Wiring
Installation and Wiring, Chapter 2
2.4 WATLOW Series 998 User’s Manual
Wiring the Series 998
Wiring options depend on the model number and DIP switch settings.
Check the terminal designation stickers on either side of the controller
and compare your model number to those shown here and with the
model number breakdown on the inside back cover of this manual.
Input-to-output Isolation
The Series 998 uses optical isolation between the analog inputs and the
controller outputs/digital input. This isolation provides a 500VÅ (ac) bar-
rier to prevent ground loops when using grounded sensors and/or
peripheral equipment.
Here is a breakdown of the isolation barriers:
• Analog inputs 1 and 2 are grouped together.
• Outputs 1 through 4 and the standard event input are grouped togeth-
er. This does not apply to Output 4 when configured as communications.
• The digital communications output (4) is separate from the above
groups.
Power Wiring
100 to 240V
ÅÅ
(ac) nominal, (85 to 264 actual)
Vertical Package 99 8
_ - _ _ _ _ - _ _ _ _
Horizontal Package 99 9
_ - _ _ _ _ - _ _ _ _
24 to 28 V
‡‡
(ac/dc) nominal, (20 to 30 actual)
Vertical Package 99 6
_ - _ _ _ _ - _ _ _ _
Horizontal Package 99 7 _ - _ _ _ _ - _ _ _ _
Sensor Installation Guidelines
Thermocouple input: Extension wire for thermocouples must be of the
same alloy as the thermocouple itself to limit errors.
Using grounded thermocouples for both input 1 and input 2 may create
ground loop problems. To correct this problem, replace at least one of the
grounded thermocouples with an ungrounded thermocouple. If the appli-
cation requires grounded thermocouples, use an isolated transmitter,
such as a Watlow Gordon 5702 isolated transmitter.
RTD input: Each 1Ω of lead wire resistance can cause a +2°F error when
using a two-wire RTD. A three-wire RTD sensor overcomes this problem.
All three wires must have the same electrical resistance (i.e., same gauge,
same length, multi-stranded or solid, same metal).
Maintain isolation between input 1 and input 2 to prevent a ground loop.
A ground loop may cause incorrect readings, dashes across the upper
display or the display of error codes.
Process input: Isolation must be maintained between input 1 and input
2. If both input 1 and input 2 are used as process inputs, a separate
power supply and transmitter must be used for each input. Output
option T (external signal conditioner power supply) can be used to supply
power for only one input.
ç
WARNING:
To avoid potential
electric shock, use
National Electric
Code (NEC) safety
practices when
wiring and connect-
ing this unit to a
power source and
to electrical sen-
sors or peripheral
devices. Failure to
do so could result
in injury or death.
NOTE:
Input-to-output iso-
lation is defeated
when the external
signal conditioner
power supply is
used to power a
transmitter con-
nected to input 1 or
input 2.
Figure 2.4 -
Power wiring.
Fuse
22
21
Earth Ground
11
L2L1
ç
CAUTION:
The Series 998 will
not function with
two grounded ther-
mocouple inputs.
Avoid using a
grounded thermo-
couple for both
input 1 and input 2.
Failure to follow
this guideline could
result in damage to
equipment.