UV100, UV200 INSTALLATION & OPERATION MANUAL
7
Lamp Replacement (Annually)
The lamp should be replaced annually even if
it appears to be operating normally. UV-C
energy production diminishes over time.
1. Obtain the correct replacement lamp for
your model.
2. Disconnect power to the equipment.
3. Open the cover of the device. Allow lamp
to cool 10 minutes before touching.
4. Detach the electrical connector from the
lamp bracket and disconnect the lamp.
5. Carefully remove the UV-C lamp and
replace it with the new lamp. Refer to page
6 for instructions. Be sure to clean the
lamp of dust and fingerprints prior to instal-
lation.
6. Close the cover of the device.
7. Reconnect power.
8. Verify operation.
Do I still need an air filter?
Yes. The Comfort Plus™ UV-C lamp is designed to be
used in addition to a dust filter or electronic air cleaner
and the filtration of dust particles will also aid in keeping
the bulb(s) of the Comfort Plus™ UV-C lamp unit clean.
However, filters are inefficient at dealing with micro-
scopic bacteria, molds, and viruses and are incapable
of preventing mold from growing on a surface. The
Comfort Plus™ UV-C lamp contributes significantly to
the reduction of the small microbial organisms that pass
through filters and into the general air system.
Proper Clean-Up Technique In Case Of Lamp
Breakage
●
Wear protective gloves, eyewear and mask.
●
Sweep the broken glass and debris into a plastic
bag, seal the bag, and dispose of properly.
Contact your local waste management office for
proper disposal.
●
Do not use a vacuum cleaner. Do not
incinerate.
Lamp Disposal
Dispose of your spent UV-C lamps at your
local recycling center. You may also send your
spent lamps in the same container you
received your replacement lamps to:
White-Rodgers UV Lamp Reclamation
1112 Industrial Park Drive
Royse City, TX 75189
MAINTENANCE AND TROUBLESHOOTING
• Check that the lamp connector is securely
attached to lamp.
• Check that the fuse is in good working
order. Replace if necessary.
• Check that proper power is being supplied
to the device and that switch lights when
turned on.
• Lamps should be cleaned every six (6)
months to remove any dust accumulation on
the bulbs that might lessen the effectiveness
of the UV-C light. The Comfort Plus™ UV-C
light bulbs have a service life of 9,000 hours,
or approximately 375 days.
Fuse Replacement
1. Disconnect power cord.
2. Unscrew the knob marked "Fuse" and
remove fuse.
3. Install new fuse and screw knob back in
place. Use a 3A/250V fast-acting glass fuse.
4. Reconnect power cord.
Mercury Hazard. Do Not Break.
Each UV-C lamp contains a small amount of Mercury.
May cause redness or irritation. Use proper disposal
techniques in case of breakage.
WARNING
Replacement Parts Part No.
UV-C Lamp UVP-06207
Electronic Ballast (UV100) UVP-06212
Electronic Ballast (UV200) UVP-06213
Power Cord (120V) UVP-212261-00
Power Cord (240V) UVP-212107-00
Power Cord Receptacle UVP-212106-00
Cover Interlock Switch UVP-212108-00
Lighted On/Off Switch UVP-750-0026-001
Fuseholder UVP-212225-00
Fuse UVP-750-0108-001
Burn Hazard.
During replacement, allow lamps to cool 10 minutes
before removing them. Personal injury may result.
WARNING