SERVICE MANUAL
A80UH2E / 80G2UHE
(P) 508187-01
*P508187-01*
Table of Contents
Technical Specications - A80UH2E ...........................2
Technical Specications - 80G2UHE ...........................7
Parts Arrangement.....................................................12
Unit Components .......................................................13
Flame Sensor ............................................................23
Gas Valve ..................................................................23
Heating Components .................................................23
Placement and Installation ........................................29
Start-Up .....................................................................29
Heating System Service Checks ...............................30
Typical Operating Characteristics ..............................34
Maintenance ..............................................................35
Wiring and Sequence of Operation ...........................39
Field Wiring and DIP Switch Settings ........................42
Troubleshooting .........................................................46
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals, be alert to
the potential for personal injury or death.
Electric shock hazard.
Can cause injury or death. Before attempting
to perform any service or maintenance,
turn the electrical power to unit OFF at
disconnect switch(es). Unit may have
multiple power supplies.
WARNING
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment and wear gloves
and protective clothing.
CAUTION
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal
injury or loss of life. Installation and service must be
performed by a licensed professional HVAC installer (or
equivalent), service agency or the gas supplier.
WARNING
508187-01Issue 2116Page 2 of 51
Technical Specications - A80UH2E
PHYSICAL AND ELECTRICAL DATA
Model
High Fire Low Fire
AFUE
(ICUS)
Nom.
Cooling
Capacity
(tons)
Gas
Inlet
(in.)
Volts/
Hz/
Phase
Max.
Overcurrent
Protection
Nominal
F.L.A.
Trans.
(V.A.)
Motor
Output
(hp)
Approx.
Weight
(lbs.)
Input
(Btuh)
Output
(Btuh)
Input
(Btuh)
Output
(Btuh)
UPFLOW / HORIZONTAL
A80UH2E045A12 44,000 35,000 29,000 23,000 80.0 3 1/2 120-60-1 15 6.1 40 1/2 111
A80UH2E070A12 66,000 53,000 43,000 35,000 80.0 3 1/2 120-60-1 15 6.1 40 1/2 121
A80UH2E090B12 88,000 70,000 57,000 46,000 80.0 3 1/2 120-60-1 15 6.1 40 1/2 136
A80UH2E090B16 88,000 69,000 57,000 46,000 80.0 4 1/2 120-60-1 15 8.2 40 3/4 140
A80UH2E110C16 110,000 86,000 72,000 58,000 80.0 4 1/2 120-60-1 15 8.2 40 3/4 152
A80UH2E110C20 110,000 87,000 72,000 58,000 80.0 5 1/2 120-60-1 15 10.0 40 1 156
Note: For vent length and clearances to combustibles, please reference installation instructions.
Note: Filters and provisions for mounting are not furnished and must be field provided.
MODEL NUMBER GUIDE
Major Revision
Revision Code
Nom. CFM x 00
12 = 3 Ton add on cooling
16 = 4 Ton add on cooling
20 = 5 Ton add on cooling
Cabinet Width
A = 14.5” width
B = 17.5” width
C = 21.0” width
BTUH Input
Heating Input x 1000
A
Flagship
AFUE
80 = 80% Efficency
Configuration
UH = Upflow/Horizontal
Stages
2 = Two Stage
Blower Drive
E = Constant Torque ECM
A 80 UH 2 E 110 C 20 01
508187-01 Issue 2116 Page 3 of 51
BLOWER PERFORMANCE
A80UH2E045A12
External
Static
Pressure
in. w.g.
Air Volume / Watts at Various Blower Speeds
High
(Black)
Medium-High
(Brown)
Medium
(Blue)
Medium-Low
(Yellow)
Low
(Red)
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
0.00 1500 300 1220 175 1050 114 850 65 800 48
0.10 1485 311 1200 179 1025 118 810 68 790 50
0.20 1460 323 1170 188 980 125 725 73 580 53
0.30 1420 334 1140 195 930 133 670 76 455 54
0.40 1395 343 1095 203 890 138 600 86 375 60
0.50 1355 355 1050 212 840 149 550 93 325 64
0.60 1325 368 1020 222 790 158 495 96 275 67
0.70 1290 369 980 228 745 164 420 103 238 69
0.80 1260 381 945 238 700 172 380 107 --- ---
A80UH2E070A12
External
Static
Pressure
in. w.g.
Air Volume / Watts at Various Blower Speeds
High
(Black)
Medium-High
(Brown)
Medium
(Blue)
Medium-Low
(Yellow)
Low
(Red)
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
0.00 1375 340 1350 240 1110 190 970 93 780 50
0.10 1350 346 1325 254 1100 194 940 104 725 57
0.20 1330 346 1310 264 1080 200 895 113 680 64
0.30 1315 353 1280 272 1060 204 860 118 610 70
0.40 1300 368 1250 283 1040 212 810 125 550 76
0.50 1285 369 1220 293 1010 222 765 132 510 78
0.60 1260 384 1190 301 975 227 725 140 460 83
0.70 1240 391 1150 314 950 236 680 147 400 89
0.80 1210 399 1120 319 915 244 640 152 355 95
A80UH2E090B12
External
Static
Pressure
in. w.g.
Air Volume / Watts at Various Blower Speeds
High
(Black)
Medium-High
(Brown)
Medium
(Blue)
Medium-Low
(Yellow)
Low
(Red)
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
0.00 1605 313 1475 240 1320 173 1050 99 865 60
0.10 1565 323 1430 251 1270 185 995 108 800 68
0.20 1515 334 1380 264 1225 196 935 115 730 76
0.30 1475 347 1340 275 1170 207 870 124 645 83
0.40 1435 360 1300 285 1120 215 805 133 550 91
0.50 1395 369 1250 295 1065 225 715 140 470 98
0.60 1355 378 1205 307 1010 235 655 147 395 101
0.70 1305 391 1160 318 935 246 560 156 345 107
0.80 1265 404 1105 329 875 254 510 162 300 112
508187-01Issue 2116Page 4 of 51
A80UH2E090B16
External
Static
Pressure
in. w.g.
Air Volume / Watts at Various Blower Speeds
High
(Black)
Medium-High
(Brown)
Medium
(Blue)
Medium-Low
(Yellow)
Low
(Red)
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
0.00 1800 370 1555 260 1425 207 1370 172 1240 131
0.10 1765 381 1525 272 1390 218 1320 184 1190 144
0.20 1725 397 1485 283 1350 229 1255 195 1130 157
0.30 1685 416 1450 296 1310 241 1205 206 1075 165
0.40 1635 425 1390 312 1260 250 1165 217 1015 174
0.50 1600 438 1350 322 1205 263 1100 230 955 185
0.60 1560 453 1300 332 1140 270 1050 239 905 193
0.70 1520 467 1255 344 1110 284 1000 249 840 202
0.80 1470 474 1215 352 1050 294 935 258 765 211
A80UH2E110C16
External
Static
Pressure
in. w.g.
Air Volume / Watts at Various Blower Speeds
High
(Black)
Medium-High
(Brown)
Medium
(Blue)
Medium-Low
(Yellow)
Low
(Red)
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
0.00 1780 349 1570 248 1465 190 1370 169 1250 131
0.10 1750 365 1540 260 1420 205 1330 177 1205 140
0.20 1720 382 1500 271 1365 220 1280 187 1155 150
0.30 1675 397 1460 279 1330 228 1250 197 1110 159
0.40 1645 407 1415 291 1290 241 1200 211 1070 166
0.50 1605 424 1395 307 1250 249 1165 219 1015 177
0.60 1580 432 1345 316 1205 258 1105 228 960 186
0.70 1565 448 1300 328 1165 271 1060 237 915 194
0.80 1525 449 1270 339 1125 283 1025 246 865 203
508187-01 Issue 2116 Page 5 of 51
A80UH2E110C20
External
Static
Pressure
in. w.g.
Air Volume / Watts at Dierent Blower Speeds
Bottom Return Air, Side Return Air from Both Sides or Return Air from Bottom and
One Side.
Single Side Return Air - Air volumes in bold (over 1800 cfm) require Optional Return
Air Base and eld fabricated transition to accommodate 20 x 25 x 1 in. air lter in
order to maintain proper air velocity.
High
(Black)
Medium-High
(Brown)
Medium
(Blue)
Medium-Low
(Yellow)
Low
(Red)
High
(Black)
Medium-High
(Brown)
Medium
(Blue)
Medium-Low
(Yellow)
Low
(Red)
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
0.00 2175 590 2050 410 1850 310 1695 275 1510 195 2175 605 1930 420 1785 320 1675 260 1500 195
0.10 2158 607 1943 421 1778 328 1650 283 1461 205 2129 628 1892 441 1733 345 1627 288 1458 209
0.20 2131 620 1897 436 1719 345 1591 299 1405 215 2091 649 1838 458 1691 360 1586 297 1407 220
0.30 2085 639 1847 456 1678 354 1563 308 1351 228 2072 660 1806 471 1631 371 1529 313 1353 232
0.40 2055 652 1806 466 1641 371 1499 317 1297 238 2014 677 1772 485 1591 385 1485 327 1302 243
0.50 2030 668 1767 476 1588 387 1462 333 1256 254 1977 690 1742 498 1554 395 1444 337 1252 256
0.60 1976 686 1724 495 1550 399 1419 348 1215 265 1960 707 1696 511 511 410 1412 348 1204 265
0.70 1949 700 1685 510 1512 408 1371 357 1168 271 1913 720 1661 525 1480 424 1351 359 1149 274
0.80 1896 716 1649 527 1473 419 1332 372 1121 287 1873 738 1617 538 1440 437 1313 371 1117 285
508187-01Issue 2116Page 6 of 51
ACCESSORIES
Accessory Catalog Number
Return Air Base
Return Air Base 14.5” 68W61
Return Air Base 17.5” 68W62
Return Air Base 21.0” 68W62
High Altitude Pressure Switches
2-Stage 80% UH/DF (4501 - 7500 ft) [045, 070, 090 110] 91W53
2-Stage 80% UH/DF (7501 - 10,000 ft) [045, 070, 090 110] 73W35
High Altitude Orice Kits (7500 ft+)
2-Stage 80% UH/DF - Natural Gas 51W01
2-Stage 80% UH/DF - Propane Gas 11K47
Natural to LP Kits
2-Stage 80% UH/DF (0 - 7500 ft) 11K48
2-Stage 80% UH/DF (7501 - 10,000 ft) 11K47
LP to Natural Kits
2-Stage 80% UH/DF 77W10
Downow Specic Air Filters
14.5" 51W06
17.5" 51W07
Downow Combustible Flooring Base
14.5" 11M59
17.5" 11M60
Night Service Kits
2-Stage 22J94
Horizontal Suspension Kit
80% & 90% 51W10
External Filter Rack Kits
1 pack (16 x 25) 1.841018
10 pack (16 x 25) 1.841039
Twinning Kit
Constant Torque Gas Furnace Twinning Kit 16W72
For vent length and clearances to combustibles, please reference installation instructions.
508187-01 Issue 2116 Page 7 of 51
Technical Specications - 80G2UHE
MODEL NUMBER GUIDE
PHYSICAL AND ELECTRICAL DATA
Model
High Fire Low Fire
AFUE
(ICUS)
Nom.
Cooling
Capacity
(tons)
Gas
Inlet
(in.)
Volts/
Hz/
Phase
Max.
Overcurrent
Protection
Nominal
F.L.A.
Trans.
(V.A.)
Motor
Output
(hp)
Approx.
Weight
(lbs.)
Input
(Btuh)
Output
(Btuh)
Input
(Btuh)
Output
(Btuh)
UPFLOW / HORIZONTAL
80G2UH045AE12 44,000 35,000 29,000 23,000 80.0 3 1/2 120-60-1 15 6.1 40 1/2 111
80G2UH070AE12
80G2UH070AE12L 66,000 53,000 43,000 35,000 80.0 3 1/2 120-60-1 15 6.1 40 1/2 121
80G2UH090BE12 88,000 70,000 57,000 46,000 80.0 3 1/2 120-60-1 15 6.1 40 1/2 136
80G2UH090BE16
80G2UH090BE16L 88,000 69,000 57,000 46,000 80.0 4 1/2 120-60-1 15 8.2 40 3/4 140
80G2UH110CE16 110,000 86,000 72,000 58,000 80.0 4 1/2 120-60-1 15 8.2 40 3/4 152
80G2UH110CE20
80G2UH110CE20L 110,000 87,000 72,000 58,000 80.0 5 1/2 120-60-1 15 10.0 40 1 156
Note: For vent length and clearances to combustibles, please reference installation instructions.
Note: Filters and provisions for mounting are not furnished and must be field provided.
Major Revision
Revision Code
Nom. CFM x 00
12 = 3 Ton add on cooling
16 = 4 Ton add on cooling
20 = 5 Ton add on cooling
Blower Drive
E = Constant Torque ECM
Cabinet Width
A = 14.5” width
B = 17.5” width
C = 21.0” width
AFUE
80 = 80% Efficency
Gas
Stages
2 = Two Stage
Configuration
UH = Upflow/Horizontal
BTUH Input
Heating Input x 1000
80 G 2 UH 110 C E 16 -01
508187-01Issue 2116Page 8 of 51
80G2UH070AE12 / 80G2UH070AE12L
External
Static
Pressure
in. w.g.
Air Volume / Watts at Various Blower Speeds
High
(Black)
Medium-High
(Brown)
Medium
(Blue)
Medium-Low
(Yellow)
Low
(Red)
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
0.00 1375 340 1350 240 1110 190 970 93 780 50
0.10 1350 346 1325 254 1100 194 940 104 725 57
0.20 1330 346 1310 264 1080 200 895 113 680 64
0.30 1315 353 1280 272 1060 204 860 118 610 70
0.40 1300 368 1250 283 1040 212 810 125 550 76
0.50 1285 369 1220 293 1010 222 765 132 510 78
0.60 1260 384 1190 301 975 227 725 140 460 83
0.70 1240 391 1150 314 950 236 680 147 400 89
0.80 1210 399 1120 319 915 244 640 152 355 95
80G2UH090BE12
External
Static
Pressure
in. w.g.
Air Volume / Watts at Various Blower Speeds
High
(Black)
Medium-High
(Brown)
Medium
(Blue)
Medium-Low
(Yellow)
Low
(Red)
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
0.00 1605 313 1475 240 1320 173 1050 99 865 60
0.10 1565 323 1430 251 1270 185 995 108 800 68
0.20 1515 334 1380 264 1225 196 935 115 730 76
0.30 1475 347 1340 275 1170 207 870 124 645 83
0.40 1435 360 1300 285 1120 215 805 133 550 91
0.50 1395 369 1250 295 1065 225 715 140 470 98
0.60 1355 378 1205 307 1010 235 655 147 395 101
0.70 1305 391 1160 318 935 246 560 156 345 107
0.80 1265 404 1105 329 875 254 510 162 300 112
BLOWER PERFORMANCE
80G2UH045AE12
External
Static
Pressure
in. w.g.
Air Volume / Watts at Various Blower Speeds
High
(Black)
Medium-High
(Brown)
Medium
(Blue)
Medium-Low
(Yellow)
Low
(Red)
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
0.00 1500 300 1220 175 1050 114 850 65 800 48
0.10 1485 311 1200 179 1025 118 810 68 790 50
0.20 1460 323 1170 188 980 125 725 73 580 53
0.30 1420 334 1140 195 930 133 670 76 455 54
0.40 1395 343 1095 203 890 138 600 86 375 60
0.50 1355 355 1050 212 840 149 550 93 325 64
0.60 1325 368 1020 222 790 158 495 96 275 67
0.70 1290 369 980 228 745 164 420 103 238 69
0.80 1260 381 945 238 700 172 380 107 --- ---
508187-01 Issue 2116 Page 9 of 51
80G2UH090BE16 / 80G2UH090BE16L
External
Static
Pressure
in. w.g.
Air Volume / Watts at Various Blower Speeds
High
(Black)
Medium-High
(Brown)
Medium
(Blue)
Medium-Low
(Yellow)
Low
(Red)
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
0.00 1800 370 1555 260 1425 207 1370 172 1240 131
0.10 1765 381 1525 272 1390 218 1320 184 1190 144
0.20 1725 397 1485 283 1350 229 1255 195 1130 157
0.30 1685 416 1450 296 1310 241 1205 206 1075 165
0.40 1635 425 1390 312 1260 250 1165 217 1015 174
0.50 1600 438 1350 322 1205 263 1100 230 955 185
0.60 1560 453 1300 332 1140 270 1050 239 905 193
0.70 1520 467 1255 344 1110 284 1000 249 840 202
0.80 1470 474 1215 352 1050 294 935 258 765 211
80G2UH110CE16
External
Static
Pressure
in. w.g.
Air Volume / Watts at Various Blower Speeds
High
(Black)
Medium-High
(Brown)
Medium
(Blue)
Medium-Low
(Yellow)
Low
(Red)
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
0.00 1780 349 1570 248 1465 190 1370 169 1250 131
0.10 1750 365 1540 260 1420 205 1330 177 1205 140
0.20 1720 382 1500 271 1365 220 1280 187 1155 150
0.30 1675 397 1460 279 1330 228 1250 197 1110 159
0.40 1645 407 1415 291 1290 241 1200 211 1070 166
0.50 1605 424 1395 307 1250 249 1165 219 1015 177
0.60 1580 432 1345 316 1205 258 1105 228 960 186
0.70 1565 448 1300 328 1165 271 1060 237 915 194
0.80 1525 449 1270 339 1125 283 1025 246 865 203
508187-01Issue 2116Page 10 of 51
80G2UH110CE20 / 80G2UH110CE20L
External
Static
Pressure
in. w.g.
Air Volume / Watts at Dierent Blower Speeds
Bottom Return Air, Side Return Air from Both Sides or Return Air from Bottom and
One Side.
Single Side Return Air - Air volumes in bold (over 1800 cfm) require Optional Return
Air Base and eld fabricated transition to accommodate 20 x 25 x 1 in. air lter in
order to maintain proper air velocity.
High
(Black)
Medium-High
(Brown)
Medium
(Blue)
Medium-Low
(Yellow)
Low
(Red)
High
(Black)
Medium-High
(Brown)
Medium
(Blue)
Medium-Low
(Yellow)
Low
(Red)
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
0.00 2175 590 2050 410 1850 310 1695 275 1510 195 2175 605 1930 420 1785 320 1675 260 1500 195
0.10 2158 607 1943 421 1778 328 1650 283 1461 205 2129 628 1892 441 1733 345 1627 288 1458 209
0.20 2131 620 1897 436 1719 345 1591 299 1405 215 2091 649 1838 458 1691 360 1586 297 1407 220
0.30 2085 639 1847 456 1678 354 1563 308 1351 228 2072 660 1806 471 1631 371 1529 313 1353 232
0.40 2055 652 1806 466 1641 371 1499 317 1297 238 2014 677 1772 485 1591 385 1485 327 1302 243
0.50 2030 668 1767 476 1588 387 1462 333 1256 254 1977 690 1742 498 1554 395 1444 337 1252 256
0.60 1976 686 1724 495 1550 399 1419 348 1215 265 1960 707 1696 511 511 410 1412 348 1204 265
0.70 1949 700 1685 510 1512 408 1371 357 1168 271 1913 720 1661 525 1480 424 1351 359 1149 274
0.80 1896 716 1649 527 1473 419 1332 372 1121 287 1873 738 1617 538 1440 437 1313 371 1117 285
508187-01 Issue 2116 Page 11 of 51
ACCESSORIES
Accessory Catalog Number
Return Air Base
Return Air Base 14.5” 68W61
Return Air Base 17.5” 68W62
Return Air Base 21.0” 68W62
High Altitude Pressure Switches
2-Stage 80% UH/DF (4501 - 7500 ft) [045, 070, 090 110] 91W53
2-Stage 80% UH/DF (7501 - 10,000 ft) [045, 070, 090 110] 73W35
High Altitude Orice Kits (7500 ft+)
2-Stage 80% UH/DF - Natural Gas 51W01
2-Stage 80% UH/DF - Propane Gas 11K47
Natural to LP Kits
2-Stage 80% UH/DF (0 - 7500 ft) 11K48
2-Stage 80% UH/DF (7501 - 10,000 ft) 11K47
LP to Natural Kits
2-Stage 80% UH/DF 77W10
Downow Specic Air Filters
14.5" 51W06
17.5" 51W07
Downow Combustible Flooring Base
14.5" 11M59
17.5" 11M60
Night Service Kits
2-Stage 22J94
Horizontal Suspension Kit
80% & 90% 51W10
External Filter Rack Kits
1 pack (16 x 25) 1.841018
10 pack (16 x 25) 1.841039
Twinning Kit
Constant Torque Gas Furnace Twinning Kit 16W72
For vent length and clearances to combustibles, please reference installation instructions.
508187-01Issue 2116Page 12 of 51
Parts Arrangement
Figure 1.
Combustion Air
Pressure Switch
Combustion Air
Inducer
Gas Valve and Manifold
Assembly
Limit Switch
(under collector box)
Collector Box
Heat Exchanger
Indoor Blower and Motor Assembly
(installed in cabinet)
Make Up Box
Constant Torque Indoor Blower Motor
(removed from cabinet)
Two-Stage Integrated Control
508187-01 Issue 2116 Page 13 of 51
Unit Components
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
Electrostatic discharge can aect electronic
components. Take precautions to
neutralize electrostatic charge by touching
your hand and tools to metal prior to
handling the control.
CAUTION
A80UH2E / 80G2UHE(L) unit components are shown
in Figure 1. The gas valve, combustion air inducer and
burners can be accessed by removing the access panel.
Electrical components are in the control box (Figure 2)
found in the blower section.
A80UH2E / 80G2UHE(L) units are factory equipped with
a bottom return air panel in place. The panel is designed
to be eld removed as required for bottom air return.
Markings are provided for side return air and may be cut
out in the eld.
Control Box Components (Figure 2)
Transformer
Integrated Control
Interlock Switch
Circuit Breaker
Figure 2. Control Box
Transformer (T1)
A transformer located in the control box provides power
to the low voltage section of the unit. Transformers on all
models are rated 40VA with a 120V primary and a 24V
secondary.
Door Interlock Switch (S51)
A door interlock switch is wired in series with line voltage.
When the inner blower access panel is removed the unit
will shut down.
Circuit Breaker (CB8)
A 24V circuit breaker is also located in the control box. The
switch provides overcurrent protection to the transformer
(T1). The breaker is rated at 3A at 32V. If the current
exceeds this limit the breaker will trip and all unit operation
will shutdown. The breaker can be manually reset by
pressing the button on the face. See Figure 3.
Figure 3. Circuit Breaker (CB8)
PRESS TO RESET
Integrated Ignition Control (A92)
Shock hazard.
Disconnect power before servicing.
Control is not eld repairable. If control is
inoperable, simply replace entire control.
Can cause injury or death. Unsafe
operation will result if repair is attempted.
WARNING
Units are equipped with a two-stage, integrated control.
The system consists of a ignition / blower control (Figure
4 and Figure 5) with control pin designations in Table 1
and Table 2 and ignitor. The control and ignitor work
in combination to ensure furnace ignition and ignitor
durability. The control provides gas ignition, safety checks
and indoor blower control with two-stage gas heating.
The furnace combustion air inducer, gas valve and indoor
blower are controlled in response to various system inputs
such as thermostat signal, pressure and limit switch signal
and ame signal. The control features a seven-segment
LED display, indicating furnace status and error codes.
The LED ashes in single digits. For example, using Table
4 under LIMIT CODE, an “E” followed by “2” followed by “5”
followed by “0”, the limit switch circuit is open. The control
also has two unpowered (dry) 1/4” contacts for a humidier
and a 120 volt accessory terminal. Both rated at (1) one
amp each.
508187-01Issue 2116Page 14 of 51
Pin # Function
1Ignitor
2 Combustion Air Inducer High Speed
3Combustion Air Inducer Low Speed
4Combustion Air Inducer Neutral
5Ignitor Neutral
Table 1. 5-Pin Terminal Designations
Pin # Function
1Gas Valve Second Stage
2 Second Stage Pressure Switch
3Rollout Switch In
4Ground
524V Hot
6Primary Limit In
7Gas Valve First Stage
8Gas Valve Common
9 24V Neutral
10 Ground
11 Primary Limit Out
12 First Stage Pressure Switch
Table 2. 12-Pin Terminal Designations
Electric Shock Hazard.
Can cause injury or death. Unit must be
properly grounded in accordance with
national and local codes.
WARNING
Fire Hazard.
Use of aluminum wire with this product may result in a
re, causing property damage, severe injury or death.
Use copper wire only with this product.
WARNING
Electronic Ignition
At the beginning of the heat cycle the integrated control
monitors the rst stage and second stage combustion air
inducer pressure switch. The control will not begin the
heating cycle if the rst stage pressure switch is closed
(bypassed). Likewise the integrated control will not begin
the second stage heating cycle if the second stage
pressure switch is closed, and will remain in rst stage
heat. However, if the second stage pressure switch closes
during the rst stage heat pre-purge, the control will allow
second stage heat. Once the rst stage pressure switch
is determined to be open, the combustion air inducer is
energized on low (rst stage) heat speed. When the
dierential in the pressure switch is great enough, the
pressure switch closes and a 15-second pre-purge begins.
After the 15-second pre-purge period, the ignitor warms
up for 20 seconds after which the gas valve opens for a
4-second trial for ignition. The ignitor remains energized
during the trial until ame is sensed. If ignition is not proved
during the 4-second period, the control will try four more
times with an inter purge and warm-up time between trials
of 35 seconds. After a total of ve trials for ignition (including
the initial trial), the control goes into Watchguard-Flame
Failure mode. After a 60-minute reset period, the control
will begin the ignition sequence again.
NOTE: During abnormal conditions such as low supply
voltage or low outdoor temperatures and the low re
pressure switch does not close, the combustion air inducer
will switch to high speed. After the low & high pressure
switch close, the unit will proceed with a 15 sec pre-purge,
followed by a 20 sec ignitor warm up, then ignition on
highre. After 10 to 20 seconds of high re operation the
unit will switch to low re.
Two Stage Operation / Thermostat Selection DIP
Switch
The control can be utilized in two modes: SINGLE-STAGE
thermostat or TWO-STAGE thermostat. The thermostat
selection is made using a DIP switch and must be positioned
for the particular application. DIP switch 1, labeled T”STAT
HEAT STAGE is factory-set in the OFF position for use
with a two-stage thermostat. Move the DIP switch to ON
for use with a single stage thermostat.
While in the single-stage thermostat mode, the burners will
always re on rst-stage heat. The combustion air inducer
will operate on low speed and indoor blower will operate on
low heat speed. The unit will switch to second stage heat
after a “recognition period”. DIP switch 2, labeled SECOND
STAGE DELAY, is factory set in the OFF position for a 7
minute recognition period. The switch can be moved to the
ON position for a 12 minute recognition period, after which
time the unit will switch to second-stage heat.
While in the two-stage thermostat mode, the burners will
re on rst-stage heat. The combustion air inducer will
operate on low speed and indoor blower will operate on low
heat speed. The unit will switch to second-stage heat on
call from the indoor thermostat. If there is a simultaneous
call for rst and second stage heat, the unit will re on
rst stage heat and switch to second stage heat after 30
seconds of operation. See Sequence of Operation ow
charts in the back of this manual for more detail.
508187-01 Issue 2116 Page 15 of 51
Figure 4. Integrated Control
Flame Sense
S4 DIP Switches
24VAC Indoor
Blower Terminals
HUM ACC
Ignitor and Combustion
Air Inducer
Neutrals
On Board Links
LED
Diagnostic Push
Button
3/16” QUICK CONNECT TERMINALS
FLAME SENSE SIGNAL
HI COOL 24VAC
LO COOL 24VAC
LO HEAT 24VAC
PARK
PARK
COMMON 24VAC
1/4” QUICK CONNECT TERMINALS
NEUTRALS = 120 VAC NEUTRAL
HUM = UNPOWERED NORMALLY OPEN (DRY) CONTACTS
LI = 120VAC INPUT TO CONTROL
A
CC = 120VAC OUTPUT TO OPTIONAL ACCESSORY
THERMOSTAT CONNECTIONS (TB1)
DS = DEHUMIDIFICATION SIGNAL
W2 = HEAT DEMAND FROM 2ND STAGE TSTAT
W1 = HEAT DEMAND FROM 1ST STAGE TSTAT
R = CLASS 2 VOLTAGE TO TSTAT
G = MANUAL FAN FROM TSTAT
C = TSTAT SIGNAL GROUND CONNECTED TO
TRANSFORMER GRD (TR) & CHASSIS GROUND (GRD)
Y1 = TSTAT 1ST STAGE COOL SIGNAL
Y2 = TSTAT 2ND STAGE COOL SIGNAL
O = TSTAT SIGNAL TO HEAT PUMP REVERSING VALVE
DH = NOT USED
L = NOT USED
508187-01Issue 2116Page 16 of 51
Figure 5. Integrated Control Conguration Guide
HEATING BLOWER−OFF DELAY
60 SECOND
HTG BLOWER
OFF DELAY
120 SECOND
HTG BLOWER
OFF DELAY
180 SECOND
HTG BLOWER
OFF DELAY
FLAME
15
HSI/CAI
2ND STAGE HEAT ON DELAY
7 MIN
UPSTAGE
DELAY
12 MIN
UPSTAGE
DELAY
*
W915
2 STAGE
COMPR
1−STG COMPRESSOR
2−STAGE
COMPRESSOR LINK
(JUMPERS Y1 to Y2)
W915
DO NOT CUT
2−STG COMPRESSOR
HEAT PUMP LINK
(JUMPERS R to O)
W951
(JUMPERS R to DS)
W914
W915
2 STAGE
COMPR
CUT LINK
A/C UNIT
DO NOT CUT
HEAT PUMP UNIT
CUT LINK
W951
HEAT
PUMP
W951
HEAT
PUMP
W914
DEHUM
NO SIGNATURESTAT
W/ DS CONNECTION
DO NOT CUT
SIGNATURESTAT W/
DS CONNECTION
CUT LINK
W914
DEHUM
1
1
1
ON−BOARD LINK
OPTION SELECTION
1234567
1234567
123567
4
123567
4
NEUTRALS
L1
ACC
HUM
14
36
P79
110
312
J2
4 7
W915
2 STAGE
COMPR
W951
HEAT
PUMP
W914
DEHUM
CUT FOR
OPTION
SELECTION
123456
ON
W1W2 GY2 Y1 CC DH LODSR
W1
W2
G
Y2
Y1
C
C
R
L
DH
7
1
ON
ON
ON
ON
90 SECOND
HTG BLOWER
OFF DELAY
*1234567
ON
1234567
ON
THERMOSTAT SELECTION
1−STAGE
THERMOSTAT
(TIMED STAGING)
−SEE SW #2
TWO STAGE
THERMOSTAT
*
1234567
1234567
ON
ON
−BLOWER ON DELAY − 30 SEC. FIXED
1234567
ON
SENSE
IGN
CAI2
CAI1
N
N
J3
S1
S4S3
DIAGNOSTIC
LED
DIAGNOSTIC
PUSH BUTTON
*45 SECOND
COOL BLOWER
OFF DELAY
2 SECOND
COOL BLOWER
OFF DELAY
123567
4
123567
4
ON
ON
COOLING BLOWER-OFF DELAY
1234567
ON
1234567
ON
1234567
ON
CONTINUOUS FAN SETTINGS
LOW HEAT SPEED
LOW COOL SPEED
HIGH HEAT SPEED
HIGH COOL SPEED
DEHUMIFICATION LINK
- CUT ON-BOARD LINK (SOLDER TRACE)
COMPLETELY THROUGH BOTH LAYERS ON THE
CONTROL BOARD
- LINKS CUT IN ERROR - INSTALL A JUMPER ON THE
APPROPRIATE TERMINALS ON THE TERMINAL
STRIP
- PROTECTIVE PLASTIC FILM ON DIP SWITCHES
MAY BE REMOVED FOR EASE IN SETTING OF DIP
SW.
* FACTORY DEFAULT
508187-01 Issue 2116 Page 17 of 51
Display Action (when button released)
No change (idle)* Remain in idle mode
Solid “E” Enter diagnostic recal mode
Solid “F” Enter ame signal mode
* No change implies the display will continue to show whatever is currently being displayed for normal operation (blinking decimal,
active error code, heat state, etc.)
Table 3. Integrated Control Diagnostic Modes
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
.Idle mode (Decimal blinks at 1 Hertz -- 0.5
second ON, 0.5 second OFF).
CCooling stage (1 second ON, 0.5 second OFF)
1 or 2 displayed / Pause / Repeat codes.
d Dehumidication mode (1 second ON, 1
second OFF) / Pause / Repeat Codes).
H Gas Heat Stage (1 second ON, 0.5 second
OFF) 1 or 2 displayed / Pause / Repeat codes.
Blinking during ignition.
hHeat pump stage.
E110 Low line voltage. Line Voltage Low (Voltage lower than nameplate rating). Check power line
voltage and correct. Alarm clears 5 seconds after fault recovered.
E111 Line voltage polarity reversed. Reverse line power voltage wiring. System resumes normal operation 5
seconds after fault recovered.
E112 Ground not detected. System shuts down. Provide proper earth ground. System resumes normal
operation 5 seconds after fault recovered.
E113 High line voltage. Line Voltage High (Voltage higher than nameplate rating). Provide power
voltage within proper range. System resumes normal operation 5 seconds
after fault recovered.
E114 Line voltage frequency out-of-range. No 60 Hertz Power. Check voltage and line power frequency. Correct
voltage and frequency problems. System resumes normal operation 5
seconds after fault recovered.
E115 Low 24V - Control will restart if the error
recovers.
24-Volt Power Low (Range is 18 to 30 volts). Check and correct voltage.
Check for additional power-robbing equipment connected to system. May
require installation of larger VA transformer to be installed in furnace / air
handler. Clears after fault recovered.
E117 Poor ground detected (Warning only) Provide proper grounding for unit. Check for proper earth ground to the
system. Warning only will clear 30 seconds after fault recovered.
E125 Control failed self-check, internal error,
failed hardware. Will restart if error recovers.
Integrated control not communicating. Covers
hardware errors (ame sense circuit faults, pin
shorts, etc.).
Hardware problem on the control. Cycle power on control. Replace if
problem prevents service and is persistent. Critical alert. Cleared 300
seconds after fault recovered.
E200 Hard lockout - Rollout circuit open or previously
open.
Correct cause of rollout trip, or replace ame rollout switch. Test furnace
operation. Cleared after fault recovered.
E204 Gas valve mis-wired. Check gas valve operation and wiring. Clears when repaired.
E205 Gas valve control relay contact shorted. Check wiring on control and gas valve. If wiring is correct, replace control.
E206 Gas valve second-stage relay failure. Furnace will operate on 1st stage for remainder of the heating demand.
Will clear after fault recovered. If unable to operate 2nd stage, replace
control.
E207 Hot surface ignitor sensed open. Measure resistance of hot surface ignitor. Replace if open or not within
specied range found in IOM. Resumes normal operation after fault is
cleared.
Table 4. Integrated Diagnostic Codes / Status of Equipment
508187-01Issue 2116Page 18 of 51
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
E223 Low pressure switch failed open. Check pressure (inches w.c.) of low pressure switch closing on heat call.
Measure operating pressure (inches w.c.). Inspect vent and combustion
air inducer for correct operation and restriction. Resumes normal operation
after fault is cleared
E224 Low pressure switch failed closed. Check operation of low pressure switch to see if it is stuck closed on
heat call longer than 150 seconds. Measure operating pressure (inches
w.c.). Inspect vent and combustion air inducer for correct operation and
restriction. Resumes normal operation after fault is cleared.
E225 High pressure switch failed open. Check pressure (inches w.c.) of high pressure switch closing on heat call.
Measure operating pressure (inches w.c.). Inspect vent and combustion air
inducer for correct operation and restriction. Resumes normal operation
after fault is cleared.
E226 High pressure switch failed closed. Check operation of high pressure switch closing on heat call. Measure
operating pressure (inches w.c.). Inspect vent and combustion air inducer
for correct operation and restriction. Resumes normal operation after fault
is cleared.
E227 Low pressure switch open during trial for
ignition or run mode.
Check pressure (inches w.c.) of low pressure switch closing on heat call.
Measure operating pressure (inches w.c.). Inspect vent and combustion
air inducer for correct operation and restriction. Resumes normal operation
after fault is cleared.
E229 Ignition on High Fire - Information Only. Code is displayed if 1) low pressure switch fails to close, then furnace will
switch to high speed inducer to close both low and high pressure switches,
then furnace lights on high re, or 2) if continuous fan is active, furnace
lights on high re for 60 seconds to improve heat exchanger warm up time.
E240 Low ame current - Run mode. Check micro-amperes of ame sensor using control diagnostics or eld-
installed mode. Clean or replace sensor. Measure voltage of neutral to
ground to ensure good unit ground. Alert clears after current heat call has
been completed.
E241 Flame sensed out of sequence - Flame still
present.
Shut o gas. Check for gas valve leak. Replace, if necessary. Alert clears
when fault is recovered.
E250 Limit switch circuit open. Check for proper ring rate on furnace. Ensure there is no blockage in
heater. Check for proper air ow. If limit not closed within 3 minutes, unit will
go into 1-hour soft lockout. Resumes normal operation after fault is cleared.
E270 Soft lockout - Exceeded maximum number of
retries. No ame current sensed.
Check for proper gas ow. Ensure that ignitor is lighting burner. Check
ame sensor current. Clears when heat call nishes successfully.
E271 Soft lockout - Exceeded maximum number of
retries. Last retry failed due to the pressure
switch opening.
Check pressure (inches w.c.) of low pressure switch closing on heat call.
Measure operating pressure (inches w.c.). Inspect vent and combustion air
inducer for correct operation and restriction. Clears when heat call nishes
successfully.
E272 Soft lockout - Exceeded maximum number
of recycles. Last recycle due to the pressure
switch opening.
Check operation of low pressure switch to see if it is stuck closed on
heat call. Check pressure (inches w.c.) of high pressure switch closing
on heat call. Measure operating pressure (inches w.c.). Inspect vent and
combustion air inducer for correct operation and restriction. Clears when
heat call nishes successfully.
E273 Soft lockout - Exceeded maximum number of
recycles. Last recycle due to ame failure.
Check micro-amperes of ame sensor using control diagnostics or eld-
installed mode. Clean or replace sensor. Measure voltage of neutral
to ground to ensure good unit ground. Clears when heat call nishes
successfully.
E274 Soft lockout - Exceeded maximum number of
recycles. Last recycle failed due to the limit
circuit opening or limit remained open longer
than 3 minutes.
Shut down system. 1-hour soft lockout. Check ring rate and air ow.
Check for blockage. Clears when heat call nishes successfully.
E275 Soft lockout - Flame sensed out of sequence.
Flame signal is gone.
Shut o gas. Check for gas valve leak. 1-hour soft lockout. Clears when
ame has been proven stable.
Table 4. Integrated Diagnostic Codes / Status of Equipment
508187-01 Issue 2116 Page 19 of 51
Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover
E290 Ignitor circuit fault - Failed ignitor or triggering
circuitry.
Measure resistance of hot surface ignitor. Replace if open or not within
specications. 1-hour soft lockout. Clears when ame has been proven
stable.
Table 4. Integrated Diagnostic Codes / Status of Equipment
Diagnostic LED (Figure 4)
The seven-segment diagnostic LED displays operating
status, error codes and other information. Table 4 lists
diagnostic LED codes.
Diagnostic Push Button (Figure 4)
The diagnostic push button is located adjacent to the seven-
segment diagnostic LED. This button is used to enable
the Error Code Recall “E” mode and the Flame Signal “F”
mode. Press the button and hold it to cycle through a menu
of options. Every ve seconds a new menu item will be
displayed. When the button is released, the displayed item
will be selected. Once all items in the menu have been
displayed, the menu resumes from the beginning until the
button is released.
Error Code Recall Mode
Select ”E” from the menu to access the most recent 10
error codes. Select “c” from the Error Code Recall menu
to clear all error codes. Button must be pressed a second
time while “c” is ashing to conrm command to delete
codes. Press the button until a solid “≡” is displayed to exit
the Error Code Recall mode.
Flame Signal Mode
Select ”F” from the menu to access the ame signal mode.
The integrated control will display the ame current on
seven-segment LED in in micro amps (uA).
Flame signal mode is exited after any of the following:
Power is reset
Pressing and holding push button until 3 horizontal
lines “≡” are displayed
10 minutes after entering the ame sense mode.
Integrated Control DIP Switches
Integrated Control DIP Switches
A80UH2E / 80G2UHE(L) units are equipped with a two-
stage integrated control. This control manages ignition
timing, heating mode fan o delays and indoor blower
speeds based on selections made using the control dip
switches and jumpers. The control includes an internal
watchguard feature which automatically resets the ignition
control when it has been locked out. After one hour of
continuous thermostat demand for heat, the watchguard
will break and remake thermostat demand to the furnace
and automatically reset the control to relight the furnace.
Heating Operation DIP Switch Settings
Switch 1 -- Thermostat Selection -- This unit may be
used with either a single-stage or two-stage thermostat.
The thermostat selection is made using a DIP switch which
must be properly positioned for the particular application.
The DIP switch is factory-positioned for use with a twostage
thermostat. If a single-stage thermostat is to be used, the
DIP switch must be repositioned.
a. Select “OFF” for two-stage heating operation
controlled by a two-stage heating thermostat
(factory setting);
b. Select “ON” for two-stage heating operation
controlled by a single-stage heating thermostat.
This setting provides a timed delay before second-
stage heat is initiated.
Switch 2 --- Second Stage Delay (Used with Single-
Stage Thermostat Only) -- This switch is used to determine
the second stage on delay when a single-stage thermostat
is being used. The switch is factory-set in the OFF position,
which provides a 7-minute delay before second-stage heat
is initiated. If the switch is toggled to the ON position, it
will provide a 12-minute delay before second-stage heat is
initiated. This switch is only activated when the thermostat
selector jumper is positioned for single-stage thermostat
use.
508187-01Issue 2116Page 20 of 51
Indoor Blower Operation DIP Switch Settings
Switches 3 and 4 -- Heating Mode Blower-O Delay --
The blower-on delay of 30 seconds is not adjustable. The
blower-o delay (time that the blower operates after the
heating demand has been satised) can be adjusted by
moving switches 3 and 4 on the integrated control. The
unit is shipped from the factory with a blower-o delay
of 90 seconds. The blower o delay aects comfort and
is adjustable to satisfy individual applications. Adjust
the blower o delay to achieve a supply air temperature
between 90° and 110°F at the exact moment that the blower
is de-energized. Longer o delay settings provide lower
supply air temperatures; shorter settings provide higher
supply air temperatures. Table 5 provides the blower o
timings that will result from dierent switch settings.
Blower O Delay
(seconds) Switch 3 Switch 4
60 On O
90 (Factory) O O
120 O On
180 On On
Table 5. Blower O Heating Mode Delay Switch
Settings
Switch 5 -- Cooling Mode Blower-O Delay -- The unit
is shipped from the factory with the dip switch positioned
OFF for a 45 second delay. Table 6 provides the cooling
mode o delay settings.
Blower O Delay
(seconds) Switch 5
45 (Factory) O
2 On
Table 6. Blower O Cooling Mode Delay Switch
Settings
Switches 6 and 7 -- Continuous Fan Mode -- Continuous
fan speed can be controlled by changing DIP switch
positions. Table 7 provides DIP switch settings for
continuous fan mode.
Continuous Fan
Mode Switch 6 Switch 7
Low Heat Speed
(Factory) O O
Low Cool Speed O On
High Heat Speed On O
High Cool Speed On On
Table 7. Continuous Fan Mode Settings
Onboard Links
W914 Dehum
Onboard link W914, is a clippable connection between
terminals R and DS on the integrated control. W914 must
be cut when the furnace is installed with a thermostat which
features humidity control. If the link is not cut, terminal “DS”
will remain energized not allowing the blower to reduce to
low cool speed upon a call for dehumidication.
W951 Heat Pump (R to O)
Onboard link W951 is a clippable connection between
terminals R and O on the integrated control. W951 must
be cut when the furnace is installed in applications which
include a heat pump unit and a thermostat which features
dual fuel use. If the link is left intact, terminal “O” will remain
energized eliminating the HEAT MODE in the heat pump.
W915 2 Stage Compr (Y1 to Y2)
Onboard link W915 is a clippable connection between
terminals Y1 and Y2 on the integrated control. W915 must
be cut if two-stage cooling will be used. If the Y1 to Y2
link is not cut the outdoor unit will operate in second-stage
cooling only.
If any onboard link is cut by mistake, install a jumper
across the corresponding terminals on the low voltage
terminal strip. Do not replace control.
IMPORTANT
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51

Allied 80G2E User manual

Category
Split-system air conditioners
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI