Danfoss VLT AutomationDrive FC 301 Installation guide

Type
Installation guide

This manual is also suitable for

Operating Guide
VLT® Extended Relay Card MCB 113
VLT® HVAC Drive FC 102, VLT® Refrigeration
Drive FC 103, VLT® AQUA Drive FC 202, VLT® Au-
tomationDrive FC 301/FC 302
Contents
1 Introduction 5
1.1 Purpose of this Operating Guide 5
1.2 Trademarks 5
1.3 Document Version 5
1.4 Additional Resources 5
1.5 Product Overview 5
1.5.1 Intended Use 5
1.6 Type Approvals and Certifications 6
2 Safety 8
2.1 Safety Precautions 8
3 Installation 10
3.1 Mechanical Installation 10
3.1.1 Installation in Enclosure Sizes A5–C4 10
3.2 Electrical Installation 10
3.2.1 Safety Instructions 10
3.2.2 Wiring Schematic 11
3.2.3 Wiring Schematic - Following NAMUR 13
3.2.4 Galvanic Isolation 13
4 Parameter Setup 15
4.1 Introduction to Parameter Setup 15
4.2 5-** Digital In/Out 15
4.2.1 Parameter Group 5-1* Digital Inputs 15
4.2.2 Parameter Group 5-2* Digital Inputs 31
4.2.3 Parameter Group 5-3* Digital Outputs 32
4.2.4 Parameter Group 5-4* Relays 38
4.3 6-** Analog Outputs 43
4.3.1 6-7* Analog Output 3 MCB 113 43
4.3.2 6-8* Analog Output 4 MCB 113 45
4.4 14-** 24 V DC External Supply 46
4.4.1 14-8* Options 46
4.5 16-** Data Readouts 47
4.5.1 16-6* Inputs and Outputs 47
5 Specifications 50
5.1 Relays 50
5.2 Digital Inputs 50
5.3 Analog Outputs 50
ContentsOperating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / | 3Danfoss A/S © 2020.01
5.4 EMC 50
6 Appendix 51
6.1 Abbreviations 51
6.2 Conventions 51
ContentsOperating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 /4 | Danfoss A/S © 2020.01
1 Introduction
1.1 Purpose of this Operating Guide
This Operating Guide provides information for safe installation and setup of a VLT® Extended Relay Card MCB 113 option used in the
VLT
®
FC drive series.
The Operating Guide is intended for use by qualified personnel only. Personnel must be familiar with the VLT
®
FC drive series.
Read and follow the instructions before installation and setup, and ensure that instructions for safe installation and setup are observed.
Always keep these instructions available with the drive.
1.2 Trademarks
VLT
®
is a registered trademark for Danfoss A/S.
1.3 Document Version
This operating guide is regularly reviewed and updated. All suggestions for improvement are welcome. See document version and
changes applied in table 1.
The original language of this manual is English.
Table 1: Version and Changes Applied
Document version Remarks
AQ322553864968, version 0101 Option now also applicable for VLT® HVAC Drive FC 102, VLT® Refrigeration Drive FC 103, and VLT®
AQUA Drive FC 202.
1.4 Additional Resources
More information resources are available to understand advanced drive functions and programming.
The VLT® FC Series Operating Guides provide information required to install and commission the drive for given applications.
The VLT® FC Series Programming Guides provide greater detail on working with parameters.
VLT® FC Series Design Guides provide detailed capabilities and functionality to design motor control systems for various
applications.
Technical documentation for other product options is available at www.danfoss.com.
1.5 Product Overview
1.5.1 Intended Use
The VLT® Extended Relay Card MCB 113 is exclusively intended for use in option slot C1. The option is constructed as a standard C1
option compatible with the following VLT® FC Series:
Introduction
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353| 5
Danfoss A/S © 2020.01
VLT® HVAC Drive FC 102
VLT® Refrigeration Drive FC 103
VLT® AQUA Drive FC 202
VLT® AutomationDrive FC 301/FC 302.
The MCB 113 adds 7 digital inputs, 2 analog outputs, and 4 SPDT relays to the standard I/O of the drive. These additions make it
possible to comply with the German NAMUR NE37 recommendations.
When ordered with the drive, the option is installed from factory. For ordering, use the following order numbers:
130B1164 (Non-coated)
130B1264 (Coated)
For retrofit, a mounting kit must be purchased. The mounting kit includes a fan for VLT® Motion Control MCO 305 and is only to be
mounted if MCO 305 is used.
Table 2: Mounting Kits for Book-style Enclosures
Enclosure sizes Order number
A2 and A3 (40 mm for 1 C option) 130B7530
A2 and A3 (60 mm for C0 + C1 option) 130B7531
B3 (40 mm for 1 C option) 130B1413
B3 (60 mm for C0 + C1 option) 130B1414
Table 3: Mounting Kits for Compact Enclosures
Enclosure size Order number
A5 130B7532
B (except B3), C, D, E, and F 130B7533
1.6 Type Approvals and Certifications
The following list is a selection of possible type approvals and certifications for Danfoss drives:
089
Introduction
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353
6 | Danfoss A/S © 2020.01
NOTICE
The specific approvals and certification for the drive are on the nameplate of the drive. For more information, contact the local
Danfoss office or partner.
Introduction
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353| 7
Danfoss A/S © 2020.01
2 Safety
2.1 Safety Precautions
WARNING
HIGH VOLTAGE
AC drives contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to perform installation,
start-up, and maintenance by qualified personnel can result in death or serious injury.
-
Only qualified personnel must perform installation, start-up, and maintenance.
WARNING
UNINTENDED START
When the drive is connected to the AC mains, DC supply, or load sharing, the motor may start at any time, causing risk of death,
serious injury, and equipment or property damage. The motor may start by activation of an external switch, a fieldbus
command, an input reference signal from the LCP or LOP, via remote operation using MCT 10 Set-up software, or after a cleared
fault condition.
-
Press [Off] on the LCP before programming parameters.
-
Disconnect the drive from the mains whenever personal safety considerations make it necessary to avoid unintended
motor start.
-
Check that the drive, motor, and any driven equipment are in operational readiness.
WARNING
DISCHARGE TIME
The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be
present even when the warning indicator lights are off.
Failure to wait the specified time after power has been removed before performing service or repair work could result in death
or serious injury.
-
Stop the motor.
-
Disconnect AC mains, permanent magnet type motors, and remote DC-link supplies, including battery back-ups, UPS, and
DC-link connections to other drives.
-
Wait for the capacitors to discharge fully. The minimum waiting time is specified in the table Discharge time and is also
visible on the nameplate on top of the drive.
-
Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors
are fully discharged.
Table 4: Discharge Time, VLT® HVAC Drive FC 102 and VLT® Refrigeration Drive FC 103
Voltage [V] Minimum waiting time (minutes)
4 7 15
200–240 1.1–3.7 kW (1.5–5 hp) 5.5–45 kW (7.5–60 hp)
380–480 1.1–7.5 kW (1.5–10 hp) 11–90 kW (15–125 hp)
525–600 1.1–7.5 kW (1.5–10 hp) 11–90 kW (15–125 hp)
Safety
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353
8 | Danfoss A/S © 2020.01
Voltage [V] Minimum waiting time (minutes)
525–690 1.1–7.5 kW (1.5–10 hp) (FC 102 only) 11–90 kW (15–125 hp) (FC 102 only)
Table 5: Discharge Time, VLT® AQUA Drive FC 202
Voltage [V] Minimum waiting time (minutes)
4 7 15
200–240 0.25–3.7 kW (0.34–5 hp) 5.5–45 kW (7.5–60 hp)
380–480 0.37–7.5 kW (0.5–10 hp) 11–90 kW (15–125 hp)
525–600 0.75–7.5 kW (1.0–10 hp) 11–90 kW (15–125 hp)
525–690 1.1–7.5 kW (1.5–10 hp) 11–90 kW (15–125 hp)
Table 6: Discharge Time, VLT® AutomationDrive FC 301/FC 302
Voltage [V] Minimum waiting time (minutes)
4 7 15
200–240 0.25–3.7 kW (0.34–5 hp) 5.5–37 kW (7.5–50 hp)
380–500 0.25–7.5 kW (0.34–10 hp) 11–75 kW (15–100 hp)
525–600 0.75–7.5 kW (1–10 hp) 11–75 kW (15–100 hp)
525–690 1.5–7.5 kW (2–10 hp) 11–75 kW (15–100 hp)
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the drive properly can result in death or serious injury.
-
Ensure the correct grounding of the equipment by a certified electrical installer.
WARNING
ROTATING SHAFTS
Contact with rotating shafts and electrical equipment can result in death or serious injury.
-
Ensure that only trained and qualified personnel perform installation, start-up, and maintenance.
-
Ensure that electrical work conforms to national and local electrical codes.
-
Follow the procedures in this guide.
Safety
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353| 9
Danfoss A/S © 2020.01
3 Installation
3.1 Mechanical Installation
3.1.1 Installation in Enclosure Sizes A5–C4
NOTICE
For enclosure sizes A5–C4, only 1 C option can be installed at the time.
NOTICE
Do not mount the small fan for VLT® Extended Relay Card MCB 113, VLT® A/B in C Option Adapter MCF 106, or enclosure sizes
B4, C3, C4, D, E, and F.
RemoveJumper to activate Safe Stop
12 13 18 19 27 29 32 33 20
1
2
130bb457.11
Illustration 1: Installation of VLT® Extended Relay Card MCB 113 - Exploded View
If only 1 C option is used, use the 40 mm mounting kit.
If the MCB 113 is used with VLT® Motion Control MCO 305, use the 60 mm mounting kit.
3.2 Electrical Installation
3.2.1 Safety Instructions
See 2.1 Safety Precautions for general safety instructions.
Installation
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353
10 | Danfoss A/S © 2020.01
3.2.2 Wiring Schematic
3
2
1 876
54 11
10
9
13
12 142
1
4
3
1
2
1 32 4 65 7 98 10 1211
Digital in
Relay
Analog out
CPU
CPU
7
2
24 VDC
Control Card
MCB 113
Internal
24 VDC
CAN BUS
Par. 14-80
0/4-20 mA
AOUT3
AOUT4
GND
GND
GND
GND
GND
GND
GND
GND
GND
GND
DIN1
DIN3
DIN5
DIN7
DIN9
DIN11
DIN13
Ext.*
Ext.*
24 VDC
X45/ X58/
X46/
Relay 6Relay 5Relay 4Relay 3
X47/
Rin = 4kW
e30ba746.11
NOTICE
The connections of these relays differ from the standard relays of the drives. The coil is between T2 and T3 and not between T1
and T2.
Digital inputs are programmed for either PNP or NPN in parameter 5-00 Digital I/O Mode.
Installation
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353| 11
Danfoss A/S © 2020.01
GND
24 V DC
Par. 5-00
24 V (NPN)
0 V (PNP)*
e30ba765.11
Illustration 3: Programming Digital Inputs
Installation
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353
12 | Danfoss A/S © 2020.01
3.2.3 Wiring Schematic - Following NAMUR
Digital in
Rela
y
Analog out
CPU
CPU
7
2
24 VDC
Control Card
MCB 113
Internal
24 VDC
CAN BUS
Par. 14-80
0/4-20 mA
AOUT3
AOUT4
GND
GND
GND
GND
GND
GND
GND
GND
GND
GND
DIN1
DIN2
DIN3
DIN4
DIN4
DIN6
DIN7
Ext.*
Ext.*
24 VDC
X2/ X58/ X2/
Relay 6
Relay 5Relay 4Relay 3
Rin = 4kW
e30ba770.11
X2/
60 61 62 63 1 2 10 - 11 - 12 - 13 - 14 - 15 - 16
-
31
30
-
33
32
34
35
37
39
38
-
36
3.2.4 Galvanic Isolation
The VLT® Extended Relay Card MCB 113 can be connected to an 24 V external supply on X58/ to ensure galvanic isolation between the
drive and the option card. If galvanic isolation is not needed, the option card can be supplied through internal 24 V from the drive. The
internal 24 V supply is available on X58 if parameter 14-80 Option Supplied by External 24VDC is set to [0] No.
The relays support a combination of 24 V and 250 V signals as long as there is an unused relay in between.
Installation
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353| 13
Danfoss A/S © 2020.01
1
2
3
4 5
6
7
8
9
10
11
12
1
2
3
4
5
6
7
8
9
10
11
12
1
2
3
4
5
6
7
8
9
10
11
12
Live
part
Live
part
PELV
Live
part
Live
part
Live
part
PELV
PELV
PELV
PELV
PELV
e30bb443.11
Illustration 5: Valid Connections for Galvanic Isolation
Installation
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353
14 | Danfoss A/S © 2020.01
4 Parameter Setup
4.1 Introduction to Parameter Setup
The parameters included in this Operating Guide are extracts from the drive-specific programming guides. Refer to these
Programming Guides for full parameter descriptions.
4.2 5-** Digital In/Out
4.2.1 Parameter Group 5-1* Digital Inputs
The digital inputs are used for selecting various functions in the drive. Refer to table 7 to see which functions can be assigned to digital
inputs.
Functions in group 1 have higher priority than the functions in group 2.
Group 1 Reset, coast stop, reset, and coast stop, quick stop, DC brake, stop, and the [Off] key.
Group 2 Start, latched start, reversing, start reversing, jog, and freeze output.
Table 7: Digital Input Functions
Digital input function Select Terminal
No operation [0] All, terminal 32, 33
Reset [1] All
Coast inverse [2] All, terminal 27
Coast and reset inverse [3] All
Quick stop inverse [4] All
DC brake inverse [5] All
Stop inverse [6] All
Start [8] All, terminal 18
Latched start [9] All
Reversing [10] All, terminal 19
Start reversing [11] All
Enable start forward [12] All
Enable start reverse [13] All
Jog [14] All, terminal 29
Preset reference on [15] All
Preset ref bit 0 [16] All
Preset ref bit 1 [17] All
Preset ref bit 2 [18] All
Freeze reference [19] All
Freeze output [20] All
Parameter Setup
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353| 15
Danfoss A/S © 2020.01
Digital input function Select Terminal
Speed up [21] All
Speed down [22] All
Set-up select bit 0 [23] All
Set-up select bit 1 [24] All
Precise stop inverse [26] 18, 19
Precise start, stop [17] 18, 19
Catch up [28] All
Slow down [29] All
Counter input [30] 29, 33
Pulse input edge triggered [31] 29, 33
Pulse input time based [32] 29, 33
Ramp bit 0 [34] All
Ramp bit 1 [35] All
Latched precise start [40] 18, 19
Latched precise stop inverse [41] 18, 19
External interlock [51]
DigiPot increase [55] All
DigiPot decrease [56] All
DigiPot clear [57] All
DigiPot hoist [58] All
Counter A (up) [60] 29, 33
Counter A (down) [61] 29, 33
Reset Counter A [62] All
Counter B (up) [63] 29, 33
Counter B (down) [64] 29, 33
Reset Counter B [65] All
Mech. brake feedb. [70] All
Mech. brake feedb. inv. [71] All
PID error inv. [72] All
PID reset I-part [73] All
PID enable [74] All
MCO specific [75] All
PTC card 1 [80] All
PROFIdrive OFF2 [91] All
PROFIdrive OFF3 [92] All
Parameter Setup
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353
16 | Danfoss A/S © 2020.01
Digital input function Select Terminal
Light-load detection [94] All
Evacuation [95] All
Mains loss [96] 32, 33
Mains loss inverse [97] 32, 33
Start edge triggered [98] All
Safety option reset [100]
Enable master offset [108] All
Start virtual master [109] All
Start homing [110] All
Activate touch [111] All
Relative position [112] All
Enable reference [113] All
Sync. to Pos. mode [114] All
Home sensor [115] 18, 32, 33
Home sensor inverse [116] 18, 32, 33
Touch sensor [117] 18, 32, 33
Touch sensor inverse [118] 18, 32, 33
Speed mode [119] All
Power limit mot. [231] All
Power limit gen. [232] All
Power limit both [233] All
Light load + evacuation [234] All
The standard terminals of the drive are:
18
19
27
29
32
33
In all drive series, except for VLT® AutomationDrive FC 301, terminals 27 and 29 also function as an output.
The VLT® Extended Relay Card MCB 113 option has the following terminals:
Analog outputs
X45/1
X45/3
Digital inputs
Parameter Setup
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353| 17
Danfoss A/S © 2020.01
X46/1
X46/3
X46/5
X46/7
X46/9
X46/11
X46/13
Relays
X47/3
X47/4
X47/5
X47/6
Functions dedicated to only 1 digital input are stated in the associated parameter.
All digital inputs can be programmed to these functions:
Table 8: 5-10 Digital Inputs - 1
Option Function
[0] No operation No reaction to signals transmitted to the terminal.
[1] Reset Resets the drive after a trip/alarm. Not all alarms can be reset.
[2] Coast inverse (Default digital input 27): Coast stop, inverted input (NC). The drive leaves the motor in free mode. Logic
0coast stop.
[3] Coast and reset
inverse
Reset and coast stop inverted input (NC). Leaves the motor in free mode and resets the drive. Logic
0coast stop and reset.
[4] Quick stop in-
verse
Inverted input (NC). Generates a stop in accordance with quick stop ramp time set in parameter 3-81 Quick
Stop Ramp Time. When the motor stops, the shaft is in free mode. Logic 0quick stop.
[5] DC brake in-
verse
Inverted input for DC brake (NC). Stops motor by energizing it with a DC current for a certain time period.
See parameter 2-01 DC Brake Current to parameter 2-03 DC Brake Cut In Speed [RPM]. The function is only
active when the value in parameter 2-02 DC Braking Time is different from 0. Logic 0DC brake.
[6] Stop inverse Stop inverted function. Generates a stop function when the selected terminal goes from logical level 1 to
logical level 0.
The stop is performed according to the selected ramp time:
Parameter 3-42 Ramp 1 Ramp Down Time,
Parameter 3-52 Ramp 2 Ramp Down Time,
Parameter 3-62 Ramp 3 Ramp down Time, and
Parameter 3-72 Ramp 4 Ramp Down Time.
NOTICE
When the drive is at the torque limit and has received a stop command, it may not stop by itself.
To ensure that the drive stops, configure a digital output to [27] Torque limit and stop. Connect this
digital output to a digital input that is configured as coast.
[8] Start (Default digital input 18): Select start for a start/stop command. Logic 1 = start, logic 0 = stop.
Parameter Setup
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353
18 | Danfoss A/S © 2020.01
Option Function
[9] Latched start If a pulse is applied for minimum 2 ms, the motor starts. The motor stops when stop inverse is activated,
or a reset command (via DI) is given.
[10] Reversing (Default digital input 19). Change the direction of motor shaft rotation. Select logic 1 to reverse. The re-
versing signal only changes the direction of rotation. It does not activate the start function. Select both
directions in parameter 4-10 Motor Speed Direction. The function is not active in process closed loop.
[11] Start reversing Used for start/stop and for reversing on the same wire. Signals on start are not allowed at the same time.
[12] Enable start
forward
Disengages the counterclockwise movement and allows clockwise direction.
[13] Enable start re-
verse
Disengages the clockwise movement and allows counterclockwise direction.
[14] Jog (Default digital input 29): Activate jog speed. See parameter 3-11 Jog Speed [Hz].
[15] Preset refer-
ence on
Shifts between external reference and preset reference. It is assumed that [1] External/preset has been se-
lected in parameter 3-04 Reference Function. Logic 0 = external reference active; logic 1 = 1 of the 8 preset
references is active.
[16] Preset ref bit 0 Preset reference bit 0, 1, and 2 enable a choice between 1 of the 8 preset references according to table 9.
[17] Preset ref bit 1 Same as [16] Preset ref bit 0.
[18] Preset ref bit 2 Same as [16] Preset ref bit 0.
Table 9: Preset Reference Bit
Preset ref. bit 2 1 0
Preset ref. 0 0 0 0
Preset ref. 1 0 0 1
Preset ref. 2 0 1 0
Preset ref. 3 0 1 1
Preset ref. 4 1 0 0
Preset ref. 5 1 0 1
Preset ref. 6 1 1 0
Preset ref. 7 1 1 1
Table 10: 5-10 Digital Inputs - 2
Option Function
[19] Freeze
ref
Freezes the actual reference, which is now the point of enable/condition to be used for [21] Speed up and [22]
Speed down. If speed up/speed down is used, the speed change always follows ramp 2 (parameter 3-51 Ramp 2
Ramp Up Time and parameter 3-52 Ramp 2 Ramp Down Time) in the range 0–parameter 3-03 Maximum Reference.
Parameter Setup
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353| 19
Danfoss A/S © 2020.01
Option Function
[20] Freeze
output
Freezes the actual motor frequency (Hz), which is now the point of enable/condition to be used for [21] Speed up
and [22] Speed down. If speed up/speed down is used, the speed change always follows ramp 2 (parameter 3-51
Ramp 2 Ramp Up Time and parameter 3-52 Ramp 2 Ramp Down Time) in the range 0–parameter 1-23 Motor Fre-
quency.
NOTICE
When freeze output is active, the drive cannot be stopped via a low [8] Start signal. Stop the drive via a
terminal programmed for [2] Coasting inverse or [3] Coast and reset inverse.
[21] Speed
up
Select [21] Speed up and [22] Speed down for digital control of the up/down speed (motor potentiometer). Acti-
vate this function by selecting either [19] Freeze ref or [20] Freeze output. When speed up/speed down is activa-
ted for less than 400 ms, the resulting reference is increased/decreased by 0.1%. If speed up/speed down is acti-
vated for more than 400 ms, the resulting reference follows the setting in ramping up/down parameters 3- x1/3-
x2.
Table 11: Shut Down/Catch Up
Shut down Catch up
Unchanged speed 0 0
Reduced by %-value 1 0
Increased by %-value 0 1
Reduced by %-value 1 1
Table 12: 5-10 Digital Inputs - 3
Option Function
[22] Speed down Same as [21] Speed up.
[23] Set-up se-
lect bit 0
Select [23] Set-up select bit 0 or select [24] Set-up select bit 1 to select 1 of the 4 set-ups. Set parameter 0-10
Active Set-up to [9] Multi Set-up.
[24] Set-up se-
lect bit 1
(Default digital input 32): Same as [23] Set-up select bit 0.
[26] Precise stop
inv.
Sends an inverted stop signal when the precise stop function is activated in parameter 1-83 Precise Stop Func-
tion. Precise stop inverse function is available for terminals 18 or 19.
[27] Precise start,
stop
Use when [0] Precise ramp stop is selected in parameter 1-83 Precise Stop Function. Precise start, stop is availa-
ble for terminals 18 and 19. Precise start ensures that the rotor turning angle from standing still to reference
is the same for each start (for same ramp time, same setpoint). This function is the equivalent to the precise
stop where the rotor turning angle from reference to standstill is the same for each stop. When using param-
eter 1-83 Precise Stop Function option [1] Cnt stop with reset or [2] Cnt stop w/o reset: The drive needs a precise
stop signal before reaching the value of parameter 1-84 Precise Stop Counter Value. If this signal is not sup-
plied, the drive does not stop when the value in parameter 1-84 Precise Stop Counter Value is reached. Trigger
precise start, stop by a digital input. The function is available for terminals 18 and 19.
[28] Catch up Increases reference value by percentage (relative) set in parameter 3-12 Catch up/slow Down Value.
[29] Slow down Reduces reference value by percentage (relative) set in parameter 3-12 Catch up/slow Down Value.
[30] Counter in-
put
Precise stop function in parameter 1-83 Precise Stop Function acts as counter stop or speed compensated
counter stop with or without reset. Set the counter value in parameter 1-84 Precise Stop Counter Value.
Parameter Setup
Operating Guide | VLT® Extended Relay Card MCB 113
AQ322553864968en-000101 / 130R0353
20 | Danfoss A/S © 2020.01
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54

Danfoss VLT AutomationDrive FC 301 Installation guide

Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI