FläktGroup eQ Controls ABAV-S3 smoke detectors Installation and Maintenance Manual

Category
Smoke detectors
Type
Installation and Maintenance Manual
1Fläkt Woods 8811 GB 2011.09 Speci cations are subject to alteration without notice
Installation & maintenance
Control equipment
Control unit for smoke detectors
ABAV-S3
With relay contacts for controlling, for example
air handling units.
Function
The unit is designed for DIN-Rail mounting with
LED/indications on the front panel. When a smoke
detector, connected to the ABAV-S3, indicates alarm
for smoke, the ABAV-S3 unit will trigger an alarm
relay, which can be used to stop ventilation fans
and to close re dampers.
At alarm, a red LED is lit and at the same time the
alarm relay drops. When a smoke detector is indi-
cating service alarm the yellow service alarm LED
starts to blink fastly during one minute. After that,
the relay is energized and the LED is showing xed
yellow light. If the service alarm of the smoke
detector is remedied, the service alarm relay is
de-energized and the yellow LED starts to blink
slowly. Service alarm is an indication that the
smoke detector is contaminated and should
be replaced. Short circuit or interruption will ener-
gize the failure relay and at the same time a yellow
LED is lit (for interruption there is a ten seconds
delay).
If the short circuit or interruption is remedied, the
failure relay is de-energized and the yellow LED
starts to blink slowly. Test of relays: Press the reset
button during ve seconds.
Dimensions (mm)
45 62 86
52,5/3 mod.
53
29 19 10
58
Technical data
Operating voltage: 230V AC, ±10% 50-
60Hz
Energy consumption:: 1,8 VA
Alarm relay: NC+NO 250V, 8A
NC 250V, 8A
Service alarm relay: NO 250V, 5A
Failure alarm realy: NC+NO 250V, 5A
End resistor: 2,2 kOhm
Indications:
- Normal operation:
- Service alarm:
- Short circuit
- Interruption
- Alarm
Green LED
Yellow LED
Yellow LED
Yellow LED
Red LED
Mounting:: DIN-rail
Weight: 280g
Number of detectors: 30 st
Surrounding temp.: 0-50°C
Detector circuit:
Normal operation: 4-21 mA
Short circuit: > 100mA
Broken Line: < 4 mA
Service alarm: >21mA (contamina-
ted detector):
Alarm (smoke): >38mA
Duct mounted smoke detectors
The alarm relay and the failure relay outputs are
shown in alarm/no power on condition and the
service alarm relay is shown in operative/no power
on condition.
6
7
10
9
2
1
3
4
5
+
-
-
+
8
11
12
13
14
CONTROL UNIT
ABAV-S3 SD1
Terminals in
Uniguard Superflow
SDn
Terminals in
Uniguard Superflow
FAULT
ALARM
ALARM
SERVICE
1
2
3
4
5
-
+-
+
LED-03*
+
-
+
1
2
3
4
5
Rb
2,2kOhm
230VAC / 24VAC/DC
*Cable length to LED-03 max 3 m
  • Page 1 1

FläktGroup eQ Controls ABAV-S3 smoke detectors Installation and Maintenance Manual

Category
Smoke detectors
Type
Installation and Maintenance Manual