GasRelease System Line Terminator
Item Number: 2980-0005
Introduction
The Line Terminator facilitates the straightforward termination of the GasRelease Panel’s extinguishant output to a
maximum of two solenoids (described below) or multiple Metrons (see overleaf)..
Typical Solenoid Wiring
The GasRelease Panel’s extinguishant output is capable of supplying 1A
for a maximum duration of 5 minutes (the actual duration can be set using
the panel’s commissioning menus). If connecting one solenoid (as shown
in Figure 1), it must have a resistance greater than 30 ohms. If connecting
two solenoids (as shown in Fig. 2), each solenoid must have a resistance
greater than 60 ohms. Note that one Line terminator is required per
solenoid (max. 2 per system) and the quantity used (1 or 2) should be
programmed into the GasRelease panel via its commissioning menus.
+
-