•Open the pre-cut hole on the left hand side of the boiler and re-insert the collar in this hole.
•Now slide the shaft from the left into the boiler; ensure it is positioned correctly (underneath the
follower lever, see figure!)
•Bolt the shaft and the follower lever back together.
1.7 Chimney connection
The KÜNZEL pellet boiler is fitted with a forced draft fan. In order to ensure safe operation of the pellet
boiler, it is necessary to ensure that the flue gas branch of the pellet boiler has a negative pressure of at
least 10 Pa under all operating conditions. However, this negative pressure may not exceed 18 Pa under
any operating conditions. KÜNZEL recommends the use of a draft regulating device. When putting the
unit into service for the first time, the draft is to be measured and recorded when the unit is cold and
when it is operating at its maximum output setting.
The exhaust gas duct to the chimney should be as short as possible, without any bends and installed at
a slight incline. The connection to the chimney should have an aerodynamic design that curves upward.
The connector joining the furnace and the chimney must comply with EN 1856-2:2004 and have the
required identification marking (CE). In accordance with EN 1856-2:2004, non-insulated connectors
must be kept at least 40cm cm away from combustible components. We recommend the use of insulated
connectors.
The figures required for the chimney design calculations can be found in the technical data listed in
section 4on page 25. Calculated chimney diameters that are smaller than the flue gas branch of the boiler
are not permissible.
Important: Please note that the low exhaust temperatures occurring during prolonged operation may
mean that it is necessary to fit a moisture-resistant chimney (thermal conductivity factor - resistance
group I in accordance with DIN 18160/T1).
Before connecting the pellet boiler to an existing chimney, subject it to a chimney calculation or obtain
a chimney report. Before commencing with the installation it is essential to obtain the approval of your
local master chimney sweep.
It is essential to ensure that the flue gas duct is airtight. Exhaust gases could otherwise leak into the boiler
room under some circumstances. This applies in particular to the cleaning hatches on the duct elbows.
1.8 Heating connection
1.8.1 General
The PK type pellet boiler are designed for use with open or closed-circuit heating systems with a maxi-
mum operating pressure of 3 bar and a maximum flow line temperature of 95◦C.
The following safety equipment is to be installed by the building contractor:
•A pressurised expansion tank (please take account of any buffer tanks fitted to the system)
•A safety valve with a maximum actuation pressure of 3 bar at the highest point of the heat generator
•A thermometer and a manometer
9