Weil-McLain GV is a condensate drain line check valve kit designed to prevent condensate from backing up into your boiler, which can cause damage or reduce efficiency. It features a 90° Ell with a bleed hole, CPVC nipples of various lengths for different boiler series, a check valve subassembly, and a street ell (for GV Series 3 only).

Weil-McLain GV is a condensate drain line check valve kit designed to prevent condensate from backing up into your boiler, which can cause damage or reduce efficiency. It features a 90° Ell with a bleed hole, CPVC nipples of various lengths for different boiler series, a check valve subassembly, and a street ell (for GV Series 3 only).

GVGV
GVGV
GV
GOLDGOLD
GOLDGOLD
GOLD
Part Number 550-110-273/0699
For use with Weil-McLain Condensate Drain Line Check
Valve Kit — Kit part # 382-200-406
Condensate drain lineCondensate drain line
Condensate drain lineCondensate drain line
Condensate drain line
check valve kit instructionscheck valve kit instructions
check valve kit instructionscheck valve kit instructions
check valve kit instructions
WW
WW
W
ater boiler — Seriesater boiler — Series
ater boiler — Seriesater boiler — Series
ater boiler — Series
1, 2 1, 2
1, 2 1, 2
1, 2
&&
&&
&
3 3
3 3
3
Hazard definitions
The following terms are used throughout these Instructions to bring attention to the presence
of hazards of various risk levels or to important information concerning the life of the product.
Indicates presence of hazards that will cause severe personal injury, death
or substantial property damage.
Indicates presence of hazards that can cause severe personal injury, death
or substantial property damage.
Indicates presence of hazards that will or can cause minor personal injury
or property damage.
Indicates special instructions on installation, operation or maintenance
that are important but not related to personal injury or property damage.
To the installer:
These Instructions must only be used by a qualified installer/service
technician. Read these instructions completely before beginning the
installation. Failure to follow all instructions can cause severe personal
injury, death or substantial property damage.
Part Number 550-110-273/0699
2
GOLD GV
Water boiler — Series 1, 2 & 3
Table 1 Lists parts, which are provided in the
WW
WW
W
ee
ee
e
il-Mil-M
il-Mil-M
il-M
cLcL
cLcL
cL
ain Cain C
ain Cain C
ain C
oo
oo
o
ndnd
ndnd
nd
ee
ee
e
nsatnsat
nsatnsat
nsat
e De D
e De D
e D
rr
rr
r
ain Lineain Line
ain Lineain Line
ain Line
CC
CC
C
hehe
hehe
he
cc
cc
c
k k
k k
k
VV
VV
V
alal
alal
al
vv
vv
v
e Ke K
e Ke K
e K
it.it.
it.it.
it.
Figure 1 Shows the assembly of kit parts for GV Series 1 and 2 Boilers only.
Figure 2 Shows the assembly of kit parts for GV Series 3 Boilers only.
Parts
Table 1
Parts
provided in
kit
Figure 1 GV Series 1 and 2 Boilers
Figure 2 GV Series 3 Boilers
A
B
C
D
E
F
Bleed Hole
Flow Direction
27302
A
B
C
D
Bleed Hole
Flow Direction
27301
Item number Description
A 90˚ Ell, ½" x ½" CPVC, with bleed hole
B Nipple, CPVC
Series 1 — ½" x 2 ¹⁄₈"
Series 2 — ½" x 2 ½"
Series 3 — ½" x 2 ¾"
C Check valve subassembly
D Nipple, CPVC
Series 1 — ½" x 2 ½"
Series 2 — ½" x 2 ¹⁄₈"
Series 3 — ½" x 2 ½"
E Nipple, ½" x 2 ¹⁄₈" CPVC (Series 3 only)
F Street ell, ½" (Series 3 only)
Note: Kit includes three ½” x __ CPVC nipples:
(1) 2 ½"
(1) 2 ¹⁄₈"
(1) 2 ¾"
Use in designated positions as indicated in Instructions.
Part Number 550-110-273/0699
3
Condensate drain line check valve kit instructions
Installation
Step 1
Turn off power to the boiler.
Step 2
If you are using this kit to replace an existing condensate drain line, detach the existing
condensate drain line from the boiler at the jacket.
Step 3
Determine which of the nipples in the kit to use in the vertical position B as follows:
GV Series 1 Boilers — 2 ¹⁄₈" nipple
GV Series 2 Boilers — 2 ¹⁄₂" nipple
GV Series 3 Boilers — 2 ³⁄₄" nipple
Step 4
Determine preferred routing of check valve assembly. Figure 3 and Figure 4 on the next page
show acceptable methods for GV Series 1 and 2 Boilers, while Figure 5 shows the acceptable
method for GV Series 3 Boilers.
Step 5
Install the piping with nipple B vertical to keep the check valve assembly as close to the floor as
possible.
Step 6
GV Series 1 and 2 Boilers — Clean items A, B and C with CPVC cleaner. Then pre-assemble
in the desired orientation using CPVC cement on the joints. Make sure the bleed hole in elbow
A is at the top. See Figure 1 on page 2.
GV Series 3 Boilers — Clean items A, B, C, E and F with CPVC cleaner. Then pre-assemble
using CPVC cement on the joints. Make sure the bleed hole in elbow A is at the top. See Figure 2
on page 2.
Step 7
GV Series 1 and 2 BoilersAttach elbow A to the condensate drain at the boiler jacket,
using CPVC cleaner and cement. Check the bleed hole to make sure it hasnt been blocked by
cement during the assembly. Clean out if necessary by hand reaming the hole with a #46 drill
bit.
GV Series 3 Boilers — Attach street ell F to the condensate drain at the boiler jacket, using
CPVC cleaner and cement. Check the bleed hole to make sure it hasn’t been blocked by cement
during the assembly. Clean out if necessary by hand reaming the hole with a #46 drill bit.
Step 8
If desired, you can use nipple D to connect the condensate line to the check valve assembly.
Clean the nipple with CPVC cleaner and cement in place with CPVC cement.
Do not allow the drain line to rise above the height of the check valve
assembly at any point. This could prevent the check valve from removing
condensate and could damage the boiler or prevent it from operating. Failure
to comply with this warning could result in severe personal injury, death or
substantial property damage.
Step 9
Connect drain line from check valve assembly (using nipple D if desired) to floor drain, making
sure the drain line runs level or continuously downhill. Drain line must not be higher than
the check valve.
Step 10
If necessary, provide support(s) under the condensate drain line to make sure it remains in
position.
Step 11
If using a condensate drain pump, connect the outlet of the check valve assembly to the inlet of
the pump. Make sure the inlet of the pump is at or below the level of the check valve.
Part Number 550-110-273/0699
4
GOLD GV
Water boiler — Series 1, 2 & 3
Weil-McLain
500 Blaine Street
Michigan City, IN 46360-2388
http://www.weil-mclain.com
Installation continued
27305
Condensate drain line
check valve assembly
Figure 5 GV Series 3 Boilers only
NIPPLE LENGTH:
Series 1 Boilers - 2 1/8“
Series 2 Boilers - 2 1/2“
Connect drain hose here
Bleed Hole
27303
Figure 3 GV Series 1 and 2 Boilers only
Assembly parallel to jacket
NIPPLE LENGTH:
Series 1 Boilers - 2 1/8
Series 2 Boilers - 2 1/2
Connect drain
hose here
Bleed Hole
27304
Figure 4 GV Series 1 and 2 Boilers only
Assembly perpendicular to jacket
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Weil-McLain GV Owner's manual

Type
Owner's manual

Weil-McLain GV is a condensate drain line check valve kit designed to prevent condensate from backing up into your boiler, which can cause damage or reduce efficiency. It features a 90° Ell with a bleed hole, CPVC nipples of various lengths for different boiler series, a check valve subassembly, and a street ell (for GV Series 3 only).