Danfoss ICAD 600A, ICAD 1200A - Low ICM liquid temperature setting Installation guide

  • Hello! I am an AI chatbot trained to assist you with the Danfoss ICAD 600A, ICAD 1200A - Low ICM liquid temperature setting Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Installation Guide
ICAD 600A / ICAD 1200A
How to prevent ice built-up on ICAD magnets
027R9970
027R9970
© Danfoss | DCS (MWA) | 2017.10
DKRCI.PI.HV0.M1.02 | 520H12460 | 1
NOTE!
It is important to keep ICAD magnets icefree
If the media temperature is lower than -30°C (-22°F) do the following:
Use the tables below when setting the parameters for (i30) running and (i31) holding current.
T: Ambient temperature
If ambient temperate varies over time, always select the highest temperature.
In parameter i10 (password), enter: 19
In parameter i30 (running current), enter value from Table 1 (ICAD 600A) or Table 2 (ICAD 1200A)
In parameter i31 (holding current), enter value from Table 1 (ICAD 600A) or Table 2 (ICAD 1200A)
ICAD 600A i30
Parameter.
Max value
i31
Parameter.
Max value
T< 20°C (6F) 20 20
20°C (68°F) < T < 30°C (86°F) 19 19
30°C (86°F) < T < 40°C (104°F) 18 18
40°C (104ºF) < T < 45°C (113°F) 17 17
45°C (113°F) < T < 50°C (122°F) 15 15
ICAD 1200A i30
Parameter.
Max value
i31
Parameter.
Max value
T< 20°C (6F) 20 20
20°C (68°F) < T < 30°C (86°F) 18 18
30°C (86°F) < T < 40°C (104°F) 15 15
40°C (104°F) < T < 45°C (113°F) 14 14
45°C (113°F) < T < 50°C (122°F) 11 11
Table 1
Table 2
/