Danfoss VLT AutomationDrive FC 302 Installation guide

Type
Installation guide

Danfoss VLT AutomationDrive FC 302 is a versatile and powerful drive that offers a wide range of features and capabilities for controlling and monitoring electric motors. With its compact design, it is suitable for use in a variety of applications, including pumps, fans, conveyors, and compressors. The FC 302 is easy to install and operate, and it can be programmed to perform a variety of tasks, such as starting and stopping motors, controlling speed and torque, and protecting motors from damage. It also has built-in safety features to help protect personnel and equipment.

Danfoss VLT AutomationDrive FC 302 is a versatile and powerful drive that offers a wide range of features and capabilities for controlling and monitoring electric motors. With its compact design, it is suitable for use in a variety of applications, including pumps, fans, conveyors, and compressors. The FC 302 is easy to install and operate, and it can be programmed to perform a variety of tasks, such as starting and stopping motors, controlling speed and torque, and protecting motors from damage. It also has built-in safety features to help protect personnel and equipment.

Installation Guide
VLT® C-option Adapter MCF 107
1 Introduction
1.1 Product Overview
The VLT® C-option Adapter MCF 107 extends the number of B options that can be installed in a VLT® AutomationDrive FC 302.
The following drives support the MCF 107 option:
VLT® AutomationDrive FC 302, enclosure sizes A5, B1, and B2.
The MCF 107 option is supported from firmware version 8.43.
Normally, a drive can be fitted with 1 A option and 1 B option in the A- and B-slots on the control card. With the MCF 107, it is possible
to have 2 different B options installed. One in the standard B-slot and 1 in the MCF 107. However, when 2 B options are installed, it is
not possible to have any fieldbus options (A options) installed.
The following options are supported in the standard B-slot:
VLT® Encoder Option MCB 102.
VLT® Resolver Option MCB 103.
VLT® Safe PLC I/O MCB 108.
The following options are supported in the MCF 107:
VLT® PTC Thermistor Card MCB 112.
1.2 Order Numbers
Table 1: Order Numbers
Option Uncoated Coated
VLT® C-option Adapter MCF 107 134B7093
VLT® Encoder Option MCB 102 130B1115 130B1203
VLT® Resolver Option MCB 103 130B1127 130B1227
VLT® Safe PLC I/O MCB 108 130B1120 130B1220
VLT® PTC Thermistor Card MCB 112 130B1137
1.3 Items Supplied
The following items are supplied:
VLT® C-option Adapter MCF 107
Ribbon cable
2 x Torx 10 screws
Installation Guide
AN320938053147en-000101 / 130R0911 | 1
Danfoss A/S © 2020.01
1.4 Tools Required
The following tools are required for installing the VLT® C-option Adapter MCF 107:
Torx 10 screwdriver
Flat-head screwdriver
Introduction
Installation Guide | VLT® C-option Adapter MCF 107
AN320938053147en-000101 / 130R0911
2 | Danfoss A/S © 2020.01
2 Safety
2.1 Safety Instructions
W A R N I N G
DISCHARGE TIME
The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be
present even when the warning indicator lights are off.
Failure to wait the specified time after power has been removed before performing service or repair work could result in death
or serious injury.
-
Stop the motor.
-
Disconnect AC mains, permanent magnet type motors, and remote DC-link supplies, including battery back-ups, UPS, and
DC-link connections to other drives.
-
Wait for the capacitors to discharge fully. The minimum waiting time is specified in the table Discharge time and is also
visible on the nameplate on top of the drive.
-
Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors
are fully discharged.
Table 2: Discharge Time
Voltage [V] Minimum waiting time (minutes)
4 7 15 20
200–240 0.25–3.7 kW (0.34–5.0 hp) 5.5–37 kW (7.5–50 hp)
380–500 0.25–7.5 kW (0.34–10 hp) 11–75 kW (15–100 hp) 90–200 kW (150–350 hp)
400 90–315 kW (125–450 hp)
500 110–355 kW (150–450 hp)
525 55–315 kW (75–400 hp)
525–600 0.75–7.5 kW (1.0–10 hp) 11–75 kW (15–100 hp)
525–690 1.5–7.5 kW (2.0–10 hp) 11–75 kW (15–100 hp) 37–315 kW (50–450 hp)
690 55–315 kW (75–400 hp)
Safety
Installation Guide | VLT® C-option Adapter MCF 107
AN320938053147en-000101 / 130R0911 | 3
Danfoss A/S © 2020.01
3 Installation
3.1 Overview
e30bh721.10
1
2
1 Front cover 2 VLT® C-option Adapter MCF 107
Illustration 1: Location of the MCF 107 Option
Installation
Installation Guide | VLT® C-option Adapter MCF 107
AN320938053147en-000101 / 130R0911
4 | Danfoss A/S © 2020.01
3.2 Installing the MCF 107
Context:
1
2
4
e30bh731.10
3
1 Location of A options
3 B option
2 Location of B options
4 LCP frame
Installation
Installation Guide | VLT® C-option Adapter MCF 107
AN320938053147en-000101 / 130R0911 | 5
Danfoss A/S © 2020.01
Procedure
1. Disconnect power to the drive.
2. Disconnect power to the live part connections on the relay terminals.
3. Remove the LCP or the blind cover.
4. Remove the terminal cover.
5. Remove the control cables.
6. Remove the front cover.
7. Remove the LCP cradle.
e30bf720.11
8. Remove all control cables from the metal bracket (spring-loaded).
9. Install the VLT® C-option Adapter MCF 107.
e30bh729.10
10. Tighten the 2 T10 screws (marked with circles in the following illustration). Tightening torque is 1.5 Nm (13.27 in-lb).
Installation
Installation Guide | VLT® C-option Adapter MCF 107
AN320938053147en-000101 / 130R0911
6 | Danfoss A/S © 2020.01
e30bh728.10
11. Connect 1 end of the ribbon cable in the A-option slot and the other end in the upper slot in the MCF 107.
Installation
Installation Guide | VLT® C-option Adapter MCF 107
AN320938053147en-000101 / 130R0911 | 7
Danfoss A/S © 2020.01
e30bh730.10
12. Install the VLT® PTC Thermistor Card MCB 112 option in the option holder and plug on the MCF 107.
e30bh727.10
1
2
3
1 VLT® PTC Thermistor Card MCB 112
3 Encoder or resolver option
2 Ribbon cable
Installation
Installation Guide | VLT® C-option Adapter MCF 107
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective
companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Danfoss A/S
Ulsnaes 1
DK-6300 Graasten
vlt-drives.danfoss.com
Danfoss A/S © 2020.01 M0011201
*
M0011201*
AN320938053147en-000101/ 130R0911
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Danfoss VLT AutomationDrive FC 302 Installation guide

Type
Installation guide

Danfoss VLT AutomationDrive FC 302 is a versatile and powerful drive that offers a wide range of features and capabilities for controlling and monitoring electric motors. With its compact design, it is suitable for use in a variety of applications, including pumps, fans, conveyors, and compressors. The FC 302 is easy to install and operate, and it can be programmed to perform a variety of tasks, such as starting and stopping motors, controlling speed and torque, and protecting motors from damage. It also has built-in safety features to help protect personnel and equipment.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI