Karel DS200 Installation guide

Type
Installation guide
CONTENTS
I. SETTING UP THE SYSTEM ...........................................................................................1
I.1.THE WALL TYPE DS200 SYSTEM INSTALLATION..............................................................1
I.1.A. PREPARATION...............................................................................................................................1
I.1.B. APPLICATION ................................................................................................................................1
I.1.C. GROUNDING ..................................................................................................................................4
I.1.D. BATTERY CONNECTION................................................................................................................5
I.2.THE CABINET-TYPE DS200 SYSTEM INSTALLATION........................................................5
I.2.A. PREPARATION...............................................................................................................................5
I.2.B. APPLICATION ................................................................................................................................6
I.2.C. INSTALLATION OF SYSTEMS WITH FOUR OR MORE RACKS .....................................................8
I.2.C.1. CONNECTIONS IN THE MAIN RACK, TO WHICH THE CPU200 CARD HAS BEEN ATTACHED:........... 9
I.2.C.1.1. ATTACHING THE CC EXTRA CARD ONTO THE CPU200 CARD:..........................................................................9
I.2.C.1.2. INTEGRATION OF THE C MASTER CARD TO THE MAIN RACK:........................................................................10
I.2.C.1.3. CONNECTING THE BPLSPS-FCX CABLE:.........................................................................................................11
I.2.C.2. CONNECTIONS ON THE FOURTH RACK:.............................................................................................12
I.2.C.2.1. INTEGRATION OF THE C SLAVE CARD TO THE MAIN RACK............................................................................12
I.2.C.2.2. ATTACHING THE CC ENABLE CARD TO THE MAIN RACK: ..............................................................................12
I.2.C.2.3. CONNECTING THE BPLSPS-FCX CABLE:.........................................................................................................12
I.2.D. GROUNDING................................................................................................................................12
I.2.E. BATTERY CONNECTION..............................................................................................................14
I.3.INSTALLING POWER SUPPLIES IN THE SYSTEM............................................................16
I.3.A. SPS200 AC/DC POWER SUPPLY.................................................................................................16
I.3.B. SPS248 DC/DC POWER SUPPLY ................................................................................................16
I.4.INTEGRATING MODULES TO THE SYSTEM......................................................................16
I.4.A.CPU200, REDUNDANT CPU200 & DS200 CPUKON CARDS.......................................................16
I.4.A.1. THE LAN ADAPTOR CARD:....................................................................................................................17
I.4.B. THE UTIL200 UTILITY MODULE..................................................................................................18
I.4.B.1. ınstallıng the conference chıp on UTIL200...........................................................................................18
I.4.C. CON2/CON3 LINE CONNECTION CARDS...................................................................................19
I.4.D. INSTALLING EXPANSION MODULES.........................................................................................21
I.4.D.1. ATTACHING EX200 MODULES:.............................................................................................................21
I.4.D.2. CABLING OF EX200 MODULES:............................................................................................................22
I.4.D.2.1. EX200 (0/16) ANALOG EXTENSION MODULE:...................................................................................................22
I.4.D.2.2. EX200 (8/0) ANALOG LINE MODULE:................................................................................................................23
I.4.D.2.3. EX200 (0/8S0) ISDN BRI EXTENSION MODULE:...............................................................................................23
I.4.D.2.4. EX200 (1S2/0) ISDN PRI MODULE:....................................................................................................................24
I.4.D.2.5. EX200 (1R2/0) R2 DIGITAL LINE MODULE:.......................................................................................................24
I.4.D.2.6. EX200 (0/8U) DIGITAL EXTENSION MODULE:...................................................................................................25
I.4.D.2.7. EX200 (0/16U) DIGITAL EXTENSION MODULE:.................................................................................................25
I.4.D.2.8. EX200 (8 T0/S0) ISDN BRI LINE/EXTENSION MODULE:...................................................................................26
I.4.D.2.9. EX200 (0/8LB) LOCAL BATTERY EXTENSION MODULE:...................................................................................27
I.4.D.2.10. EX200 (4E&M/0) E&M LINE MODULE:............................................................................................................27
I.4.E. JUMPER SETTINGS ON THE EX200 (8T0/S0) MODULE........................................................28
I.4.F. JUMPER SETTINGS ON THE EX200 (4E&M/0) MODULE ......................................................29
I.4.G. INSTALLATION OF THE EVM200L MODULE ..............................................................................31
I.5. THE FINAL PREPARATIONS............................................................................................31
II. PUTTING THE SYSTEM ON LINE...............................................................................33
II.1. SINGLE-RACK, WALL-TYPE SYSTEM.............................................................................33
II.2. TWO-RACK WALL-TYPE SYSTEM...................................................................................33
II.3. CABINET-TYPE SYSTEM.................................................................................................33
II.4. TWO-CABINET SYSTEM..................................................................................................34
III. TESTING THE SYSTEM AND TROUBLESHOOTING BASIC PROBLEMS ..................36
DS200 Installation Guide
DS200 Installation GuideDS200 Installation Guide
DS200 Installation Guide
V003. 25.06.2002
B-1
I. SETTING UP THE SYSTEM
The DS200 system can be set up in two different structures, namely as wall type and cabinet
type.
I.1.THE WALL TYPE DS200 SYSTEM INSTALLATION
If the DS200 system consists of one or two racks at most, then it can be mounted as wall
type. As for the systems with three or more racks, they definitely have to be mounted as
cabinet type.
I.1.A. PREPARATION
The following requirements should be fulfilled prior to the installation of the exchange:
1- The wall on which the DS200 exchange will be mounted should be firm enough to carry
the weight and it should have a smooth surface.
2- The exchange should be installed in places that are not exposed to direct sunlight, that
are not humid, but that are ventilated, well lit, with an environmental temperature of 0-
45
o
C. It should not be exposed to effects of dust, vibration, oil and water.
3- Devices that generate high frequency waves (such as welding machines, office equipment
such as computers and telex machines, air conditioners, TV sets) should not be in the
same room if possible, and they should be at least 3 meters away from the exchange,
otherwise.
4- The mains supply should be reserved for the exchange only. The power supply of the
system should be uninterrupted and, if possible, the system should be powered from an
independent and well-grounded source from which no other device is powered.
!
POWER SUPPLY THAT IS INTERRUPTED FREQUENTLY MAY AFFECT
NORMAL OPERATION OF THE SYSTEM!
5- The spot where the exchange is to be mounted should be at a distance to the main
distribution frame (MDF), so that the MDF can be reached through three-meter line
connection cables. While the distance is being determined, the flexibility of the cables
and the way they will be fixed to the wall should also be considered.
6- A location that can be reached easily should be chosen, considering the installation work
and later maintenance work.
7- Place requirement for the batteries should be considered, as well.
!
THE AIR VENTS AT THE TOP AND BOTTOM OF THE EXCHANGE MUST
NOT BE BLOCKED BY ANY MEANS. PREVENTING VENTILATION MAY DAMAGE
THE EXCHANGE!
I.1.B. APPLICATION
1- Plot a location that complies with the requirements indicated in the Preparation step
above.
2- By making use of the installation template that comes with the racks, mark the locations
for the wall mount bars carefully that are to be used for hanging the racks on the wall.
DS200 Installation Guide
DS200 Installation GuideDS200 Installation Guide
DS200 Installation Guide
V003. 25.06.2002
B-2
The lower hole of the wall mount bars should be approximately 130 cm. above the floor. It
is essential to check whether the height of both holes are the same, in order to make
sure the exchange is parallel to the floor.
3- If there are two DS200 racks to be installed, then the lower hole of the wall mount bars,
for the first rack to be installed (That will be the lower rack.), should be 100 cm. above
the floor.
4- Drill the lower wall mount bar hole of the second rack 140 cm. above the floor, vertically
on the same line with the first one. When the installation is over, there will be a 10-cm
gap between the two racks.
Figure – 1
5- Drive the anchor plugs into the holes, whose locations have already been checked, and
then screw the wall mount bars. Note that the right and the left side of the wall mount
bars differ. The screws must be fixed enough to burry their heads completely into the
wall.
6- After removing the front cover of the exchange by unscrewing the Allen screws, remove
the bottom cover by sliding it to the front.
7- While removing the bottom cover, watch out for the grounding cables that are between
the cover and the main frame, so that they will not break off. Remove the cables from the
covers together with their tags and keep them safe from any damage during the
installation.
8- Slide the SPS200 to the front and remove it, after loosening its screws. (This is just for
facilitating the installation and not obligatory.)
DS200 Installation Guide
DS200 Installation GuideDS200 Installation Guide
DS200 Installation Guide
V003. 25.06.2002
B-3
9- Hold the exchange so that the wall mount bar holes at the back of the exchange
correspond to the wall mount bar holders, then push the exchange towards the wall, so
that the holders would carry it. Make sure the holders of both wall mount bars have been
inserted into the holes, and then lower the exchange cautiously. The exchange is fixed 5
mm. below. If it is still not fixed, even though it has been lowered for about one
centimeter, that indicates the holders do not carry it. In that case, try to hang the
exchange once again. In order to make sure that the exchange has been fixed, gently
shake it to check whether the wall mount bars really carry it.
10- In case it is necessary to displace the exchange, just lift it upwards cautiously and pull it
out.
!
IT IS ESSENTIAL TO MOUNT AND DISMOUNT THE WALL MOUNT BARS
SIMULTANEOUSLY; OR THEY MAY GET DISTORTED.
11- If the second rack will be installed, then remove the top cover of the lower rack and the
bottom cover of the upper rack, in order to attach the cables that will connect the racks
to each other (Caution is needed for the grounding cables, as explained in the seventh
step.) The BPL200 main boards are connected to each other by the BPL200-FC and
BPLSPS-FC connection cables that come with the shipped hardware of the auxiliary rack.
There are three such cables. Two BPL200-FC's (34-pin flat cable) are used for connecting
the BPL200 backplanes and the single BPLSPS-FC (5-wire cable) is used for combining
BPL200-SPS backplanes.
1. BPL200-FC connections 2. BPLSPS-FC connection
DS200 Installation Guide
DS200 Installation GuideDS200 Installation Guide
DS200 Installation Guide
V003. 25.06.2002
B-4
a) BPL200-AUX d) BPL200-SPS
b) BPL200-FC e) BPLSPS-FC
c) BPL200-MAIN f) BPL200-SPS
Figure – 2
12- Replace the covers by coinciding the cables with the corresponding cable slots that are at
the back of the covers.
13- If SPS200 has been removed in order to facilitate the installation, then replace it as will
be explained in detail later.
14- Connect the 230 VAC cable to the corresponding input on SPS200. Before plugging the
other end of the cable in, check the position of the on/off switches and whether the fuses
are defective. The mains on/off switch must be off. Keep in mind that the battery on/off
switch must be set to “on” after the mains supply is on and it must be set to “off” before
the power is shut off. (Putting the System on Line is described in Section II.)
Two 2A T-type fuses that are necessary for 230 VAC are in the drawer-type compartment
next to the 230 VAC input.
I.1.C. GROUNDING
Grounding is required for protecting the DS200 exchange from lightning and other sources of
high voltage that may affect through lines or peripheral devices. The 230 VAC power cable of
the exchange has grounding feature, so there is no need for an extra grounding if the
electrical installation of the building has sound grounding.
Although special tools are required for measuring the sufficiency of grounding of the electric
installation of the building precisely, voltages between Neuter-Phase and Neuter-Ground
can be measured for getting a rough idea. The Neuter-Phase voltage should be 180-260 VAC
and the Neuter-Ground voltage should be 1-2 VAC. Those values must be consistent.
Possible voltage leakage in grounding installation may damage your exchange, just like all
other devices that require grounding.
!
ADDITIONAL GROUNDING MUST BE PROVIDED, IF SOUNDNESS OF
THE GROUNDING OF THE ELECTRIC SYSTEM CANNOT BE GUARANTEED.
Water installation of the building can be used for grounding, provided that the pipes are of
metal and no insulation material has been used at junctions.
Indeed, the most secure grounding method is inserting a copper rod that is 1.5 cm in
diameter with 1.5 m of length, or inserting a copper plate with 1 m
2
of area to the ground and
connecting it to the exchange through a copper grounding cable. The cable should be
fastened tightly to the rod or to the plate and precautions should be taken against corrosion.
The cable coming from the grounding plate or grounding installation must be connected to
the ground connection point of the exchange.
If the second rack is to be installed as well, then the ground connection points of the two
racks must be connected to each other tightly with the ground connection cable that comes
with the auxiliary rack.
!
THE GROUND CONNECTIONS OF THE LOWER AND UPPER COVERS OF
THE EXCHANGE MUST DEFINITELY BE DONE AGAIN WHEN THE COVERS ARE
REMOVED AND THEN REPLACED.
DS200 Installation Guide
DS200 Installation GuideDS200 Installation Guide
DS200 Installation Guide
V003. 25.06.2002
B-5
A- DS200 Main Rack
B- DS200 Auxiliary Rack
C- The grounding cable
D- The copper grounding plate or rod
Figure – 3
I.1.D. BATTERY CONNECTION
Since power failure will impede your exchange to fulfill its normal functions, a battery must
be connected to it, if there is such a possibility. Battery connection is made after SPS200 has
been fixed. The battery switch must be “0” during the connection. There are two clips on
SPS200 for the battery connection. (See The Technical Reference GuideFigure – 13). It is
strictly recommended that a 48V 24Ah dry battery group (12V, 24Ah X 4) should be connected
to those clips. The red end must be connected to the “+” pole of the battery group, and the
black end to the “-“ pole. In order to make the connection, press the springed latch of the
clips, insert the corresponding end of the battery cable into the hole in front, deep enough so
that no naked portion of the cable is left outside, and then release the latch.
Battery connection is provided only for the SPS200 of the main rack, in two-rack systems.
There is no battery connection for the second SPS200.
!
REVERSE BATTERY CONNECTION MAY DAMAGE YOUR EXCHANGE!
I.2.THE CABINET-TYPE DS200 SYSTEM
INSTALLATION
I.2.A. PREPARATION
The following requirements should be fulfilled prior to the installation of the exchange:
1- The DS200 exchange cabinet should be installed in places that are not exposed to direct
sunlight, that are not humid, but that are ventilated, well lit, with an environmental
temperature of 0-45
o
C.
2- It should not be exposed to the effects of dust, vibration, oil and water.
DS200 Installation Guide
DS200 Installation GuideDS200 Installation Guide
DS200 Installation Guide
V003. 25.06.2002
B-6
3- Devices that generate high frequency waves (such as welding machines, office equipment
such as computers and telex machines, air conditioners, TV sets) should not be in the
same room if possible, and they should be at least 3 meters away from the exchange,
otherwise.
4- The mains supply should be reserved for the exchange only. The power supply of the
system should be uninterrupted and, if possible, the system should be powered from a
well-grounded source from which no other device is powered.
!
FREQUENT POWER FAILURES MAY AFFECT NORMAL OPERATION OF
THE SYSTEM!
5- The spot where the exchange is to be mounted should be chosen considering its position
relative to the main distribution frame (MDF) and length of the cables. The installation
work and later maintenance work should also be considered, so that the covers can be
removed and replaced easily.
6- Since the installation connections will be made at the back of the cabinet, the position of
the cabinet should be arranged accordingly. The lighting at the back has been placed for
facilitating the work.
I.2.B. APPLICATION
1- Take the cabinet to a location as defined in the preparation step.
2- Lock the wheels by pressing the latches so that the exchange will not move.
3- Remove the front cover and the rack stopper screws that prevent the racks to slide.
Figure – 4
4- Remove the back and side covers, after unlocking them, by lifting them for approximately
10 cm in a manner so that their paint is not scratched.
5- While removing the covers, watch out for the grounding cables that are between the main
frame and the covers so that they do not break off. Detach the cables, together with their
tags, from the covers and keep them so as to make sure they would not get damaged
during the placement of the exchange into the cabinet.
6- Push the main rack and auxiliary racks one by one until the holes of the removed
stopping screws appear. Then replace the stopping screws so that the racks would not
slide along the slots.
DS200 Installation Guide
DS200 Installation GuideDS200 Installation Guide
DS200 Installation Guide
V003. 25.06.2002
B-7
Figure – 5
7- Open the cable panels from rear in order to facilitate the access.
8- In order to connect the main rack and the auxiliary racks, as well as to make inter-rack
ground connection: First, use the BPL200-FC and BPLSPS-FC connection cables that
come with the auxiliary rack. There are three such cables. Two BPL200-FC's (34-pin flat
cable) are used for connecting the BPL200 backplanes and BPLSPS-FC (5-wire cable) is
used for connecting BPL200-SPS backplanes. In order to connect the backplanes:
a) Primarily, attach one end of each BPL200-FC to the BPL200-MAIN backplane of the
main rack that has been placed to the bottom.
b) Extend the free ends of the BPL200-FC cables to the second rack through the cable
holes corresponding to the upper panel at the back of the first rack and the lower
panel at the back of the second rack. Attach the ends of those two cables to the
BPL200-AUX backplane connector. The cables should be parallel to each other.
Repeat the same procedure to connect the second rack to the third, later. See Figure
– 2.
DS200 Installation Guide
DS200 Installation GuideDS200 Installation Guide
DS200 Installation Guide
V003. 25.06.2002
B-8
9) Each rack comes as the power card-backplane connection has been made as factory
default. There are special cables that are used for this purpose. In case it is necessary,
those cables can be detached and the two cards can be separated or they can be
combined again, with those cables.
10) Then, you are supposed to make the power connection among the racks. In order to
connect the BPL200-SPS backplanes:
a) For the connection of the BPL200-SPS backplanes of the first and second racks, first
attach the BPLSPS-FC (5-wire cable) to the inter-rack SPS connector that is on the
BPL200-SPS backplane of the first rack.
b) Then, extend the free end of the cable through the holes of the metal plates that are
at the back of the first and the second racks and then attach it to the inter-rack SPS
connector that is on the BPL200-SPS backplane of the second rack. Repeat the same
procedure for the connection between the second and the third racks. See Figure – 2.
11) Attach the 230 VAC cable to the connector on the SPS200. First, make sure that the on/off
switches are off and the fuses are free from any defect. Then, attach the other end of the
cable to one of the plugs next to the mains switch that is at the lower front section of the
cabinet, by extending it through the back of the cabinet.
Two 2A T-type fuses that are necessary for 230 VAC are in the drawer-type compartment
next to the 230 VAC input.
!
VENTS OVER THE CABINET FANS MUST NOT BE COVERED BY ANY
MEANS DURING OPERATION OF THE SYSTEM. CERTAINLY CHECK
WHETHER THE FANS WORK PROPERLY, AT THE TEMPERATURES OVER
20°C.
CAUTION!
The rules that must be obeyed strictly while powering the system on and off are stated as a
special chapter at the end of this guide.
When the system consists of three or more racks, if it is powered on and off by the battery
switches, then those switches are damaged in time, due to the electric arcs. In order to
prevent this situation, a delayed main battery breaker (10 Ampere 250 V Main breaker) is
included in the system. Control of the electricity provided to the racks from the battery is
maintained by this breaker. Detailed information about this is in Chapter II of this guide.
I.2.C. INSTALLATION OF SYSTEMS WITH FOUR OR
MORE RACKS
Installation of the DS200 system in configurations with four, five or six racks is indeed a step
that follows the cabinet-type installation of the system.
Except the case of the four-rack cabinet that has been designed for the four-rack systems,
since installation cannot be realized with one cabinet for the systems with more than three
racks, first installation of two cabinets are realized so as to distribute the necessary quantity
of racks to those two cabinets.
The crucial point while installing the two cabinets is that they should be located side by side
and they should not be displaced during and after the installation.
!
THE CABLES PROVIDING THE CONNECTION BETWEEN THE CABINETS
MAY BE DAMAGED IN CASE OF A DISPLACEMENT.
DS200 Installation Guide
DS200 Installation GuideDS200 Installation Guide
DS200 Installation Guide
V003. 25.06.2002
B-9
The four-rack cabinet is used, if a system has four racks. In this case, since the entire racks
will fit into that cabinet, single-cabinet installation will suffice. The rack that will fit into the
uppermost rack slot of the cabinet will be of the main rack structure, too, like the first rack.
In two-cabinet systems, the first racks (lowermost) will be main rack and the others will be
auxiliary racks. However, there is CPU200 card only in a single cabinet’s main rack.
Likewise, there is DS200 CPUKON card in only a single main rack.
The first and the fourth racks are of the main rack structure and the connection between
these two racks is provided with some additional cards and cables. The list of those cards
and cables are below:
1) CC Extra card
2) C Master card
3) C Slave card
4) CC Enable card
5) Two BPL200-FC
6) Five PCM carrier cable
7) BPLSPS-FCX cable
In order to facilitate the connection of the two cabinets, you need to remove the SPS248
power units, UTIL200, DS200 CPUKON and CPU200 cards (redundant CPU200, too, if there is
any.)
I.2.C.1. CONNECTIONS IN THE MAIN RACK, TO WHICH THE
CPU200 CARD HAS BEEN ATTACHED:
I.2.C.1.1. ATTACHING THE CC EXTRA CARD ONTO THE CPU200 CARD:
Attach the card to the 20-pin connector with the code CON402, in a manner as it coincides
with the lower back corner of the CPU200 card that has been indicated with white lines,
through the female connector that is on the CC Extra card.
DS200 Installation Guide
DS200 Installation GuideDS200 Installation Guide
DS200 Installation Guide
V003. 25.06.2002
B-10
Figure – 6
If there will be a redundant CPU200 card in the system, then you should attach another CC
Extra card onto that redundant CPU200 card, too.
I.2.C.1.2. INTEGRATION OF THE C MASTER CARD TO THE MAIN RACK:
The C Master card must be attached to the main rack on which there is CPU200. Structure of
this card is suitable for attaching it to the plastic card slots of DS200 and its size is the same
as that of the CPU200 card. However, there is no 64-pin male connector at the back of the
card for the backplane connection. Instead, it is connected by a BPL200-FC to the inter-rack
connector that is at the lower section on the BPL200 backplane of the main rack, at the same
level with the CPU200.
If, on the other hand, there will not be a redundant CPU200 card in the DS200 system, then
the C Master card is attached to the slot that is reserved for the redundant CPU200 card.
Connect the cables before completely fixing the card in the slot.
The procedure for this:
1) Connect one end of the BPL200-FC to the inter-rack connector that is at the lower edge
of the BPL200-MAIN backplane of the main rack.
2) Connect the other end of the BPL200-FC to the similar connector that is on the C Master
card.
3) Connect the PCM carrier cables to the five RJ45 connectors that are on the C Master
card. The connection order of those cables is essentially important because those cables
will be connected to the second rack in the same order.
DS200 Installation Guide
DS200 Installation GuideDS200 Installation Guide
DS200 Installation Guide
V003. 25.06.2002
B-11
1- BPL200-FC 4- C Master card
2- PCM cable connectors (RJ45) 5- BPL200-Main
3- PCM carrier cables (The order is important.)
Figure – 7
After making the entire cable connections, push the card into the slot completely and make
sure the fixing latches that are on the plastic front cover have been fully fixed on the metal
casing.
If there will be redundant CPU200 card in the system, then you may install the C Master card
in the second general-purpose slot that is on the main rack. (Keep in mind that there must
be an extension card in the first general-purpose slot.) The cable connections are the same
as above.
Then, attach the DS200 CPUKON, UTIL200, CPU200 and redundant CPU200 (if there is any) of
the main rack to their corresponding slots, as will be described in later sections.
I.2.C.1.3. CONNECTING THE BPLSPS-FCX CABLE:
The BPLSPS-FCX cable is structurally the same as the BPLSPS-FC cable, yet it is longer.
Connect one end of that cable to the SPS connector that is at the lower section of the
BPLSPS backplane.
Attach the SPS248 Power Unit to its corresponding slot, as will be described in later
sections.
Finally, extend the free ends of the PCM carrier cables and the BPLSPS-FCX cable out of the
cabinet through the cable channels that are at the lower back of the cabinet. Then, insert
those cables into the second cabinet through the similar opening as that of the first one, and
extend them to the front part of the main rack.
DS200 Installation Guide
DS200 Installation GuideDS200 Installation Guide
DS200 Installation Guide
V003. 25.06.2002
B-12
I.2.C.2. CONNECTIONS ON THE FOURTH RACK:
The procedure is similar to that for the first rack.
I.2.C.2.1. INTEGRATION OF THE C SLAVE CARD TO THE MAIN RACK
Structure of the C Slave card is the same as that of the C Master card, which is on the first
rack . Besides, the connections are exactly the same.
Since there will not be any CPU200 and redundant CPU200 cards in the second cabinet, you
can place the C Slave card into the redundant CPU200 card slot that is on the main rack of
the second cabinet. You are supposed to connect the corresponding cables before
completely fixing the card in the slot.
The procedure for this:
1) Connect one end of the BPL200-FC to the inter-rack connector that is at the lower edge
of the BPL200-MAIN backplane of the main rack.
2) Connect the other end of the BPL200-FC to the similar connector that is on the C Slave
card.
3) Connect the PCM carrier cables to the five RJ45 connectors that are on the C Slave card.
The connection order of those cables is essentially important because those cables will
be connected to the C Slave card in the same order as they have been connected to the C
Master card in the first cabinet. (See Figure – 7)
!
INCORRECT CONNECTION ORDER OF THE PCM CARRIER CABLES
WOULD PRECLUDE THE OPERATION OF THE SYSTEM.
After making the entire cable connections, push the card into the slot completely and make
sure the fixing latches that are on the plastic front cover have been fully fixed on the metal
casing.
I.2.C.2.2. ATTACHING THE CC ENABLE CARD TO THE MAIN RACK:
The CC Enable card has a structure, which makes it possible to be attached to the BPL200-
MAIN backplane, thanks to the 64-pin male connector that is located at the back of it.
Attach the CC Enable card to the slot reserved for CPU200 on the main rack.
Then, you should attach the UTIL200 card of the main rack to its corresponding slot.
I.2.C.2.3. CONNECTING THE BPLSPS-FCX CABLE:
Connect free end of the BPLSPS-FCX cable, whose connection with the first cabinet has
already been provided, to the SPS connector that is at the lower section of the BPLSPS
backplane.
Attach the SPS248 Power Unit to its corresponding slot, as will be described in later
sections.
The operation of connecting two cabinets to each other will have been completed after
applying the steps above.
I.2.D. GROUNDING
Grounding is essential for protecting the DS200 Exchange from the effects of lightning or
other sources of high voltage that might affect over lines or peripheral devices.
DS200 Installation Guide
DS200 Installation GuideDS200 Installation Guide
DS200 Installation Guide
V003. 25.06.2002
B-13
Although special tools are required for measuring the sufficiency of grounding of the electric
installation of the building precisely, voltages between Neuter-Phase and Neuter-Ground
can be measured for getting a rough idea.
The Neuter-Phase voltage should be 180-260 VAC and the Neuter-Ground voltage should be
1-2 VAC. Those values must be consistent. Possible voltage leakage in grounding installation
may damage your exchange, just like all other devices that require grounding.
Water installation of the building can be used for grounding, provided that the pipes are of
metal and no insulation material has been used at junctions. Indeed, the most secure
grounding method is inserting a copper rod that is 1.5 cm in diameter with 1.5 m of length, or
inserting a copper plate with 1 m
2
of area to the ground and connecting it to the exchange
through a copper grounding cable. The cable should be fastened tightly to the rod or to the
plate and precautions should be taken against corrosion.
The cable coming from the grounding plate or grounding system must be connected to the
ground connection point of the exchange.
The DS200 Exchange and auxiliary racks are connected to each other tightly at the ground
connection points with the ground connection cable that comes with the shipped hardware.
A- DS200 Main Rack
B- DS200 Auxiliary rack
C- The grounding cable
D- The copper grounding plate or rod
Figure – 8
!
ADDITIONAL GROUNDING MUST BE PROVIDED, IF SOUNDNESS OF
THE GROUNDING OF THE ELECTRIC SYSTEM CANNOT BE GUARANTEED.
For providing the internal inter-rack grounding, first connect the grounding cable and the
grounding screw of the first rack, which is under the rack. Then, connect the grounding
screw that is under the first rack and the grounding screw of the second rack. Repeat the
same operation for the third rack. Afterwards, connect the cabinet grounding screw and the
external grounding system that has been installed for the cabinet, in order to provide
grounding for the entire cabinet.
For the two-cabinet structure, the grounding points of both cabinets must be the same.
DS200 Installation Guide
DS200 Installation GuideDS200 Installation Guide
DS200 Installation Guide
V003. 25.06.2002
B-14
I.2.E. BATTERY CONNECTION
!
SINCE ANY POWER FAILURE WILL DISRUPT THE EXCHANGE TO
PERFORM ITS NORMAL FUNCTIONS, YOU SHOULD CONNECT BATTERY TO
THE SYSTEM, IF THERE IS SUCH A POSSIBILITY.
!
THE BATTERY BREAKER MUST BE OFF DURING THE CONNECTION
PROCESS.
The system uses dry batteries. The batteries are placed at the bottom of the DS200 cabinet.
The compartment has been designed as large enough to include 38 Ah, dry-type batteries.
The dimensions of the cabinet bottom are about 60x78 cm. The capacity of that space is at
most12 batteries of 24 Ah (width: 17.5 cm, length: 16.6 cm, height: 12.5 cm) or of 38 Ah
(width: 16.5 cm, length: 19.7 cm, height: 17.0 cm). A three-rack system requires at least 4
batteries and there is room in the cabinet for 8 or 12 batteries, as needed.
Placing the batteries close to the back cover facilitates connecting them, as well as their
maintenance.
In order to connect the batteries:
First, connect the batteries that are in the compartment under the exchange serially to each
other. Then, connect the battery output through main breaker to the battery input of the main
rack, which is the lowermost rack. Attach the battery output to the connection clips on the
SPS200 (See the Technical Reference GuideFigure – 13), in the manner as the red end being
the “+” pole, and the black end being the “-“ pole. No battery connection is required for the
other SPS’s.
!
REVERSE BATTERY CONNECTION MAY DAMAGE YOUR EXCHANGE.
In order to complete the connection, press the spring latch of the clips and insert the
corresponding end of the battery cable into the hole in front, deep enough so that no naked
portion of the cable is left outside and then release the latch.
Since the batteries are connected to the 48 VDC-output of the SPS200 in parallel, completely
exhausted batteries may affect normal operation of the system. In that case, you should
charge them from an external source and then re-connect them to the system.
!
NORMAL OPERATION OF SYSTEMS WITH BATTERIES WOULD BE
AFFECTED BY FAILURES OF 230 VAC MAINS SUPPLY DURING NIGHT TIME
AND HOLIDAYS.
!
THE SYSTEM AUTOMATICALLY SHUTS DOWN IF THE BATTERY
VOLTAGE DROPS BELOW 34 VDC DURING PROLONGED POWER FAILURES AND
THE BATTERIES DO NOT SWITCH ON UNTIL THE BATTERY VOLTAGE LEVEL
EXCEEDS 46 VDC.
DS200 Installation Guide
DS200 Installation GuideDS200 Installation Guide
DS200 Installation Guide
V003. 25.06.2002
B-15
1. 230 VAC cable 4. BPL200-FC 7. Main grounding cable
2. BPLSPS-FC 5. Grounding screw
3. Grounding wire 6. Battery connection cables
Figure – 9
DS200 Installation Guide
DS200 Installation GuideDS200 Installation Guide
DS200 Installation Guide
V003. 25.06.2002
B-16
I.3. INST
I.3.A. SPS200 AC/DC POWER SUPPLY
The SPS200 AC/DC Power Supply, which includes the SPS200CR Power Card, has been
placed in a metal casing.
In order to fix SPS200 in the rack, place the metal rails properly, which are on the power
chassis, in the metal slots that are on rightmost side of the rack. (See the Technical
Reference GuideFigure–3). Then, push the SPS200 into the rack until it is firmly fixed to the
connector that is on the BPLSPS-Backplane, which is behind the power rack. Afterwards,
drive the SPS200 fixing screw that is in the upper front part of the rack. (See the Technical
Reference GuideFigure – 4).
In case you need to take the SPS200 out of rack, switch the battery and mains off,
respectively, by the ON/OFF switches on the SPS200 module. (See The Technical Reference
GuideFigure – 13). Detach the 230 V cable and battery connection cables (if there is any.)
Then, pull the power rack out after loosening the fixing screw that is on the upper front part
of the system rack.
I.3.B. SPS248 DC/DC POWER SUPPLY
SPS248 DC/DC Power Supply, which includes the SPS248CR Power Card and ring
transformer, has been mounted in a metal casing.
Attaching the SPS248 is very similar to that of the SPS200. It is attached to the slot on the
left-hand side of the SPS200. (See The Technical Reference GuideFigure – 4).
!
CAUTION! IN MULTI-RACK DS200 SYSTEMS, THE INTER-RACK
POWER CONNECTIONS MUST HAVE BEEN COMPLETED PRIOR TO PLACEMENT
OF SPS248 MODULES.
I.4. INTE
G
In this section, integration of the CPU200, DS200 CPUKON, UTIL200 UTILITY and Expansion
Modules to the system, together with CON2/CON3 Line Connection Cards, have been
explained.
I.4.A.CPU200, REDUNDANT CPU200 & DS200 CPUKON
CARDS
The CPU200 Central Processing Module has been fixed in the corresponding slot, as being
connected to the BPL200-MAIN backplane in the rack. (See The Technical Reference
GuideFigure – 11). The DS200 CPUKON Connection Card has been situated in the leftmost
slot of the main rack, as connected to the CPU200 card via the DS200 CPU-FC flat cable. The
DS200 CPUKON card has not been connected to the BPL200-MAIN backplane.
Install the CPU200, DS200 CPUKON and DS200 CPU-FC modules in the main rack as
described below:
1- Make sure that the UTIL200 module of the first rack has not been installed.
DS200 Installation Guide
DS200 Installation GuideDS200 Installation Guide
DS200 Installation Guide
V003. 25.06.2002
B-17
2- Connect the cables of the accessories to the connectors on the DS200 CPUKON. In order
to do this, extend the cables through the cable hole that is in the lower front rack and
attach them to the corresponding connectors on the DS200 CPUKON card. Then take the
free end of the cable out of the rack by extending it along underneath the rack through
the corresponding path within the cable channel that has been fixed on the back cover.
3- Install DS200 CPUKON card together with DS200 CPU-FC cable. First, attach the DS200
CPU-FC cable to the connector on the DS200 CPUKON card. Then, insert the DS200
CPUKON card so as its back corners fit the channel of the plastic card slot. Afterwards,
extend the free end of the DS200 CPU-FC cable along underneath the UTIL200 connector
on the backplane. As for the final step, when the card is completely placed, fix the DS200
CPUKON card by the fixing latches on the plastic card holder. See the figure below for
the correct usage of the plastic fixing latches.
Figure – 10
4- In order to install the CPU200 module, place the back corners of the module into the
channel of the plastic card slot and push it towards the rack. Before you set the module
completely, connect the DS200 CPU-FC cable to CPU200. Then, push the CPU200 module
inside, so as it tightly fits on its corresponding connector on the BPL200-Backplane.
When the module has been completely set, fix it by using fixing latches on the front cover
of the card. (See The Technical Reference GuideFigure – 24). See Figure – 10 for the
correct usage of the plastic fixing latches.
In case it is necessary to take CPU200 out of the rack, press the card fixing latches on the
front cover of CPU200 toward the tag on the holder and then pull the module cautiously until
DS200 CPU-FC appears. As for the final step, detach DS200 CPU-FC from CPU200 and then
take it out of the rack.
In case it is necessary to take DS200 CPUKON out of the rack, press the card fixing latches
on the front cover of the card toward the tag on the holder and then pull the module
cautiously until DS200 CPU-FC appears. Afterwards, detach DS200 CPU-FC from DS200
CPUKON and take it out of the rack.
If a redundant CPU200 is needed in the system, then install that card in the special slot at the
right-hand side of CPU200, which is reserved for it by following the same installation steps
as for CPU200. Its connection to DS200 CPUKON card is provided by DS200 CPU-FC.
!
DO NOT EVER REMOVE THE CPU200 CARD DURING THE OPERATION
OF THE EXCHANGE.
I.4.A.1. THE LAN ADAPTOR CARD:
DS200 Installation Guide
DS200 Installation GuideDS200 Installation Guide
DS200 Installation Guide
V003. 25.06.2002
B-18
The LAN Adaptor card has been designed to be attached to two female sockets, each with 5
pins, which are on the CPUKON card. There are pins on the solder side of the card
corresponding to the female sockets on CPUKON. While the RJ45 socket on the LAN Adaptor
card is facing out of the CPUKON card, attach the pins to the sockets. In addition to that, fix
the LAN Adaptor card to the CPUKON card through lead card holders.
In the figure below the LAN Adaptor card is illustrated as it has been attached onto CPUKON.
Figure – 11
After you have attached the LAN Adaptor card onto the DS200 CPUKON card, adjust the
jumpers on the CPUKON card according to the proper configuration. The table below shows
states of the jumpers:
Jumper State Selected output
1, 2 ON
3, 4 OFF
RS232
1, 2 OFF
3, 4 ON
LAN Adaptor
After the installation of the card is over, make the network connection through a one-to-one
cable with RJ45 connectors on both sides.
I.4.B. THE UTIL200 UTILITY MODULE
The UTIL200 Utility Module has been set on the related plastic card slot in the rack. (See The
Technical Reference GuideFigure – 11 and Figure – 12). The UTIL200 module is situated
between the CPU200 and DS200 CPUKON cards in the main rack. The DS200 CPU-FC cable
passes through the back of the UTIL200 module. On the other hand, it is installed in the
leftmost slot in the auxiliary racks.
In order to set UTIL200 into the rack, insert the module so as its back corners fits the plastic
card slot. Then, you should push it towards the inside of the rack so as the connector at the
back of it would fully fit its correspondent on BPL200-MAIN or BPL200-AUX (While you are
attaching the one that is on the main rack, be careful so that the DS200 CPU FC cable
remains behind the card.) When the module has been completely set, fix it by using latches
on the plastic card holder. (See Figure –10).
In case it is necessary to take UTIL200 out of the rack, press the card fixing latches on the
front cover of the card toward the sticker on the holder and then take the module out of the
rack.
I.4.B.1. INSTALLING THE CONFERENCE CHIP ON UTIL200
DS200 Installation Guide
DS200 Installation GuideDS200 Installation Guide
DS200 Installation Guide
V003. 25.06.2002
B-19
If the chip enabling conferencing with up to 16 participants, which is offered optionally is to
be utilized within the system, then insert this into the socket that is reserved for it on the
UTIL200 card of the first rack. While inserting the chip into the socket, make sure positioning
of the chip is correct.
In case there is an optional conference chip in the system, since this chip needs 32 PCM
channel in order to be functional, you must leave the last two general-purpose slots (The two
general-purpose slots on the rightmost edge of the rack) of the first rack vacant.
!
WHILE INSERTING THE CONFERENCE CHIP INTO THE UTIL200
CARD, LEAVE THE TWO GENERAL-PURPOSE SLOTS VACANT, WHICH ARE AT
THE RIGHTMOST SIDE ON THE BACKPLANE.
I.4.C. CON2/CON3 LINE CONNECTION CARDS
The CON2 and CON3 line connection cards constitute the connection among telephones,
lines and the extension and line cards of the system. High voltage protection circuits, the
line-busy LED, grounding pins and line connection connectors are all situated on the line
connection cards.
There are four female RJ45 connectors on the CON2 card. The MDF cable with 16 pairs,
which is called CBL-16, is for CON2. The male RJ45s at one end of the CBL-16 cable are
attached to the corresponding female connectors on CON2. Cable pairs at the other end of
the CBL-16 cable should be attached to the related sections on the MDF.
There are two female RJ45 connectors on the CON3 card. The MDF cable with 8 pairs, which
is called CBL-8, is for CON3. The male RJ45s at one end of the CBL-8 cable are attached to
the corresponding female connectors on CON3. Cable pairs at the other end of the CBL-8
cable should be attached to the related sections on the MDF.
The CON2 and CON3 cards are attached to the related expansion card on the side with circuit
elements. Two 20-pin connectors on the component side of the CON2 and CON3 cards are
attached to the corresponding connectors on the component side of the expansion card.
You should connect the cables CBL-8 and CBL-16 correctly in order to experience no
problems while removing the expansion modules from the exchange and replacing them
back. Proper connection of those cables is shown in Figure – 12.
It would be proper to extend the cables that go to the line connection connectors alongside
the expansion card connection connector (20-pin, white connector) in order to reduce the
space they occupy. Fixing line connection cables tightly to the expansion card by cable tie so
as their thin sides would touch the card, would provide for a trouble-free installation.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39

Karel DS200 Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI