Danfoss 20 User guide

Type
User guide

This manual is also suitable for

vacon 20
ac drives
quick guide
®
safety vacon 1
24-hour support +358 (0)201 212 575 • Email: [email protected]
1
This quick guide includes the steps that will enable you to easily install and setup
your Vacon 20 frequency converter.
Before putting your drive into operation, download and read the complete Vacon 20
user manual from
www.vacon.com -> Downloads
1. SAFETY
THE ELECTRICAL INSTALLATION MAY ONLY BE CARRIED
OUT BY A COMPETENT ELECTRICIAN!
This quick guide contains clearly marked warnings that are intended for your per-
sonal safety and to prevent any unintentional damage to the product or connected
appliances.
Please read these warnings carefully:
The components of the frequency converter's power unit are
live when Vacon 20 is connected to the mains. Coming into
contact with this voltage is extremely dangerous and may
cause death or severe injury.
The motor terminals U, V, W (T1, T2, T3) and the optional brake
resistor terminals - / + are live when Vacon 20 is connected to
the mains even if the motor is not running.
The control I/O terminals are isolated from the mains poten-
tial. However, the relay output terminals may have a danger-
ous control voltage even when Vacon 20 is disconnected from
the mains.
The earth leakage current of Vacon 20 frequency converters
exceeds 3.5 mA AC. A reinforced protective ground connection
must be available in accordance with standard EN61800-5-1.
See Chapter 7!
If the frequency converter is used as part of a machine, the
machine manufacturer is responsible for providing the
machine with a main switch (EN 60204-1).
If Vacon 20 is disconnected from the mains while the motor is
running, Vacon 20 will remain live if the motor is fed by the
process. In this case, the motor functions as a generator that
feeds energy to the frequency converter.
After disconnecting the frequency converter from the mains,
wait until the fan stops and the display segments or status
LEDs on the front panel switch off. Wait 5 more minutes before
doing any work on Vacon 20 connections.
The motor can start automatically after a fault if the autoreset
function is active.
!
Doc: DPD00856F1 Release: Aug.2014 Sw Package: FW0107V010.vcx
2 vacon safety
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
1
NOTE! English and French product manuals with applicable information on safe-
ty, warnings, and cautions can be downloaded from www.vacon.com/down-
loads.
REMARQUE Vous pouvez télécharger les versions anglaise et française des
manuels produit contenant l’ensemble des informations de sécurité, avertisse-
ments et mises en garde applicables sur le site www.vacon.com/downloads.
installation vacon 3
24-hour support +358 (0)201 212 575 • Email: [email protected]
2
2. INSTALLATION
2.1 Mechanical installation
There are two possible ways to mount Vacon 20 on the wall. For MI1 - MI3, either
screw or DIN rail mounting; for MI4 - MI5, either screw or flange mounting.
Figure 1: Screw mounting, MI1 - MI3
Figure 2: Screw mounting, MI4 - MI5
M5
MI3
MI1
=M4
MI2
=M5
LOC
REM
BACK
RESET
OK
LOC
REM
BACK
RESET
OK
LOC
REM
BACK
RESET
OK
4 vacon installation
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
2
Figure 3: DIN rail mounting, MI1 - MI3
Note! See the mounting dimensions on the back of the drive.
Leave free space for cooling above (100 mm), below (50 mm), and on the sides
(20 mm) of Vacon 20! (For MI1 - MI3, side-by-side installation is only allowed if the
ambient temperature is below 40°C; for MI4 - MI5, side-by-side installation is not al-
lowed.
Figure 4: flange mounting, MI4 – MI5
12
LOC
REM
BACK
RESET
OK
Drive outline
Opening outline
installation vacon 5
24-hour support +358 (0)201 212 575 • Email: [email protected]
2
Figure 5: Flange mounting cutout dimensions for MI4 (unit of measure: mm)
Figure 6: Flange mounting cutout dimensions for MI5 (unit of measure: mm)
Drive outline
Opening outline
6 vacon installation
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
2
Figure 7: Flange mounting depth dimensions for MI4 and MI5
(unit of measure: mm)
M15
M14
installation vacon 7
24-hour support +358 (0)201 212 575 • Email: [email protected]
2
.
Figure 8: Attaching the PE plate and API cable support, MI1 - MI3
Figure 9: Attaching the PE plate and API cable support, MI4 - MI5
Attach this plate
BEFORE installing
the p ower ca bl es
Attach the support
AF TER instal lin g
the power cables
Attach the support
AF TER i nstal lin g
Attach th is plate
BEFORE installing
the pow er ca bles
8 vacon installation
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
2
2.2 Cabling and connections
2.2.1 Power cabling
Note: The tightening torque for power cables is 0.5 - 0.6 Nm (4-5 In-Lbs).
Figure 10: Vacon 20 power connections, MI1
Figure 11: Vacon 20 power connections, MI2 - MI3
1~ (230V)
3~ (230V, 400V)
Motor out
MAINS
MOTOR
Strip the
plastic cable
coating for
360° earthing
L1 L2/ N L3 U/ T1 V/T2 W / T3R+ R-
1~ (230V)
3~(230V, 400V, 600V)
1~ (115V)
MAINS
MOTOR
BRAKE
RESISTOR
External brake resistor
Motor out
Strip the
plastic
cable
coating
for 360°
earthing
3~(230V, 400V, 600V)
installation vacon 9
24-hour support +358 (0)201 212 575 • Email: [email protected]
2
Figure 12: Vacon 20 power connections, MI4
Figure 13: Vacon 20 power connections, MI5
MAINS
MOTOR
Motor out
Brake
RESISTOR
3~ (380, 480V)
MAINS
MOTOR
Motor out
Brake
RESISTOR
3~ (380, 480V)
10 vacon installation
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
2
2.2.2 Control cabling
Figure 14: Open the lid (MI1 - MI3)
Figure 15: Open the lid (MI4 - MI5)
installation vacon 11
24-hour support +358 (0)201 212 575 • Email: [email protected]
2
Figure 16: Install the control cables (MI1 - MI3)
Figure 17: Install the control cables (MI4 - MI5)
Strip the plastic
cable coating for
360°earthing
Control cable
tightening
torque: 0.4 Nm
12 vacon installation
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
2
2.2.3 Allowed option boards in Vacon20
See below for the allowed option board slots:
Note! When OPT-B1 / OPT-B4 used in Vacon20, +24VDC (±10%, min.300mA) power
should be supplied to Terminal 6 (+24_out) and Terminal 3 (GND) in control panel.
Option board assembly structure:
Option boards (all boards are varnished)
OPT-EC-V EtherCat
OPT-E3-V Profibus DPV1 (Screw connector)
OPT-E5-V Profibus DPV1 (D9 connector)
OPT-E6-V CANopen
OPT-E7-V DeviceNet
OPT-B1-V 6 x DI/DO, each I/O can be individually
OPT-B2-V 2 x Relay output + Thermistor
OPT-B4-V 1 x AI, 2 x AO (isolated)
OPT-B5-V 3 x Relay output
OPT-B9-V 1 x RO, 5 x DI (42-240 VAC)
OPT-BH-V
3 x Temperature measurement (support for PT100, PT1000,
NI1000, KTY84-130, KTY84-150, KTY84-131 sensors)
OPT-BF-V 1 x AO, 1 x DO, 1 x RO
SLOT E5 E6 B1 B2 B9 BH
E3EC E7 B4 B5 BF
1
installation vacon 13
24-hour support +358 (0)201 212 575 • Email: [email protected]
2
2
3
4
14 vacon installation
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
2
5
6
vacon 20 api vacon 15
24-hour support +358 (0)201 212 575 • Email: [email protected]
3
3. CONTROL I/O AND TERMINALS
Terminal Signal Factory preset Description
1 +10 Vref Ref voltage out
Maximum load 10 mA
2 AI1 Analog signal in 1
Freq reference
P)
0 - 10 V, Ri = 250 k
3 GND I/O signal ground
6 24 Vout 24 V output for DIs
±20%, max load 50 mA
7DI_C
Digital Input Com-
mon
Digital Input for DI1- DI6, refer
to Table 2 for DI sink type
8 DI1 Digital input 1
Start forward
P)
Positive,
Logic1: 18…30V, Logic0: 0…5V;
Negative,
Logic1: 0…10V, Logic0: 18…30V;
Ri = 10K (floating)
9 DI2 Digital input 2
Start reverse
P)
10 DI3 Digital input 3
Fault reset
P)
A A RS485 signal A FB Communication
Negative
B B RS485 signal B FB Communication
Positive
4 AI2 Analog signal in 2
PID actual value and
Freq reference
P)
Default:
0(4) - 20 mA, Ri 250
Other:
0 - 10 V, Ri = 250 k
Selectable through microswitch
5 GND I/O signal ground
13 DO-
Digital Output
Common
Digital Output Common
14 DI4 Digital input 4
Preset speed B0
P)
ASDI1
15 DI5 Digital input 5
Preset speed B1
P)
As DI1,
Other: Encoder Input A (fre-
quency up to 10 kHz)
Selectable through microswitch
16 DI6 Digital input 6
External fault
P)
As DI1,
Other: Encoder Input B (fre-
quency up to 10 kHz), Pulse
Train Input (frequency up to 5
kHz)
18 AO Analog Output
Output frequency
P)
0 - 10 V, RL 1 K
0(4) - 20 mA, RL 500
Selectable through microswitch
20 DO Digital signal out
Active = READY
P)
Open collector, max load 35 V /
50 mA
22
RO1 NO
Relay out 1
Active = RUN
P)
Switching load:
250 Vac / 3 A, 24V DC 3A
23
RO1 CM
24
RO2 NC
Relay out 2
Active = FAULT
P)
Switching load:
250 Vac / 3 A, 24V DC 3A
25
RO2 CM
26
RO2 NO
Table 1: Vacon 20 general purpose application default I/O configuration and
connections for control board
P) = Programmable function, see User Manual: parameter lists and
descriptions for detail
mA
Vacon 20
1-10 k
16 vacon vacon 20 api
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
3
Figure 18: Microswitchs
Vacon 20 I/O terminals:
Terminal Signal Factory preset Description
3 GND I/O signal ground
6 24 Vout 24 V output for DIs
%, max load 50 mA
7DI_C
Digital Input Com-
mon
Digital Input Common
for DI1-DI6
8 DI1 Digital input 1
Start forward
P)
Positive, Logic1:18…30V,
Logic0: 0…5V;
Negative, Logic1: 0…10V,
Logic0: 18…30V;
Ri = 10K (floating)
9 DI2 Digital input 2
Start reverse
P)
10 DI3 Digital input 3
Fault reset
P)
14 DI4 Digital input 4
Preset speed B0
P)
Positive, Logic1:18…30V,
Logic0: 0…5V;
Negative, Logic1: 0…10V,
Logic0: 18…30V;
Ri = 10K (floating)
15 DI5 Digital input 5
Preset speed B1
P)
Only for DI.
16 DI6 Digital input 6
External fault
P)
Only for DI.
Table 2: DI Sink Type, remove jumper J500 and connect the wire using table 2
20
DI
Enco Nor
AO
VmA
AI2
VmA
RS485
-term
ON
S1S2S3S4
J500
OFF
4 5 13 14 15 16 2018
123678910
22 23 26
2425
AI2 GND DO- DI4 DI5 DI6 AO DO+ R13 R14 * R24
+10VAI1 GND 24V DI-C DI1 DI2 DI3 A B R21 R22
navigation & startup vacon 17
24-hour support +358 (0)201 212 575 • Email: [email protected]
4
4. NAVIGATION AND STARTUP
4. 1 The main menus of Vacon 20
Figure 19: The main menu of Vacon 20
FWD R EV I/O KEYPAD BUS
REF
MON
PA R
SYS SYS
SYS SYS
SYS SYS
SYS SYS
FAULTALARMSTOPREADY RUN
FWD REV I/O KEYPAD BUS
REF
PA R
FAULTALARMSTOPREADY RUN
MON
FW D REV I/O KEY PA D B US
REF
PAR
FAU LTALARMSTO PREADY RUN
MON
FWD REV I/O KEYPAD BUS
REF
PAR
FAULTALARMSTOPREADY RUN
MON
FWD REV I/O KEYPAD BUS
REF
PAR
FAULTALARMSTOPREADY RUN
MON
FWD REV I/O KEYPAD BUS
REF
PAR
FAULTALARMSTOPREADY RUN
MON
FWD REV I/O KEYPAD BUS
REF
PAR
FAU LTALARMSTO PREAD Y RUN
MON
PRESS
PRESS
PRESS
PRESS
PRESS
FWD REV I/O KEY PAD BUS
REF
MON
PA R
FAU LTALARMSTOPREADY R UN
PRESS
PRESS
OK
OK
OK
OK
OK
In this menu
you can
browse the
monitoring
values.
In this menu
you can
browse and
edit the
parameters.
Dispalys the
keypad reference
value
regardless of
the selected
contron place.
Here you will be
able to browse
system parameter
and fault
submenu.
MONITORING
MENU
REFERENCE
MENU
PARAMETER
MENU
SYSTEM
MENU
Hz
Hz
18 vacon navigation & startup
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
4
4.2 Putting into operation and startup wizard
4.2.1 Steps to put the drive into operation:
4.2.2 Startup wizard
Vacon 20 runs the startup wizard when the machine is powered up for the first time.
The wizard is run by setting SYS Par.4.2 =1. The following figures show the proce-
dure.
NOTE: Running the startup wizard always returns all parameters to
their factory default settings.
NOTE! StartUp-Wizard can be skipped after pressing the STOP button
continuously for 30 seconds
1. Read the safety instructions on page 1
7. Perform the test run without the motor; see
the User Manual at www.vacon.com
2. Secure the grounding and check that cables
comply with requirements
8. Run no-load tests without the motor con-
nected to the process
3. Check the quality and quantity of the cooling
air
9. Perform an identification run (Par. ID631)
4. Check that all start/stop switches are in the
STOP position
10. Connect the motor to the process and per-
form the test run again
5. Connect the drive to the mains 11. Vacon 20 is now ready for use
6. Run the startup wizard and set all necessary
parameters
Table 1: Steps to put the drive into operation
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62