EAPL ST-4M1 V2.0 User manual

Type
User manual
CREATED ON: May 24, 2018
Instruction Manual
ST-4M1 V2.0
SEQUENTIAL TIMER WITH 4 CHANNELS
EAPL
Introduction
On power application and continuous shorting of S1 & S2 terminals,
Timing sequence of the 1stchannel (CH1) is initiated by switching the
relay ON and ON-time starts. At the end of the ON-time relay goes
OFF and OFF-time starts. After completion of the OFF-time CH2 relay
comes ON and ON-time starts followed by OFF-time. This sequence
continues for rest of the channels. After the OFF-time of CH4, again
the CH1 relay comes ON and this cycle keeps repeating till the power
is interrupted.
Box Accessories
One (1) ST-4M1 SEQUENTIAL TIMER WITH 4 CHANNELS
One (1) Instruction manual.
Safety Precautions
Read and follow all the safety precautions and instructions before
installing and working with the equipment.
S1- S2 start signal shall be applied.
Shorting of S1-S2 shall be potential free; applying power to these
terminals will damage the timer permanently.
!
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Apply appropriate personal protective equipment(PPE) and follow safety
work practices
Only qualified electrical workers should install this equipment. Such work
should be performed only after reading this entire set of instructions.
If the equipment is not used in the manner specified by the
manufacturer, the protection provided by the equipment may be
impaired.
NEVER work alone.
Turn OFF all power supplying the Sequential timers and the equipment in
which it is installed before working on it.
The successful operation of this equipment depends upon proper
handling, installation and operation. Neglecting fundamental installation
requirements may lead to personal injury as well as damage to electrical
equipment or other property.
NEVER bypass external fusing.
Source Voltage should not exceed specified limits. It will damage the
unit beyond repair
Do not apply voltage terminals.
Before performing Dielectric or Megger testing on any equipment in
which the Sequential timers is installed, disconnect all the input and
output wires to the Sequential timers. High voltage testing may damage
electronic components contained in the Sequential timers.
Failure to follow these instructions will result in death or serious injury.
EAPL is not responsible for any consequential damages arising out of use
of our products, though the technology is cautiously chosen and
implemented like any other well designed good electric device.
Tools and Fasteners
Kindly use star – type screw driver for tightening the screws.
NOTE:
Installation should include a disconnecting device, like switch or
circuit breaker, with clear ON/OFF markings, to turn-off the auxiliary
supply (control power).The disconnecting device should be within the
reach of the equipment and the operator.
Dimension
Note: All Dimensions are in mm.
Front Panel
Terminal Details
A1,A2 : Source
S1-S2 : Open - Stop Signal
Continuous – Timing Initiation.
C1,NO1 : Control output 1
C2,NO2 : Control output 2
C3,NO3 : Control output 3
C4,NO4 : Control output 4
HOLD MODE: Continue the timing after resumption of interrupted power.
RESTART MODE: After the resumption of interrupted power operation starts
from the CH1 or waits for the start signal.
OD RK AN 050011 REV 02/24-05-2018
Page 1 of 2
CREATED ON: May 24, 2018
OPERATING
CONDITION
/MODE
TIMING
SEQUENCE
STATUS
RELAY LED
CH1
ON TIME RLY1 ON ON
OFF TIME RLY1 OFF OFF
CH2
ON TIME RLY2 ON ON
OFF TIME RLY2 OFF OFF
CH3
ON TIME RLY3 ON ON
OFF TIME RLY3 OFF OFF
CH4
ON TIME RLY4 ON ON
OFF TIME RLY4 OFF OFF
a) The Set time changed when timing in progress is effective for the next
cycle onwards (after the completion of the off time of ch4).
b) The Set time changed when S1-S2 is open is effective for the immediate
timing irrespective of hold/restart (i.e. Power is not interrupted).
c) The Range settings shall not be done in the forbidden area.
Technical Specification
Function Sequential timer with 4 channels.
Rated supply Voltage 240V AC
Operating voltage
range ± 10% of the rated voltage
Rated Frequency 50Hz ± 5%
Power consumption AC Approx. 20VA / 4W.
Control output 4 O/P'S (5A @ 250 VAC/28 VDC resistive)
Start Signal (S1, S2) Potential free closure (CONTINUOUS).
On time range 0.1 to 1 S/M/H for each channel
Off time range 0.1 to 1 S/M/H for each channel
Setting accuracy ± 10 % max. w.r.t full scale ± 100 mSec
Repeat accuracy ± 1 % max. ± 100 mSec
Recovery Time 1Sec minimum
Variation due to
voltage change ± 2% max. ± 100 mSec
Variation due to
temperature change ± 5% max. ± 100 mSec
Variation due to
frequency change
± 2% max. ± 100 mSec
Ambient temperature Operating : -10
˚
C to +55
˚
C
Storage : -25
˚
C to +80
˚
C
Humidity MAX 85% RH @ 40
˚
C
Disposition
Once the product life is over, you may send Back the unit to
EAPL for disposition.
Contact
Electronic Automation Pvt. Ltd
#20, KHB Industrial area
Yelahanka
Bangalore -64
Ph:+91-80-28567561/2,/42802345
Customer care :Ph:+91-80-42802323
www.eaplindia.com
OD RK AN 050011 REV 02/24-05-2018 Page 2 of 2