Microprocessor Controller for
Energy Recovery Ventilators
Microprocessor Controller for ERV 1
®
Reference Guide for Microprocessor Controller
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with these instructions will result in voiding of the product warranty and may result in personal injury
and/or property damage.
ERV Technical Support
Call 1-800-240-0870
Program Features
The microprocessor controller offers control through
easy monitoring and adjustment of unit parameters by
way of a lighted graphical display and an integral push-
button keypad.
Pre-Programmed Operating Sequences
The controller has been pre-programmed to offer
multiple control sequences to provide preconditioned
air. Factory default settings allow for easy setup and
commissioning. The sequence parameters are fully
adjustable. Refer to the Sequence of Operation for
details.
BMS Communication
The user can remotely adjust setpoints, view unit status
points and alarms. The microprocessor controller is
capable of communicating over several protocols:
BACnet® MSTP Modbus RTU
BACnet® IP Modbus IP
Reference Points List for a complete list of BMS points.
Internal Time Clock (Schedule)
The controller has an internal programmable time clock,
allowing the user to set occupancy schedules for each
day of the week.
Introduction
Alarm Management
The microprocessor controller will monitor the unit’s
status for alarm conditions. Upon detecting an alarm,
the controller will record the alarm description, time,
date, and input/output status points for user review. A
digital output is reserved for remote alarm indication.
Alarms are also communicated via BMS (if equipped).
Occupancy Modes
The microprocessor controller offers three modes of
determining occupancy: a digital input, the internal time
clock or the BMS.
Remote Display (if equipped)
A touch pad display allows for remote monitoring and
adjustment of parameters, allowing ease of control
access without going outdoors.
WARNING
Electrical shock hazard. Can cause personal injury or
equipment damage. Service must be performed only
by personnel that are knowledgeable in the operation
of the equipment being controlled.
WARNING
Mechanical high static protection cutoffs must
be installed by others to protect the system and
equipment from over-pressurization when using
factory provided control sensors. The manufacturer
does not assume responsibility for this.
ERV v3.10
Version Date: 3/1/21
Microprocessor Controller for ERV2
®
Sequence of Operation
General Operation . . . . . . . . . . . . . . . . . 3
Supply Fan VFD Sequence . . . . . . . . . . . . . 3
Exhaust Fan VFD Sequence . . . . . . . . . . . . 3
Economizer . . . . . . . . . . . . . . . . . . . . . 4
Frost Control . . . . . . . . . . . . . . . . . . . . 4
Alarms . . . . . . . . . . . . . . . . . . . . . . . 4
Setpoint Control . . . . . . . . . . . . . . . . . . 5
Heating . . . . . . . . . . . . . . . . . . . . . . . 5
Cooling . . . . . . . . . . . . . . . . . . . . . . . 5
Controller Overview
Controller . . . . . . . . . . . . . . . . . . . . . . 6
c.pCOe Expansion Board . . . . . . . . . . . . . 6
Display Use . . . . . . . . . . . . . . . . . . . . . 7
Example of Parameter Adjustment . . . . . . . . 7
Web User Interface. . . . . . . . . . . . . . . . . 8
Main Menu Navigation . . . . . . . . . . . . . . . 9
Unit Status Overview. . . . . . . . . . . . . . . .10
Menus
Unit Enable . . . . . . . . . . . . . . . . . . . . 12
Control Variables
Temperature Control . . . . . . . . . . . . . . 12
Energy Recovery . . . . . . . . . . . . . . . . 14
Fan Control
Supply Fans Control . . . . . . . . . . . . . 15
Exhaust Fans Control. . . . . . . . . . . . .16
Advanced
Manual Overrides . . . . . . . . . . . . . . .17
Advanced Setpoints . . . . . . . . . . . . . 18
Network Settings . . . . . . . . . . . . . . . 20
Backup/Restore . . . . . . . . . . . . . . . 21
I/O Configuration . . . . . . . . . . . . . . .23
Unit Configuration . . . . . . . . . . . . . .23
Alarms . . . . . . . . . . . . . . . . . . . . . . 24
Appendix
Remote Display . . . . . . . . . . . . . . . . . . 25
Carel
®
NTC Temp Sensor Chart . . . . . . . . 25
I/O Expansion Board Quick Start . . . . . . . . .26
Points List . . . . . . . . . . . . . . . . . . . . . 27
Our Commitment . . . . . . . . . . . . . Backcover
Table of Contents
Microprocessor Controller for ERV 3
®
Sequence of Operation
General Operation
UNIT START COMMAND: The microprocessor
controller requires a digital input to enable operation.
The unit can then be commanded on or off by this
digital input, keypad, the BMS or internal time clock.
When a start command becomes active the following
steps occur:
Energy Wheel
Factory mounted and wired outdoor air damper
actuator is powered.
Exhaust fan starts after a (adj.) delay.
Supply fan and energy wheel start after a (adj.) delay.
Energy Core
Factory mounted and wired outdoor air damper
actuator is powered.
Exhaust fan starts after a (adj.) delay.
Supply fan starts after a (adj.) delay.
UNIT STOP COMMAND:
The unit becomes disabled due to the following:
The unit was disabled from the controller’s Unit
Enable screen.
The unit was disabled from the BMS.
The shutdown input is in the shutdown position.
A shutdown alarm was activated.
When disabled the following actions occur:
Energy Wheel
Supply fan, exhaust fan, and energy wheel
de-energized.
Outdoor air damper actuator is spring return closed.
Energy Core
Supply fan and exhaust fan de-energized.
Outdoor air damper actuator is spring return closed.
Supply Fan VFD Sequence
The factory installed VFD is wired to the controller.
Supply fan speed needs to be set during test and
balance of the unit.
Constant Volume: The supply blower is provided
with a factory mounted and wired VFD and is
intended to operate at a constant speed (adjustable
set point in controller) during operation. This speed
needs to be set during the test and balance of the
unit.
Space/Duct CO2 Sensor: The controller will
modulate the supply fan based upon a comparison
of the CO2 setpoint to the actual CO2 levels reported
from the sensor.
Duct Static Pressure Sensor: The controller will
modulate the supply fan based upon a comparison
of the duct static pressure setpoint to the actual duct
static pressure level reported from the sensor.
Building Static Pressure Sensor: The controller will
modulate the supply fan based upon a comparison
of the building static pressure setpoint to the actual
building static pressure level reported from the
sensor.
Network Control: The controller will modulate the
supply fan based upon a command from the Building
Management System (BMS). This sequence must be
field configured.
Volatile Organic Compound (VOC) Sensor: The
controller will modulate the supply fan based upon
a signal from the VOC sensor. The controller will
modulate the supply fan based upon a comparison
of the VOC set point (adj.) to the actual VOC levels
reported from the sensor.
0-10 VDC Signal by Others: The supply blower
is modulated based upon a 0-10 VDC signal (field
provided) wire directly into the microprocessor.
Exhaust Fan VFD Sequence
The factory installed VFD is wired to the controller.
Exhaust fan speed needs to be set during test and
balance of the unit.
Constant Volume: The exhaust blower is provided
with a factory mounted and wired VFD and is
intended to operate at a constant speed (adjustable
set point in controller) during operation. This speed
needs to be set during the test and balance of the
unit.
Building Pressure Sensor: The controller will
modulate the exhaust fan based upon a comparison
of the building static pressure setpoint to the actual
building static pressure level reported from the
sensor.
Supply Fan Tracking: The controller will
proportionally modulate the exhaust fan based upon
the supply fan speed.
Network Control: The controller will modulate
the exhaust fan based upon a command from the
Building Management System (BMS). This sequence
must be field configured.
0-10 VDC Signal by Others: The exhaust blower
is modulated based upon a 0-10 VDC signal (field
provided) wire directly into the microprocessor.
Microprocessor Controller for ERV4
®
Sequence of Operation
Economizer (optional):
Energy Wheel
If the unit is equipped with an energy recovery wheel,
the economizer will modulate/stop the energy wheel to
achieve free cooling.
Stop Wheel: When economizer mode is enabled
and there is a signal for cooling, the wheel will
stop rotating to allow free cooling. The sequence
allows the wheel to rotate for a short period of time
exposing a new section to the air stream.
Modulate Wheel: When economizer mode is
enabled and there is a signal for cooling, the
controller modulates wheel speed to maintain the
supply temperature setpoint.
VFD Signal by Others: When the application
requires cooling and the outdoor air conditions
are suitable for free cooling, a 0-10 VDC signal
is provided by others to the energy wheel VFD to
control the speed of rotation.
BMS Control: When the application requires cooling
and the outdoor air conditions are suitable for free
cooling, the energy wheel is modulated based upon
a command from the Building Management System
(BMS). This sequence must be field configured.
OA Temp Setpoint: The economizer will be locked out
when the outdoor air is <50°F (adj.) or >65°F (adj.).
OA/EA Temp. Differential: The economizer will be
locked out when the outdoor air temperature is greater
than the return air temperature.
OA Enthalpy Setpoint: The economizer will be locked
out when the outdoor air is <50° F (adj.) or >75° F. (adj.)
or has an enthalpy >23.0 btu/lb. (adj.)
Energy Core
If the unit is equipped with an energy recovery core and
bypass damper, the economizer will cycle into a bypass
condition, allowing cool air to flow past the energy
recovery core rather than passing through it.
OA Temp Setpoint: The economizer will be locked out
when the outdoor air is <50°F (adj.) or >65°F (adj.).
OA Enthalpy Setpoint: The economizer will be locked
out when the outdoor air is <50° F (adj.) or >75° F. (adj.)
or has an enthalpy >23.0 btu/lb. (adj.)
Frost Control (optional):
Energy Wheel
The microprocessor controller will activate the frost
control method when the outdoor air temperature
is less than the defrost setpoint (5°F) and the wheel
pressure switch is closed due to a high wheel pressure
drop. Once the pressure drop decreases below the
pressure switch point or the outdoor air temperature
increases, the unit will resume normal operation.
Electric Preheater: When frosting is occurring, the
preheater is energized to defrost the wheel.
Modulate Wheel: When frosting is occurring, the
wheel slows to allow defrosting to occur.
Timed Exhaust: When frosting is occurring, the
supply fan is cycled off along with the tempering for
a defrost cycle time (5 minutes). The exhaust fan
will continue to run allowing the warm exhaust air
to defrost the wheel. After the defrost cycle time,
the supply fan and tempering are re-energized to
continue normal operation. The controller will not
allow another defrost cycle for a minimum normal
operating cycle time (30 minutes).
Energy Core
The microprocessor controller will activate the frost
control method when the exhaust air temperature
is less than 3F. Once the exhaust air temperature
increases above 36ºF, the unit will resume normal
operation.
Electric Preheater: When frosting is occurring, the
preheater is energized to prevent/control frost on
the core. The preheater is enabled for a minimum of
10 minutes. After 10 minutes, the unit will resume
normal operation once the exhaust air temperature
increases above 36ºF.
Timed Exhaust: When frosting is occurring, the
supply fan is cycled for a defrost cycle time (5
minutes). The exhaust fan will continue to run
allowing the warm exhaust air to defrost the core.
After the defrost cycle time, the supply fan is
re-energized to continue normal operation. The
controller will not allow another defrost cycle for a
minimum normal operating cycle time (30 minutes).
Alarms
The microprocessor controller includes a digital output
for remote indication of an alarm condition, which
connects via the J12 port. Possible alarms include:
Dirty Filter Alarm: If the outside air or return air
filter differential pressure rises above the differential
pressure switch setpoint, the microprocessor
controller will activate an alarm.
Supply and Exhaust Air Proving Alarm:
Microprocessor controller monitors proving switch on
each blower and displays an alarm in case of blower
failure.
Sensor Alarm: Microprocessor controller will send
an alarm if a failed sensor is detected (temperature,
pressure, relative humidity).
Other Alarms: High Wheel Pressure
Microprocessor Controller for ERV 5
®
Set Point Control (Occupied)
Supply air temperature setpoint can be configured
as OA reset or be set as a constant static setpoint. If
equipped with BMS communications, the user can also
directly command the supply temperature setpoint.
Outside Air Temperature Reset Function: The
controller will default to supply temperature reset
based on outdoor air temperature. The controller will
monitor the OA temperature and reset the supply
temperature setpoint based upon the outdoor air
reset function.
Set Point Control (Unoccupied)
When equipped with an unoccupied recirculation
damper and optional space temperature and/or
humidity sensors, the unit will cycle on to maintain the
unoccupied space set points.
Unoccupied Heating: If equipped with heating,
the unit is enabled when the space temperature is
less than the unoccupied heating set point minus
differential (60°F). The supply air temperature set
point will be set to the supply max reset limit (90°F).
The unit cycles off when the space temperature
reaches the unoccupied heating set point.
Unoccupied Cooling: If equipped with cooling, the
unit is enabled when the space temperature is greater
than the unoccupied cooling set point plus differential
(80°F+5°F). The supply air temperature set point will
be set to the supply min reset limit (55°F). The unit
cycles off when the space temperature reaches the
unoccupied cooling set point.
Unoccupied Dehumidification: If equipped with
cooling, the unit is enabled when the space relative
humidity exceeds the unoccupied space relative
humidity set point plus differential (50%+5%). The
supply air temperature set point will be set to the
equivalent occupied supply set point.
Morning Warm-Up/Cool Down: At the request to
occupy the space, the unit will run using the warm-up
or cool down sequence until the occupied set point
is achieved. The heating or cooling mode must not
be locked out and the space temperature is below
or above set point by the unoccupied hysteresis
(5°F, adj). This optional sequence requires a space
temperature sensor and is field-enabled.
The following steps occur during a morning warm-up/
cool down:
- The dampers would be in full recirc if the damper
if the damper actuators are not powered (adj)
during occupied mode. Otherwise the following is
true:
Outside air damper is open to minimum OAD
position.
Recirculation air damper is open at 100% minus
OAD position.
- Supply Fan is ON at 100%.
- Exhaust fan is OFF.
- In heating, controls to maintain the maximum
supply set point (90ºF).
- In cooling, controls to the minimum supply set
point (50ºF).
- Reheat off.
- Energy recovery wheel off.
Heating
The heating is controlled to maintain a supply
temperature setpoint. The heating will be locked out
when the outside air temperature is above the heating
lockout (80 deg F adj.).
Hot Water Coil: Microprocessor controller will
modulate a hot water valve (provided by others) to
maintain the supply temperature setpoint. Coil freeze
protection must be provided by others in the field!
SCR Electric Heater: Microprocessor controller will
modulate an SCR electric heater (provided by others)
to maintain the supply temperature setpoint.
Cooling
The cooling is controlled to maintain the supply
temperature setpoint. The mechanical cooling will be
locked out when the outside air temperature is below
the cooling lockout (55 deg F).
Chilled Water: Microprocessor controller will
modulate a chilled water valve (provided by others) to
maintain a supply temperature setpoint. Coil freeze
protection must be provided by others in the field!
Split DX: Microprocessor controller will enable/stage
a split DX coil (provided by others) to maintain a
supply temperature setpoint.
Sequence of Operation
Microprocessor Controller for ERV6
®
Controller Overview
Supply Fan Control Input Signal
24 VAC Power
Supply Fan Enable
24 VAC Power
Damper Enable
Alarm Dry Contact
Wheel Frost Mode
Exhaust Fan Enable
Wheel Enable/
Core Econ Damper
Exhaust Fan Control Input Signal
Supply Discharge Temp Sensor
Unit On/Off Input
Outdoor Air Temp Sensor
Modulating Wheel Control Output Signal
Dirty Filter Input
Frost Input (Exhaust temp/Wheel Pressure Input)
Wheel Rotation Alarm
Economizer Enable Input
24 VAC Power
Supply Fan Proving
Exhaust Fan Proving
Supply Fan Control Output
Exhaust Fan Control Output
c.pCOe - Expansion Board Overview, Medium Controller Arrangement
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
19.2 K
9.6 K
38.4 K
57.6 K
CAREL
Modbus
ON
OFF
Address Ext. ProtBaud
Address Ext Baud Prot
24 VAC Power
Return Air Inlet Temp Sensor/
Exhaust Air Discharge Temp Sensor
Outdoor Air Humidity Sensor*
Return Air Humidity Sensor
Heating Option (0-10VDC)
Heating Enable
Cooling Option (0-10VDC)
Cooling Output
Stage 1
Cooling Output
Stage 2
The expansion board is an I/O module than can be used to monitor additional statuses or provide commands from
medium board controller.
*Outdoor Air Humidity Sensor can float to open inputs on the main controller U1, U2, U6 or
U10. If main board inputs are full OAH will land on U7 on the expansion board.
Microprocessor Controller for ERV 7
®
The microprocessor controller is located in the unit control center. The face of the controller has six buttons,
allowing the user to view unit conditions and alter parameters. The microprocessor controller is pre-programmed
with easy to use menus. A remote display is also available, which connects via the J3 Disp port. A six wire patch
cable is needed.
Display Use
Keypad Description
Button Description Functions
Main Menu Press to go directly to the Main Menu from any screen.
From the Main Menu, navigate to the following screens:
• Unit Enable
• Unit Status
• Ctrl Variables
• Alarm Menu
Alarm The Alarm button flashes when there is an active alarm.
Press to view active alarms.
Press twice to go to the alarms reset screen.
Escape Press from the Main Menu to view the Unit Status screen.
Press to go back one menu level.
Press when editing a variable to cancel editing.
Up Press to navigate through the menus/screens.
Press after entering a variable to increase a current value.
Enter Press to enter a highlighted menu or screen item.
Press to enter a writable variable and press again to confirm the new variable value.
Down Press to navigate menus/screens.
Press after entering a variable to decrease the current value.
Virtual keypad/display on web interface only.
These two buttons on the virtual keypad/display are used to simulate two-button actions on the handheld
keypad/display.
To simulate pressing two buttons simultaneously:
1. Click on 2-Button Click.
2. Then, sequentially click on two keypad buttons (Main, Alarm, Escape, Up, Enter, Down).
To simulate pressing and holding two buttons simultaneously:
1. Click on 2-Button Hold.
2. Then, sequentially click on two keypad buttons (Main, Alarm, Escape, Up, Enter, Down).
Example of Parameter Adjustment
Supply air low limit
Alarm when supply is
below: 32.0º F
Alarm delay: 300s
Once the cursor has reached the desired parameter, press the
buttons to
adjust the value.
The cursor always begins in the upper left corner of the display and will be
blinking. Press the
button to move the cursor down for parameter adjustment.
Supply air low limit
Alarm when supply is
below: 35.0º F
Alarm delay: 300s
When satisfied with the adjustment, press the button to save the parameter.
When finished, make certain the cursor is in the upper left corner. If the cursor is
not in the upper left corner, the changes will not be saved. The cursor must be in
the upper left corner to enable screen advancement.
Supply air low limit
Alarm when supply is
below: 32.0º F
Alarm delay: 300s
Microprocessor Controller for ERV8
®
Web User Interface
The Web User Interface allows access to the unit controller through the building network. Reference Ctrl Variables/
Advanced/Network Settings to set the IP network protocol. Once proper communication is established, the user
can click on the follow tabs:
Overview – Includes a functioning unit graphic, monitoring points, and active setpoint adjustment.
Alarm – Shows current and cleared alarms.
Unit Display – Mimics the unit controller display. Allows the user full access to the controller without physically
being at the unit.
Trending – User can view past and present controller points.
Information – Provides manufacturer support information as well as IOM resources.
Service – User must be logged with service access criteria (1000). Once proper login is established, the user can
view configured input/output points associated with the unit controller
Microprocessor Controller for ERV 9
®
Main Menu Navigation
Unit Enable
Main Status Ctrl Variables Alarm Menu
Unit Status
Temp Control
Active Alarms
Input Output Status
Energy Recovery
Reset Alarms
Note:
Additional status screens
are displayed depending
on unit configuration.
Screens may include,
but are not limited
to: Occupancy, Fans,
Economizer, Frost, CO
2
,
Energy Recovery, Space
Static, Duct Static and
Expansion IO.
Fan Control Supply Fan Control
Alarm History
Exhaust Fan Control
Clear History
Damper Control
Export History
Occupancy
Advanced
Note:
The Advanced
menu is read-
only. The service
password is
required to change
these settings.
Reference the
Advanced menu
section for more
information.
*Consult
factory for more
information.
Login
Manual Overrides
Adv. Setpoints*
Network Settings
Backup/Restore
IO Status/Offset*
IO Config
Unit Config
Unit Settings*
Service Info*
Alarm
Management
Shutdown
Alarms
General
Alarms
Microprocessor Controller for ERV10
®
The microprocessor controller will revert to a default main menu loop. This loop includes several screens to view the
operating conditions of the unit. Scroll through the menu screens by using the
buttons.
Unit Status Overview
Unit Status Screen Symbols
Symbol Indicates
Supply air fan status.
Rotation indicates airflow; static blades indicate no airflow.
Economizing
Defrost
The iniTial menu screen displays The job name, uniT Tag, uniT sTaTus, ouTside
air condiTions, space condiTions and seTpoinTs.
Possible modes include:
• Off/Standby
• Unoccupied Start
• Dampers Open
• Fan Start Delay
• Fans Starting
• Startup Delay
• System On
• System Disabled
• Remote Off
• Shutdown Alarm
• Economizing
• Defrost Active
• Overrides Active
• Expansion Offline
inpuT ouTpuT sTaTus
Displays real time conditions from sensors located in the unit and building space
if equipped with space mounted sensors. Controller output conditions can also
be viewed from this screen. To view the desired input/output point, the user must
select the desired channel. Reference the Controller Overview section in this IOM
for individual point locations.
occupancy sTaTus
Displays current status of occupancy and the configured occupancy control
method and time zone.
supply Fan sTaTus
This screen displays the fan enable command, fan proving status, and the supply
fan ramp being sent from the controller to the VFD. The minimum and maximum
speeds are set in the VFD (Reference unit Installation and Operation Manual for
VFD programming). The controller can modulate the fan between the min and
max speeds via an analog output.
exhausT Fan sTaTus
This screen displays the fan enable command, fan proving status, and the
exhaust fan ramp being sent from the controller to the VFD. The minimum and
maximum speeds are set in the VFD (Reference unit Installation and Operation
Manual for VFD programming). The controller can modulate the fan between the
min and max speeds via an analog output.
heaTing ramp
This screen displays the active set point, supply air temperature, status of the
heating control ramp, and heating ramp being sent from the controller.
Microprocessor Controller for ERV 11
®
economizer ramp
The economizer ramp screen will be active if the unit is configured for an
economizer control method. This screen displays the economizer setpoint,
economizer ramp status, and economizer control mode of control. Economizer
control mode options include outside dry bulb, or outside enthalpy.
CO
2
ramp ouTpuT
The CO
2
Ramp Output screen will be active if the unit is configured for CO
2
control. This screen displays the CO
2
setpoint, CO
2
level from the space, and the
status of the control ramp.
energy recovery Wheel sTaTus
This screen only appears if the unit is equipped with an energy recovery wheel.
This screen provides overall status of the energy recovery wheel.
Unit Status Overview
deFrosT ramp ouTpuT
This screen only appears if the unit has an energy recovery wheel and a frost
control method was provided on the unit.
Upon sensing a high differential pressure across the energy wheel, the unit will
go into defrost if the outside air temperature is below the defrost temperature
setpoint.
supply space sTaTic
This screen displays status points if the unit is configured for space static
pressure control. Status points include controller output ramp, static pressure
in the space, and the space static pressure setpoint. Similar status screen will
appear for the exhaust fan if the unit is configured for exhaust fan space static
control.
supply/reTurn ducT sTaTic
This screen displays status points if the unit is configured for duct static pressure
control. Status points include controller output ramp, static pressure in the duct,
and the duct static pressure setpoint. Similar status screen will appear for the
exhaust fan if the unit is configured for exhaust fan duct static control.
voc ramp ouTpuT
The VOC Ramp Output screen will be active if the unit is configured for VOC
control. The screen displays the VOC setpoint, VOC level from the space and the
status of the control ramp.
Microprocessor Controller for ERV12
®
Menu
Unit Enable
The controller is equipped with several menus to help guide users with altering program parameters. The following
menus can be accessed by pressing the button. To enter the desired menu, press the button.
The Unit Enable menu allows the user to enable and disable the unit through the
controller. Reference sequence of operation for additional unit starts/stop details.
The unit ships from the factory in a disabled state. To allow the unit to operate,
the controller must receive a run command from digital input U4. Jumper unit
terminals R - G to allow the unit to operate.
Change to (Enabled/Disabled): Enables user to manually turn unit on/off via
display. Unit terminal G must be connected to ground to enable the unit.
Control Variables
The Controls Variables menu allows the user to view and adjust unit control
parameters.
Control Variables
Temperature Control
The Temperature Control menu allows the user to
ouTside reseT
This screen will be active if the controller is configured for outside air reset. The
heating and cooling devices modulate to maintain the supply air temperature
setpoint as determined by the outside reset circulation.
mode sWiTch display
This screen displays the time required before switching between heating and
cooling mode.
sTarTup display
This screen displays the delay time after the fans have started and tempering
begins.
economizer
This screen displays the economizer lockout temperature. Economizer will be
locked out below the economizer lockout temperature (40°F).
Microprocessor Controller for ERV 13
®
Unit Status Overview
cooling lockouT
This screen displays the cooling lockout temperature. Cooling will be disabled
when outside air is below the cooling lockout temperature (55ºF).
heaTing lockouT
This screen displays the heating lockout temperature. Heating will be disabled
when outside air is above the lockout temperature (80ºF).
economizer conTrol variables.
The economizer screen appears when economizer function is enabled.
The outside air damper will modulate between the min and max position to
maintain the supply temperature set point.
The user can select the economizer control method from the following options:
Outside Dry Bulb – Economizing is allowed when the outside dry bulb is less
than the economizer temperature enable set point.
Outside Enthalpy - Economizing is allowed when outside enthalpy is less than
the economizer enthalpy set point
economizer seTTings
There is a built-in hysteresis that disables economizer above the economizer set
point.
(Example: If economizer outside dry bulb = 65°F, economizer operation is
disabled above 67°F).
Microprocessor Controller for ERV14
®
This screen displays The economizer seTTings ouTside enThalpy
Outside Enthalpy - Economizing is allowed when the outside enthalpy is less than
the economizer enthalpy setpoint.
This screen displays The economizer seTTings hysTeresis
There is a built-in hysteresis that disables economizer above the economizer
setpoint.
(Example: If Economizer Outside Dry Bulb = 65°F, economizer operation is
disabled above 67°F).
This screen displays The economizer seTTings
Outside Dry Bulb - Economizing is allowed when the outdoor dry bulb is less than
the economizer temperature enable setpoint.
This screen displays The TemperaTure aT Which The uniT Will enable FrosT
conTrol mode iF necessary (FacTory deFaulT=F)
This screen only appears if the unit has an energy recovery wheel and a frost
control method was provided with the unit.
Upon sensing a high differential pressure across the energy wheel, the unit
will enter defrost mode if the outside air temperature is below this temperature
setting. Max Active Time and Min Off Time will be available if the frost control
method was provided as timed exhaust or cycle wheel.
This screen displays The heaT Wheel jog FuncTion
This screen display the energy recovery wheel jog function.
This screen only appears if the unit has an energy recovery wheel and stop wheel
economizer method for control.
Momentarily enables the wheel in order to expose a new section to the airstream.
Control Variables
Energy Recovery
The Energy Recovery menu allows the user to adjust energy recovery wheel
sequence setpoints.
This screen displays The heaT Wheel minimum speed
This screen displays the minimum energy wheel speed.
This screen only appears if the unit has an energy recovery wheel with a VFD.
This screen displays The economizer mode
This screen only appears if economizer functionality was provided.
The user can select the economizer control method from the following options:
- Outside Dry Bulb
- Outside Enthalpy
Menu
Microprocessor Controller for ERV 15
®
This screen displays The supply Fan delay.
The supply fan delay will begin once the damper sequence is complete. This delay
can be used to offset starting times between the supply fan and exhaust fan.
This screen displays minimum and maximum supply Fan speed percenTages.
The speed set point is the proportional percentage of the analog output from the
controller to the VFD.
50% Speed = Min speed
100% Speed = Max speed
Possible Setpoint Sources:
Local – The fan speed will be constant; set from screen (e.g. 100%).
BMS – The BMS can directly control the fan speed (requires BMS communication
option).
Duct Pressure – Fan speed is determined by duct pressure control loop.
Space Pressure – Fan speed is determined by building pressure control loop.
CO
2
– Fan speed is determined by CO
2
control loop.
VOC Monitor - Fan speed is determined by VOC control loop.
0-10 VDC Signal by Others - Fan speed is determined by others through a
0-10 VDC signal.
Control Variables
Fan Control
Supply Fan Control
The Supply Fan Control menu allows the user to adjust exhaust control
setpoints
Menu
Microprocessor Controller for ERV16
®
This screen displays minimum and maximum exhausT Fan speed
percenTages.
The speed set point is the proportional percentage of the analog output from the
controller to the VFD.
50% Speed = Min speed
100% Speed = Max speed
Possible Setpoint Sources:
Local The fan speed will be constant; set from screen (e.g. 100%).
BMSThe BMS can directly control the fan speed (requires BMS communication
option).
Space PressureFan speed is determined by building pressure control loop.
Supply Fan Tracking with OffsetThe exhaust fan will track the supply fan,
between a minimum and maximum position. An offset can be added to achieve
the proper balance.
Duct PressureFan speed is determined by duct pressure control loop.
0-10 VDC Signal by Others - Fan speed is determined by others through a
0-10 VDC signal.
Control Variables
Fan Control
Exhaust Fan Control
The Exhaust Fan Control menu allows the user to adjust supply control
setpoints.
Menu
This screen displays The exhausT Fan delay
The exhaust fan will begin once the damper sequence is complete. This delay can
be used to offset starting times between the supply and exhaust fan.
Microprocessor Controller for ERV 17
®
manual override mode
The Manual Overrides menu is for start-up, commissioning, and troubleshooting.
This menu allows the user to override the control loops and specific inputs and
outputs.
To access the Manual Overrides submenus, enter the service password (1000).
Manual overrides must be enabled at this screen to allow the user to override
control loops. Override options must be changed from Auto to Manual for manual
control.
This screen alloWs The user To override The uniT on or oFF.
When manual override is set to enable, use the arrow buttons to turn the unit on
or off.
This screen alloWs The user To override occupancy conTrol.
When manual override is set to enable, use the arrow buttons to change
occupancy control.
This screen alloWs The user To override The supply Fan vFd speed
(iFequipped).
The speed is the proportional percentage of the analog output from the controller
to the VFD.
0% Speed = Min speed (determined by VFD)
100% Speed = Max speed (determined by VFD)
(Reference unit Installation and Operation Manual for VFD programming).
Control Variables
Advanced
Manual Overrides
The Manual Overrides menus are for start-up, commissioning, and
troubleshooting.
The Advanced menu allows the user to access several submenus regarding
controller information, controller overrides, network settings, I/O configuration,
and unit configuration. Submenu options are read only and will require the user
to input proper login criteria. The service password (1000) is required to change
service access menus. Consult factory for factory level access.
Control Variables
Advanced
Menu
This screen alloWs The user To override exhausT Fan vFd speed
(iFequipped).
This screen only appears if the unit is equipped with a exhaust fan VFD controlled
by the microprocessor.
The speed is the proportional percentage of the analog output from the controller
to the VFD.
0% Speed = Min speed (determined by VFD)
100% Speed = Max speed (determined by VFD)
(Reference unit Installation and Operation Manual for VFD programming).
Microprocessor Controller for ERV18
®
The Advanced Setpoints Menus allows the user to make modifications to
lockouts and PID loops. Contact factory before adjusting.
Control Variables
Advanced
Adv. Setpoints
This screen alloWs The user To override The economizer conTrol
operaTion.
This screen allows the user to override the economizer control, if equipped.
This screen alloWs The user To override The energy recovery deFrosT
operaTion.
This screen only appears if modulating wheel frost control is equipped. When the
defrost control ramp is in manual mode, use the arrow buttons to vary the defrost
output.
0% = Maximum Wheel Speed
100% = Minimum Wheel Speed
Menu
energy recovery ramp
This screen only appears with an energy wheel VFD. When energy recovery ramp
is in manual mode, use the arrow buttons to vary the energy recovery ramp.
economizer
This screen only appears if an economizer option was provided with the unit. The
controller utilizes a PI loop control for economizer. This allows for less sporadic
changes in supply temperature, resulting in a smooth reaction to changing
conditions.
economizer Fallback
This screen only appears if an economizer was selected. The controller will fall
back to the next available mode if sensors become invalid. This screen allows this
functionality to be disabled.
deFrosT
This screen only appears if a defrost strategy based on exhaust air temperature
was selected. The controller will wait 30 seconds after the exhaust air
temperature drops below the frost threshold to enable defrost. This delay reduces
cycling in and out of defrost.
Timed exhausT deFosT
The screen only appears if a timed exhaust defrost strategy is selected. This
screen allows the minimum exhaust fan speed to be increased during defrost to
ensure proper airflow to defrost the energy recovery device.
Microprocessor Controller for ERV 19
®
Menu
supply ducT sTaTic
This screen only appears if the unit is controlling to supply duct static. The
controller utilizes a PI loop control for the supply duct static control. This allows
for less sporadic changes in the supply fan speed, resulting in a smooth reaction
to changing conditions.
login duraTion
This screen allows the user to change the login duration which controls how long
the user is logged into the service and factory menus.
uniT oFF proTecTion
This screen only appears if hot water heating and/or cold water cooling is
supplied with the unit. Unit off protection allows the unit to open the hot water
and cold water valves to a preset position when the unit is off and the outdoor air
is below the specified set point. This will keep water moving in the coils, to reduce
the chance of freezing the coils
call For cooling
This screen only appears if the unit has heating and cooling. This check box
allows for the call for cooling digital input to allow cooling and lockout out heating.
passWord managemenT
This screen allows the user to change the service password required to change
service access menus.
Microprocessor Controller for ERV20
®
This screen alloWs The user To vieW and adjusT conTroller Tcp/ip
seTTings.
This screen will appear with or without a network protocol provided with the unit.
This screen allows the user to configure the IP setting for BMS and/or when
the Web User Interface will be utilized. The controller may have a DHCP server-
assigned address or a manually-assigned static IP address. Factory settings are
shown in the screen to the left.
To change pCO Board Address parameters:
1. Power on the controller and allow several minutes to initialize.
2. Go to Network Settings menu and view pCO Board Address screen.
3. Move cursor to desired parameter by pressing the enter button. Press up and
down arrows to adjust the parameter. Press enter to accept adjusted value.
4. Once desired parameters have been entered, enable the ‘Save Settings’ option
and press the enter button.
5. Reboot the controller by cycling power to the unit. Allow several minutes for the
controller to initialize.
6. View pCO Board Address Config. If changed values did not save, contact the
factory.
The Network Settings Menus allows the user to view and modify network
settings. The service password (1000) is required to make changes.
Control Variables
Advanced
Network Settings
This screen alloWs The user To vieW and adjusT conTroller bacneT ip
conFig seTTings.
This screen will appear if the unit is set for BACnet IP and allows the user to set
the device and port settings.
bms communicaTion menu
This screen shows the current BMS protocol and the location where the BMS
system should be connected.
Menu
This screen alloWs The user To adjusT bacneT and msTp parameTers.
This screen only appears if the selected BMS protocol is set to BACnet MSTP.
Factory settings are shown in the screen to the left.
To change BACnet MSTP parameters:
1. Power on the controller and allow several minutes to initialize.
2. Go to Network Settings menu and view BACnet MSTP Config screen.
3. Move cursor to desired parameter by pressing the enter button. Press up and
down arrows to adjust the parameter. Press enter to accept adjusted value.
4. Once desired parameters have been entered, enable the ‘Save Settings’ option
and press the enter button.
5. Reboot the controller by cycling power to the unit. Allow several minutes for the
controller to initialize.
6. View BACnet MSTP Config. If changed values did not save, contact the factory.
This screen alloWs The user To vieW and adjusT conTroller modbus Tcp
slave.
This screen will appear if the unit is set for Modbus TCP and allows the user to set
device ID number.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32