet pipe of the safety valve is connected.
Ensure that the response pressure of the safety
valve is not exceeded.
NOTE
The venting program on the controller can
-
ing process. It is possible to control individual
circulation pumps and even the changeover
valve via the venting programs. As a result it is
not necessary to remove the valve motor.
1. Vent the system at the highest point.
2. Vent the heat pump at the hydraulic connection set.
9 Insulation of hydraulic
connections
Insulate hydraulic lines in accordance with the local
regulations.
1. 
2. Perform a pressure test and check for leaks.
3. Insulate external piping on site.
4. 
5. -
sible in combination with the wall-mounted control-

6. Insulate the condensate drain in a frost-proof
manner.
7. Fit the cover hood on the connection set.
8. The unit must be completely closed on all sides to
ensure rodent protection.
10 
NOTE
The activities in this section are only nec-
essary for the integration of the storage
tank in series.
Complete the work steps quickly, other-
wise the maximum return temperature
could be exceeded and the heat pump will
switch to high-pressure fault.
Turn the rotary-push button on the over-
-
      
the left to reduce it

cold condition).
The IBN assistant already provides the option, in the
event of the integration of the storage tank in series to
   -
lic system.

14
Subject to change without notice | 83059600jUK – Translation of the original operating manual | ait-deutschland GmbH
The “Set bypass valve” menu item is set by default to
-
tivated.
The UWP control signal is the indication of the
currently required pump capacity in %

accuracy +/- 200 l/h)
1.        
circuits
2. If the “Set bypass valve” menu item is set from
No” to “Yes”, the circulation pump is activated
with 100% – and the pump starts up.
3. If the control signal UWP reaches 100%, close

  Technical data / scope of supply,
page 17) can be ensured.
1 Rotary-push button
 
4. If you exit the “Set bypass valve” menu or at the
latest after one hour, the circulation pump switch-
es back to standard regulation
5. Open valves to heating circuit.
11 Commissioning
CAUTION
Prior to commissioning the unit, the fan
protection grilles must be mounted and the
facing panels closed.
Relevant planning & design data of the system is
documented in full.
The relevant energy supply company has been

The system is air-free.
Installation check using the general checklist has
been completed successfully.
1. -
pletely:

available at the compressor
The system is installed and mounted according to
this operating manual
The electrical installation has been carried out
properly according to this operating manual and
the local regulations
The power supply for the heat pump is equipped
with an all-pole circuit-breaker with at least 3 mm

The tripping current is complied with


The pipe systems and components of the system
are tight
2.   
for the heat pump systems.
3. In Germany: Send notice of completion for heat
pump systems and general checklist to the man-
ufacturer’s factory customer service depart-
ment.
In other countries: Send notice of completion for
heat pump systems and general checklist to the
manufacturers local partner.
4. Arrange for the heat pump system to be com-
missioned by the manufacturer’s authorised after
sales service for a fee.
15
Subject to change without notice | 83059600jUK – Translation of the original operating manual | ait-deutschland GmbH
12 Maintenance
NOTE
We recommend that you conclude a mainte-
nance agreement with your specialist heating
company.
12.1 Basic principles
The cooling circuit of the heat pump does not require
any regular maintenance.

specify tightness checks beforehand and/or for a log
book to be kept for certain heat pumps.
Ensure compliance with the local regulations re-

12.2 Maintenance as required
Check and clean the components of the heating
circuit, e.g. valves, diaphragm expansion vessels,

Test the function of the safety valve for the heat-
ing circuit
Always regularly control for unimpeded air in-
feed accordingly. Constrictions or even blockages
which, for example occur
when applying house insulation with polysty-
rene balls
     -
tons etc.)
through foliage, snow, icing or similar weath-
er-related deposits


etc.)
and which must be prevented and/or removed im-
mediately
Check at regular intervals that the condensate
can drain out of the unit freely, without obstruc-
tion. To this end, check the condensate pan in the
unit and the evaporator regularly for dirt/clogging
and clean as necessary
Check the evaporator and the condensate
pan and clean them, if required
1. Remove the front panel, the side panels and the
cover, thus gaining access to the cover of the

2. -
-
tor is visible and can be cleaned if necessary.
Heat source inlet
sensor
As an alternative, the fan module can be removed to
obtain additional access.
 “Optional separation of the fan module“,
page 9
16
Subject to change without notice | 83059600jUK – Translation of the original operating manual | ait-deutschland GmbH
12.3 
the condenser
       
manufacturer’s instructions.
-
       
condenser thoroughly with water.
12.4 Annual maintenance
Determine the quality of the heating water by
analysis. In the event of deviations from the speci-

13 Malfunctions
Read out the cause of the malfunction via the diag-
nostic program of the heating and heat pump con-
troller.
Consult the local partner of the manufacturer or
the factory’s customer service. Have the fault
message and unit number at hand.
14 Dismantling and disposal
14.1 Dismantling
The unit is disconnected from the power supply
and protected against being switched back on
again.
Collect all media safely.
Separate components by their materials.
14.2 Disposal and recycling
Dispose of environmentally hazardous media ac-
      
compressor oil).
Ensure the correct recycling or disposal of unit
components and packaging materials in accord-
ance with the local regulations.
17
Subject to change without notice | 83059600jUK – Translation of the original operating manual | ait-deutschland GmbH
Performance data Values in brackets: (1 Compressor) LWAV 82R1/3 LWAV 122R3
Heating capacity | COP for A10/W35 acc. to EN14511 Partial load operation kW | COP 3,18 5,25 5,50 5,10
for A7/W35 acc. to EN14511 Partial load operation kW | COP 2,81 5,03 5,29 4,71
for A7/W55 acc. to EN14511 Partial load operation kW | COP 3,28 2,85 9,36 2,65
for A2/W35 acc. to EN14511 Partial load operation kW | COP 3,82 4,19 5,00 4,01
for A-7/W35 acc. to EN14511 Full load operation kW | COP 6,40 3,17 8,50 2,63
for A-7/W55 acc. to EN 14511 Full load operation kW | COP 4,93 2,20 8,46 2,05
Heating capacity for A10/W35 min. I max. kW | kW 2,90 7,00 5,40 11,0
for A7/W35 min. I max. kW | kW 2,80 6,60 5,40 11,0
for A7/W55 min. I max. kW | kW 2,50 6,40 4,50 11,0
for A2/W35 min. I max. kW | kW 2,60 6,40 4,60 10,3
for A-7/W35 min. I max. kW | kW 2,30 6,50 3,60 8,50
for A-7/W55 min. I max. kW | kW
1,80 4,95 2,80 8,50
Cooling capacity | EER for A35/W18 Partial load operation kW | EER 6,00 3,00 8,50 2,80
for A35/W7 Partial load operation kW | EER 3,60 1,80 5,00 1,80
Cooling capacity for A35/W18 min. I max. kW | kW 1,00 6,00 2,00 8,50
for A35/W7 min. I max. kW | kW 1,00 4,50 2,00 6,00
Operating limits
Heating circuit return min. | Heating circuit flow max. Heating within heat source min./max. °C 20 45 20 45
Heat source, heating min. I max. °C -22 35 -22 35
Additional operating points A-5 / W60 A-5 / W60
Sound
Sound power level inside min. | Night | max. dB(A)
Sound power level outside 1) min. | Night | max. dB(A) 47 52 58 46 53 58
Sound power level acc. to EN12102 inside | outside dB(A) 50 58
Tonality | Low-frequency dB(A) | • yes – no
Heat source
Air flow rate at maximum external pressing | Maximum external pressure m³/h | Pa 2500 2900
Heating circuit
Flow rate (pipe dimensioning) I Min. volume buffer tank in series I Min. volume separation buffer tank l/h | l | l 1200 60 100 1900 100 200
Free pressing | Pressure loss | Flow rate bar | bar | l/h 0,14 1200 0,2 1900
Max. allowable operating pressure bar 3 3
Circulation pump control range min. I max. l/h
General unit data
Total weight kg 132 148
Weight of heat pump module | Compact module | Fan module kg | kg | kg 88 16 104 16
Refrigerant type | Refrigerant capacity … | kg R410A 3,00 R410A 3,60
Electrics
Voltage code | all-pole fuse protection for heat pump *)**) … | A 1~N/PE/230V/50Hz B16 3~N/PE/400V/50Hz B16
Voltage code | Control voltage fuse protection **) … | A 1~N/PE/230V/50Hz B10 1~N/PE/230V/50Hz B10
Voltage code | Electric heating element fuse protection **) … | A
WP*): effect. Power consumption A7/W35 (partial load operation) EN14511 I Electric consumption I cosφ kW |
A
0,559 1,09 0,83 1,12 2,40 0,83
WP*): effective power consumption A7/W35 acc. to EN14511: min. I max. kW | kW 0,5 1,12
WP*): Max. machine current I Max. power consumption within the operating limits A | kW 16 3,5 13 6,0
Starting current: direct | with soft starter A | A < 5 < 5
Degree of protection IP 24 24
Residual current circuit breaker if required type B B
Electric heating element output 3 | 2 | 1 phase kW | kW | kW
Circulation pump power consumption, heating circuit min. I max. W
Other unit information
Safety valve heating circuit | Response pressure included in scope of supply: • yes – no | bar
Buffer tank | Volume included in scope of supply: • yes – no | l
Heating circuit expansion vessel | Volume | Prepressure incl. in scope of supply: • yes – no | l | bar
Overflow valve | Changeover valve heating - domestic hot water integrated: • yes – no
Heating circuit vibration decoupling incl. in scope of supply or integrated: • yes – no
Controller I Heat quantity recording I Extension board incl. in scope of supply or integrated: • yes – no
831581d 813582d
*) compressor only, **) note local regulations 1) Indoor and outdoor installation.
For indoor installation: Intake 1.5m air duct, Blow-out 1.5m air duct + air duct bend (original accessories)
Technical data / scope of supply
LWAV
18
Subject to change without notice | 83059600jUK – Translation of the original operating manual | ait-deutschland GmbH
823290 c
Legende: Legende:
V
HW
Volumenstrom Heizwasser
V
KW
Volumenstrom Kühlwasser
TempWQ Temperatur Wärmequelle TempWS Temperatur Wärmesenke
Qh min/max minimale/maximale Heizleistung Q0 min/max
Q0 min/max minimale/maximale Kühlleistung
Pel min/max minimale/maximale Leistungsaufnahme Pel min/max Pel min/max minimale/maximale Leistungsaufnahme
∆pmax maximaler Druckverlust ∆pmax Druckverlust Wärmepumpe
Bezeichnung: Bezeichnung:
Seite: 1 Seite: 1
Datei: 823290 Leistungs- Druckverlustkurven LW(A)V 82R1_3
ÄÄnndd..//ÄÄ..MM..//EErrsstteelllleerr//DDaattuumm
Leistungs-Druckverlustkurven
a / PEPxxx-2018 / Peplau / 09.04.2018
LW(A)V 82R1/3
b / PEPxxx-2018 / Peplau / 10.08.2018
Zeichnungsnummer:
c / 030-2020 / ArPe / 15.04.2020
ÄÄnndd..//ÄÄ..MM..//EErrsstteelllleerr//DDaattuumm
Leistungs-Druckverlustkurven
823290 c
c / 030-2020 / ArPe / 15.04.2020
Datei: 823290 Leistungs- Druckverlustkurven LW(A)V 82R1_3
a / PEPxxx-2018 / Peplau / 09.04.2018
LW(A)V 82R1/3
b / PEPxxx-2018 / Peplau / 10.08.2018
Zeichnungsnummer:
823290
0
1
2
3
4
5
6
7
8
9
10
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35
Temp„ [°C]
Qh min/max [kW]
35°C
55°C
0,00
0,05
0,10
0,15
0,20
0,25
0,30
0 0,5 1 1,5 2 2,5 3
“ ” [m³/h]
∆pmax [bar]
15
20
25
30
35
40
45
50
55
60
65
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40
Temp” [C°]
Temp„ [°C]
0
1
2
3
4
5
6
7
8
9
10
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35
Temp„ [°C]
Pel min/max [kW]
35°C
55°C
0
1
2
3
4
5
6
7
8
9
10
10 15 20 25 30 35 40 45
Temp
WS
[°C]
Q0 min/max [kW]
7°C
18°C
0,00
0,05
0,10
0,15
0,20
0,25
0,30
0 0,5 1 1,5 2 2,5 3
V
KW
[m³/h]
∆pmax [bar]
5
10
15
20
25
30
35
40
5 10 15 20 25 30 35 40 45
Temp
KW
C]
Temp
WS
C]
0
1
2
3
4
5
6
7
8
9
10
10 15 20 25 30 35 40 45
Temp
WS
[°C]
Pel min/max [kW]
7°C
18°C
Keys: 823290cKeys: 823290c
“”“” Volume ow rate heating waterVolume ow rate heating water
TempTemp
Heat source temperatureHeat source temperature
∆pmax∆pmax max. free pressingmax. free pressing
Qh min/maxQh min/max min./max. heating powermin./max. heating power
Pel min/maxPel min/max min./max. power consumptionmin./max. power consumption
LWAV 82R1/3Performance curves / operating limits / heating
19
Subject to change without notice | 83059600jUK – Translation of the original operating manual | ait-deutschland GmbH
823290 c
Legende: Legende:
V
HW
Volumenstrom Heizwasser
V
KW
Volumenstrom Kühlwasser
TempWQ Temperatur Wärmequelle TempWS Temperatur Wärmesenke
Qh min/max minimale/maximale Heizleistung Q0 min/max
Q0 min/max minimale/maximale Kühlleistung
Pel min/max minimale/maximale Leistungsaufnahme Pel min/max Pel min/max minimale/maximale Leistungsaufnahme
∆pmax maximaler Druckverlust ∆pmax Druckverlust Wärmepumpe
Bezeichnung: Bezeichnung:
Seite: 1 Seite: 1
Datei: 823290 Leistungs- Druckverlustkurven LW(A)V 82R1_3
ÄÄnndd..//ÄÄ..MM..//EErrsstteelllleerr//DDaattuumm
Leistungs-Druckverlustkurven
a / PEPxxx-2018 / Peplau / 09.04.2018
LW(A)V 82R1/3
b / PEPxxx-2018 / Peplau / 10.08.2018
Zeichnungsnummer:
823290
c / 030-2020 / ArPe / 15.04.2020
ÄÄnndd..//ÄÄ..MM..//EErrsstteelllleerr//DDaattuumm
Leistungs-Druckverlustkurven
823290 c
c / 030-2020 / ArPe / 15.04.2020
Datei: 823290 Leistungs- Druckverlustkurven LW(A)V 82R1_3
a / PEPxxx-2018 / Peplau / 09.04.2018
LW(A)V 82R1/3
b / PEPxxx-2018 / Peplau / 10.08.2018
Zeichnungsnummer:
823290
0
1
2
3
4
5
6
7
8
9
10
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35
Temp„ [°C]
Qh min/max [kW]
35°C
55°C
0,00
0,05
0,10
0,15
0,20
0,25
0,30
0 0,5 1 1,5 2 2,5 3
“ ” [m³/h]
∆pmax [bar]
15
20
25
30
35
40
45
50
55
60
65
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40
Temp” [C°]
Temp„ [°C]
0
1
2
3
4
5
6
7
8
9
10
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35
Temp„ [°C]
Pel min/max [kW]
35°C
55°C
0
1
2
3
4
5
6
7
8
9
10
10 15 20 25 30 35 40 45
Temp
WS
[°C]
Q0 min/max [kW]
7°C
18°C
0,00
0,05
0,10
0,15
0,20
0,25
0,30
0 0,5 1 1,5 2 2,5 3
V
KW
[m³/h]
∆pmax [bar]
5
10
15
20
25
30
35
40
5 10 15 20 25 30 35 40 45
Temp
KW
C]
Temp
WS
C]
0
1
2
3
4
5
6
7
8
9
10
10 15 20 25 30 35 40 45
Temp
WS
[°C]
Pel min/max [kW]
7°C
18°C
Keys: 823290cKeys: 823290c
KWKW
Volume ow rate cooling waterVolume ow rate cooling water
TempTemp
WSWS
Heat sink temperatureHeat sink temperature
∆pmax∆pmax max. free pressingmax. free pressing
Q0 min/maxQ0 min/max min./max. cooling capacitymin./max. cooling capacity
Pel min/maxPel min/max min./max. power consumptionmin./max. power consumption
LWAV 82R1/3
Performance curves / cooling
20
Subject to change without notice | 83059600jUK – Translation of the original operating manual | ait-deutschland GmbH
Legende: Legende:
V
HW
Volumenstrom Heizwasser
V
KW
Volumenstrom Kühlwasser
TempWQ Temperatur Wärmequelle TempWS Temperatur Wärmesenke
Qh min/max minimale/maximale Heizleistung Q0 min/max
Q0 min/max minimale/maximale Kühlleistung
Pel min/max minimale/maximale Leistungsaufnahme Pel min/max Pel min/max minimale/maximale Leistungsaufnahme
∆pmax maximaler Druckverlust ∆pmax Druckverlust Wärmepumpe
Bezeichnung: Bezeichnung:
Seite: 1 Seite: 1
823291 c
Datei: 823291 Leistungs- Druckverlustkurven LW(A)V 122R3
ÄÄnndd..//ÄÄ..MM..//EErrsstteelllleerr//DDaattuumm
Leistungs-Druckverlustkurven
a / PEPxxx-2018 / Peplau / 09.04.2018
LW(A)V 122R3
c / 030-2020 / ArPe / 15.04.2020
b / PEPxxx-2018 / Peplau / 10.08.2018
Zeichnungsnummer:
823291
823291 c
ÄÄnndd..//ÄÄ..MM..//EErrsstteelllleerr//DDaattuumm
Leistungs-Druckverlustkurven
c / 030-2020 / ArPe / 15.04.2020
Datei: 823291 Leistungs- Druckverlustkurven LW(A)V 122R3
a / PEPxxx-2018 / Peplau / 09.04.2018
LW(A)V 122R3
b / PEPxxx-2018 / Peplau / 10.08.2018
Zeichnungsnummer:
823291
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35
Temp„ [°C]
Qh min/max [kW]
35°C 55°C
0,00
0,05
0,10
0,15
0,20
0,25
0,30
0 0,5 1 1,5 2 2,5 3
“ ” [m³/h]
∆pmax [bar]
15
20
25
30
35
40
45
50
55
60
65
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40
Temp” [C°]
Temp„ [°C]
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35
Temp„ [°C]
Pel min/max [kW]
35°C
55°C
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
10 15 20 25 30 35 40 45
Temp
WS
[°C]
Q0 min/max [kW]
7°C
18°C
0
1
2
3
4
5
6
7
8
9
10
10 15 20 25 30 35 40 45
Temp
WS
[°C]
Pel min/max [kW]
7°C
18°C
5
10
15
20
25
30
35
40
5 10 15 20 25 30 35 40 45
Temp
KW
[C°]
Temp
WS
[°C]
0,00
0,05
0,10
0,15
0,20
0,25
0,30
0 0,5 1 1,5 2 2,5 3
WS
[m³/h]
∆pmax [bar]
Keys: 823291cKeys: 823291c
“”“” Volume ow rate heating waterVolume ow rate heating water
TempTemp
Heat source temperatureHeat source temperature
∆pmax∆pmax max. free pressingmax. free pressing
Qh min/maxQh min/max min./max. heating powermin./max. heating power
Pel min/maxPel min/max min./max. power consumptionmin./max. power consumption
LWAV 122R3Performance curves / operating limits / heating
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44

Alpha innotec LWAV Owner's manual

Category
Heat pumps
Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI